ML080790104

From kanterella
Jump to navigation Jump to search

Response to Request for Additional Information Request for Relief Number 06-CN-003, Use of Polyethylene Material in Nuclear Safety Related Piping Applications
ML080790104
Person / Time
Site: Catawba  
Issue date: 03/13/2008
From: Morris J
Duke Energy Carolinas, Duke Power Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
TAC MD3729, TAC MD3730
Download: ML080790104 (33)


Text

JAMES R MORRIS Duke MRt En er Vice President Catawba Nuclear Station 4800 Concord Road / CNO1 VP York, SC 29745-9635 803 831 4251 803 831 3221 fax March 13, 2008 U.S. Nuclear Regulatory Commission Attention:

Document Control Desk Washington, D.C.

20555

Subject:

Duke Power Company LLC d/b/a Duke Energy Carolinas, LLC (Duke)

Catawba Nuclear Station, Units 1 and 2 Docket Numbers 50-413 and 50-414 Request for Relief Number 06-CN-003 Use of Polyethylene Material in Nuclear Safety Related Piping Applications (TAC Numbers MD3729 and MD3730)

References:

1. Letters from Duke to NRC, same subject, dated October 26, 2006 and June 21, 2007.
2. Requests for Additional Information (RAIs),

provided electronically to Duke on February 4, 2008.

The Reference 1 letters comprising Duke's original request for relief submittal and first RAI response supported a proposed alternative of utilizing polyethylene material in lieu of steel material in piping associated with the emergency diesel generator jacket water coolers and other nuclear safety related piping applications.

The NRC provided additional RAIs in conjunction with this submittal via the Reference 2 transmittal.

The attachment to this letter constitutes Duke's response to these additional RAIs.

The format of the response is to restate each NRC question, followed by our response.

Duke is requesting NRC review and approval of this request for alternative by March 31, 2008.

There are no regulatory commitments contained in this letter or its attachment.

4-r7 www. duke-energy. com

Document Control Desk Page 2 March 13, 2008 If you have any questions concerning this material, please call L.J. Rudy at (803) 831-3084.

Very truly yours, James R.

Morris LJR'/s Attachment

Document Control Desk Page 3 March 13, 2008 xc (with attachment):

V.M.

McCree, Acting Regional Administrator U.S. Nuclear Regulatory Commission, Region II Atlanta Federal Center 61 Forsyth St.,

SW, Suite 23T85

Atlanta, GA 30303 A.T. Sabisch, Senior Resident Inspector U.S. Nuclear Regulatory Commission Catawba Nuclear Station J.F. Stang, Jr., Senior Project Manager (addressee only)

U.S. Nuclear Regulatory Commission Mail Stop 8-G9A Washington, D.C. 20555-0001

Document Control Desk Page 4 March 13, 2008 bxc (with attachment):

R.D. Hart L.J. Rudy D.L.

Ward E.W.

McElroy M.L. Arey, Jr.

S.S. Lefler, Jr.

M.A; Pyne M.J. Ferlisi R.N. McGill Document Control File 801.01 RGC File NCMPA-1 NCEMC PMPA SREC ELL-EC050

Attachment Response to NRC Requests for Additional Information (RAIs)

Attachment Page 1

Request for Additional Information on the NRC Staff Review of Relief from ASME Code Requirements to Install Polyethelyne Piping at Catawba Units 1 and 2 (TAC MD3729 and MD3730)

The NRC staff has had scoping discussions with representatives of Duke Energy to determine a path forward to enable the staff to complete its review of the Catawba Units 1 and 2 relief request to install polyethylene pipe in the essential service water system.

The principal staff concern has been the inability to perform effective volumetric examinations of fused joints.

A meeting was held on December 7, 2007 at the Catawba plant site for further discussions on the items below.

1. Visual examination of fused joints.
a. The NRC staff is interested in qualification of visual examination procedures and personnel.

It is not clear to the staff that adequate guidance is provided in ASME Code Case N-.

755 in this area.

The staff is interested in reviewing a specific proposal by the licensee in this area.

The licensee should address use of physical samples of acceptable and unacceptable joints in training, procedure development, and qualification of visual examination personnel.

Duke Response Physical samples of visually acceptable and unacceptable joints will be utilized for the training of visual examination personnel.

Visual examination procedure qualification will use a performance demonstration and use samples containing at least ten flaws.

Five flaws will be used for the visual examination procedure qualification and all ten flaws will be used for the personnel demonstration using the visual examination procedure.

b. The NRC staff believes that it is essential that visual examination of fused joints be performed on both the inside and outside of the joint at the time of fabrication.

The licensee should address its plans for performing visual examination of the inside of the joint.

Duke Response Visual examination of the inner joint bead will be performed as an additional quality check and as additional assurance that there were not any equipment or process problems during the joining process.

This Attachment Page 2

examination will be performed in accordance with a new Duke procedure that will be written to address the inner joint bead.

Pictures of the interior beads of samples will be used to be consistent with what the inspector sees using remote examination methods.

The visual acceptance criteria for bead appearance will be included in the visual examination procedure.

In addition, physical samples of visually acceptable and unacceptable joints will be available to provide the inspector with supplemental visual comparison standards to use during visual examination.

Following the meeting at Catawba on December 7, 2007, a number of fused joints were made using parameters outside of the procedure limits and also at the procedure limits.

These samples were then examined and the results were documented in the December 19, 2007 Materials Engineering and Lab Services Report (Metallurgy File #3895 - ).

These samples provide some examples of fused joint beads that would be acceptable and unacceptable.

  • In-process inner joint bead inspections shall be performed only on pipe-to-pipe joints that are made in the field.

Exempting the inspection of joints in fittings is justified because of the more controlled conditions for fusing and inspecting that exist in a manufacturing facility compared to possible field installation conditions.

Fittings also have a greater wall thickness than the pipe and are designed to be stronger than the pipe Joints.

  • Beads on the fused joints will not be removed for the piping addressed by this relief request.
c. The NRC staff believes that, to the extent feasible, the piping design should include provisions for future access for examination of all joints from the inside surface.

The licensee should address its plans for designing the piping for access for future examinations.

Duke Response The piping design shall include the following provisions for future examination:

Attachment Page 3

All joints will be identified and located on the appropriate drawings.

A tee with a blank flange, spool piece, flanged elbow, or other method will be installed at each end of the piping run to allow future access into the pipe.

2.

System leakage testing.

The NRC staff believes that since the essential service water piping system is being redesigned, the new design should include provisions to. enable the system leakage testing requirements of the ASME Code,Section XI, IWA-5000 via either pressure drop testing or by determining the change in flow between the ends of the piping, i.e.,

IWA-5244(b) (1).

The licensee should address its plans for designing the piping to meet the system leakage requirements of Section XI.

Duke Response Piping addressed by this relief request will meet the Section XI, IWA-5000 requirements for system pressure tests.

The polyethylene piping is being installed in accordance with the Duke Section XI program for repairs and replacements.

Polyethylene material is being used to replace existing material in an existing system.

Duke plans to meet the pressure testing requirement as it currently exists with the nuclear service water system flow balance.

3.

Process controls.

The NRC staff recognizes the importance of process controls in ensuring that fused joints provide high assurance of pressure boundary integrity throughout the service life of the piping.

The NRC staff plans to witness joint fabrication at. the Catawba site during its upcoming meeting and discuss the adequacy of the process controls.

In these discussions the NRC staff anticipates reaching agreement on whether additional measures may be necessary beyond those required by Code Case N-755.

The licensee should provide a summary of the discussion on process control from the meeting on December 7, 2007.

Duke Response The NRC Staff witnessed fusing of polyethylene piping during the December 7, 2007 visit to Catawba.

Pipe-fusing was performed in accordance with the Duke polyethylene pipe joining procedure which was prepared in accordance with Supplement IX requirements of the Catawba relief request.

(Requirements presented in the Catawba relief request are Attachment Page 4

based on Code Case N-755 requirements that were in draft form at the time of the Catawba relief request.)

The Duke joining procedure meets the requirements of paragraph QF-230 b) of the Catawba relief request.

The essential variables specified in this paragraph are qualified by testing documented by Plastic Pipe Institute TR-33.

Training of the fusion machine operator will be similar to Appendix A to Supplement IX of the Catawba relief request.

Qualification of the fusion machine operator will be performed in accordance with Supplement IX, Article III of the Catawba relief request.

During the December 7, 2007 meeting, the NRC Staff wanted to assure that data logger results are accepted by QC before the joint is considered acceptable.

This issue is addressed by a final QA review that is performed by Duke for any document that is a QC record.

Paragraph 5120(c) of the relief request is clarified to read that visual examination by QC Inspection is required before piping with fused joints is permanently covered in the burial trench.

Revised Page 27 of the relief request is included with this response (Enclosure 3).

Following the December 7, 2007 meeting, a number of sample joints were fabricated using essential parameters at joining procedure limits and outside the joining procedure limits and were then evaluated.

This work is documented in the December 19, 2007 Materials*Engineering and Lab Services Report (Metallurgy File #3 895 - ).

4.

In-Process Destructive Examination of Joints.

The licensee has proposed developing a program of in-process destructive examination of joints.

The NRC staff has

.encouraged the licensee to develop the plans for such a' program.

During the upcoming meeting the NRC staff plans to discuss specific licensee proposals in this area, including but not limited to sample selection criteria (blindness and randomness), sample testing frequency, and sample testing methods and acceptance criteria.

The licensee should provide a discussion of its proposal to discuss in-process destructive examination of joints..

Duke Response This is Duke's first installation of polyethylene piping in ASME Section III service and an in-process destructive Attachment Page 5

examination of joints will be used to provide an' additional quality check for field fabricated polyethylene pipe joints.

TESTING FREQUENCY A minimum of 10% of the field pipe joints fabricated during a production period on each machine shall be tested.

A production period shall be a single shift of operation for each fusion machine.

In addition, one field fabricated joint shall be selected at random sometime during every four production periods for testing.

TESTING REQUIRMENTS Testing shall be performed in accordance with ASTM F 2634-07, Standard Test Method for Laboratory Testing of Polyethylene (PE) Butt Fusion Joints using Tensile-Impact Method, with the exception of the number of test specimens tested from each joint.

One test specimen will be tested from the first joint of each production period.

Four test specimens will be tested from each joint selected at random for testing with the test specimens being taken at each 90 degree segment in the joint.

ACCEPTANCE CRITERIA Test specimens shall be evaluated by Engineering in accordance with Appendix Xl of ASTM F 2634-07.

A valid failure of any test specimen will be evaluated in accordance with the Duke corrective action program.

SELECTION OF JOINTS FOR TESTING The first joint fabricated on each machine during each production period shall be tested.

This first joint may be fabricated using pipe material from the same lot of pipe material as the pipe material that is being installed.

To meet the blindness and randomness selection criteria, the joint that is selected each four production periods from piping that is being installed shall be selected at random.

In-process destructive examination shall be performed only on pipe-to-pipe joints that are fabricated in the field.

Exempting the testing of joints in fittings is justified because of the more controlled conditions for fusing that exist in a manufacturing facility compared to possible field installation conditions.

Pipe-to-fitting joints are exempted from destructive testing.

Attachment Page 6

BASIS FOR TESTING FREQUENCY The testing frequency is based on the testing frequency requirements of ASME Section III, Division 2 Code for Concrete Reactor Vessels and Containments.

Table CC-5200-1 provides requirements for conducting strength tests for concrete.

Testing of a minimum of 10% of the polyethylene pipe joints made during a production period matchesSection III, Division 2 Code requirements for testing frequency.

5.

The components affected by the request should be stipulated as the 12 nominal diameter piping to the emergency diesel generator jacket water coolers.

Duke Response This relief request applies to the use of 12-inch nominal diameter supply and return piping to and from the diesel generator jacket water coolers.

6.

In the draft response to Question 1 above (provided during the January 17, 2008 meeting) pertaining to performance-based qualifications, the licensee visual examination procedure qualification referenced Section V, Article 14, 2004 Edition, Intermediate Rigor.

The staff does not review Section V.

However,Section V, Article 14, Intermediate Rigor has multiple performance demonstrations.

For the request alternative, Catawba should describe the performance-based process (T-1471 a, b, or c).

The staff does not support (d) at this time.

As discussed in the public meeting on January 17,

2008, specifying the number of test samples to be used in the performance-based qualification for visual examination would be an acceptable approach for addressing Question 1.

Duke Response The response to Question 1 has been revised to delete reference to Section V and the performance based process is described.

The number of test samples used in the performance based qualification is specified.

7.

In the response to Question 1 above pertaining to visual examination of fittings, it may be appropriate to add to the justification that the fitting wall is thicker than-the straight pipe wall being attached to it thus the fittings joints are designed to be stronger than the pipe joints.

In response to Question 2, we would appreciate a discussion on the visual examination of pipe to fitting joints.

Attachment Page 7

Duke Response The greater thickness of fittings is now referenced in paragraph 3 of the Duke response to Question lb.

The visual examination of pipe-to-fitting joints will be conducted the same as for pipe-to-pipe joints.

The thicker walled fitting will be counter-bored to the same thickness as the matching pipe as illustrated by Figure 4421.2-1 of the Duke relief request.

8.

Regarding in-process destructive examination, there is some concern that the one impact tensile specimen from the random test may not be sufficient to detect the range of potential problems the test is intended to uncover; for example the effects from thermal differentials within the pipe wall from the sun shining on black OD surface while the ID may be. at night time temperatures.

Duke Response Four test specimens from each joint tested at random will be tested in accordance with ASTM F 2634-07 with the test specimens being taken at each 90 degree segment in the joint.

This will ensure that thermal differential effects from solar heating are addressed by the testing.

This requirement has been added to the "Testing Requirements" of the Duke response to Question 4.

9.

In the relief request paragraph QF-131.2(a) test specimens of butt fused pipe shall have the bead remaining on, while paragraph 4422.1 (mislabeled as 4421.1) permits the removal of the bead at the owner discretion.

Why is there a difference between testing and application?

Duke Response Duke has decided not to remove the beads for piping addressed by this relief request.

Paragraph 4421.1 has been removed from the relief request as shown by revised Page 25 which is included with this response (Enclosure 3).

10.

10 CFR, Part 50, Appendix B, Criterion IX, "Control of Special Processes," require the use of qualified personnel and procedure.

In the relief request, paragraph QF-223 provides the testing qualification criteria for the fusion procedure specification (FPS).

QF-230 provides generic parameters for by-passing the procedure testing qualifications.

According to

PPI, TR-33/2006, not all HDPE material is capable of making an Attachment Page 8

acceptable joint.

The justification for QF-230 is not clear in the request, nor is the ability to trace back to the qualification testing data.

Information is needed to clearly explain the basis for the qualification of the fusion procedure specification.

This information needs to explain how the various elements of the qualification are related and requirements for qualification are satisfied.

This information should include aspects such as the material and material supplier, the pipe manufacturer, the joint fabricator, pipe size and wall thickness, the independent

tester, the testing data results, and the industry standards and/or code of federal regulation sections (e.g. 49 CFR 192) used to establish qualification requirements and acceptance criteria and audit requirements.

Information is also needed to provide the NRC with assurance that QA program requirements related to the qualification of the FPS are being met.

Duke Response The joining procedure of theCatawba relief request is based on requirements of TR-33.

The TR-33 joining procedure specification was qualified by testing performed under the direction of the Plastic Pipe Institute.

In addition, testing is performed by the pipe manufacturer to qualify the joining procedure specification.

Performance Pipe letter dated January 24, 2008 from Larry Petroff provides specific qualification information and testing results and this information is included with the response to this relief request (Enclosure 2).

Duke has audited Performance Pipe to 10 CFR 50, Appendix B and Performance Pipe (Brownwood, TX) has been added to the Duke Qualified Supplier List for the Product/Service of High Density Polyethylene (HDPE) pipe.

TR-33 2006 Appendix C states that materials that have been pre-qualified to be joined are within the nominal melt index range of 0.05 to 0.25 gm/10 minutes and a nominal density range of 0.936 to 0.955 gm/cc.

The Catawba material is qualified by TR-33 with a melt index < 0.15 gm/10 minutes and a density range of 0.947 to 0.955 gm/cc.

Additional confidence in the joining process was established by the laboratory examination of piping test specimens which were joined at procedure limits and outside procedure limits.

Reference the December 191 2007 Materials Engineering and Lab Services Report (Metallurgy File #3895 - Enclosure 1).

These test specimens demonstrated that there is a broad range for Attachment Page 9

the essential joining parameters.

The joining procedure requires joining parameters to be within a narrow band in this broad range.

Finally, the destructive testing and random testing addressed in Question 4 provides routine and ongoing assurance of the acceptability of the joining process.

Attachment Page 10 December 19, 2007 Materials Engineering and Lab Services Report (Metallurgy File #3895)

PDuke EEnergy Nuclear Generation Materials Engineering & Lab Services December 19, 2007 Memorandum to:

Subject:

Steve Lefler, Nuclear Generation, Duke Energy Corporation CNS - HDPE Fusion Joint Research Metallurgy File #3895 Fusion joints were created in 12"-diameter HDPE pipe under varying process conditions. An approximate 5-inch arc length of fused pipe was provided from each sample. Pipe wall thickness was 1.2 inches.

Each joint was photographed on the ID and OD, and then cross-sectioned to examine the bead structure. The cross-section was prepared to a 600-grit finish and then heated with a heat gun at -500'F to expose the fused area. Photographs of each sample are attached.

In general, there was more variation across the samples in the visual appearance of the bead than there was in the size of the fusion zone. Fusion Joint #1, created at low temperature and low pressure, had an obviously wider fusion zone than the other samples, but the external bead size was small.as well.

If the Metallurgy Lab can be of further assistance, please call us at (704) 875-5326.

Susan Anderson, P.E.

Senior Engineer Duke Energy Corporation 13339 Hagers Ferry Road MG03A6 Huntersville, NC 28078

Page 2, Sample No. 3895 Fusion joint sections as received.

Page 3, Sample No. 3895 FUSION JOINT #1 0D TEMPERATURE:

280'F PRESSURE:

150 psig

Page 4, Sample No. 3895 DFUSION JOINT #2 OD TEMPERATURE:

345°F PRESSURE:

450 psig

Page 5, Sample No. 3895 OD 7FUSION JOINT #3 TEMPERATURE:

575°F PRESSURE:

492 psig

Page 6, Sample No. 3895 FUSION JOINT #21 OD TEMPERATURE:

Not reported PRESSURE:

Not reported Deliberately misaligned and allowed to stay apart too long after heat plate was removed

Page 7, Sample No. 3895 FUSION JOINT #33 TEMPERATURE:

591°F PRESSURE:

200 psig

Page 8, Sample No. 3895 OD

DEMO 8 JOINT #7 TEMPERATURE

300°F PRESSURE:

500 psig

Page 9, Sample No. 3895 O...DEMO 9 JOINT #8 TEMPERATURE:

400'F PRESSURE:

300 psig

Page 10, Sample No. 3895 OD DEMO 10 JOINT #9 TEMPERATURE:

450OF PRESSURE:

300 psig

Page 11, Sample No. 3895

.DEMO 11 JOINT #10 TEMPERATURE:

275°F PRESSURE:

550 psig Performance Pipe Letter Dated January 24, 2008 from Larry Petroff

A gmsft V

&mow U

Aww Oiw CP*

IPC Larry J. Petroff Technical Service Specialist 139 Imperial Way Bogart, GA 30622 Telephone: 706-208-1031 petrol icpchem.com www.DriscoPlex.com January 24, 2008 Fusion Qualification Report for XTIO Resin to Itself:

Purpose The purpose of this set of testing was to qualify the following fusion procedures on pipe made at Performance Pipe using Total XT10 resin:

Generic PE Pipe Heat Fusion Procedure Plexco HDPE Pipe Heat Fusion Procedure Driscopipe HDPE Heat Fusion Procedure Driscopipe 8000/8100 Heat Fusion Procedure This testing satisfies the DOT fusion qualification requirements for PE pipe to be used in gas distribution systems as detailed in DOT 192.283.

Requirements Tensile elongation per ASTM D638 of 25% or greater. Minimum hydrostatic burst pressure per ASTM D1 599 of 580 psi (corresponds to 2900 psi stress)'

Testing Pipe made at Performance Pipe using XT1 0 resin was fused to itself.

Various fusion parameters were used to fuse the pipe to cover all fusion procedures being qualified (as listed above). The pipe was then subjected to quick burst testing and tensile elongation testing. See attached table.

Findings As detailed in the following test results, all samples from all testing passed their respective tests.

(Excerpted from a Fusion Qualification report by Barrett Jesseph dated July 10, 2006.)

Larry J. Petroff Technical Information. By using any Technical Information contained herein, Recipient agrees that said Technical Information is given by Performance Pipe for convenience only, without any warranty.or guarantee of any kind; and is accepted and used at your sole risk. Recipients are encouraged to verify independently any such information to their reasonable satisfaction. As used in this paragraph, "Technical Information" includes any technical advice, recommendations, testing, or analysis, including, without limitation, information as it may relate to the selection of a product for a specific use and application.

Paqe 2 Like Material Butt Fusion: XT10 Resin fused to XT10 Resin Fusion Conditions Pipe rReference Result Heater Interfacial Size Test

, LTe__mperature Pressure

.Method 430 F 75 psi 4" DR r Tensile

!FDOT 192.283(a)(3)

PASS: Elongation of greater 11 5 samples ASTM D 638 than 300% on all samples

.tested Quick Burst DOT PASS: Burst Pressures (psi) 5 samples 192.283(a)(1)(i) of 684, 678, 702, 711, 706 tested ASTM D 2513 All samples were ductile in ASTM D 1599 appearance and all breaks occurred in pipe section with no separations at the fusion joints 430 F 75 psi 6" DR 11 Tensile 5 samples tested_---..

DOT 192.283(a)(3) I ASTM D 638 PASS: Elongation of greater than 400% on all samples Quick Burst 5 samples tested DOT 192.283(a)(1)(i)

ASTM D 2513 ASTM D 1599 PASS: Burst Pressures (psi) of 694, 739, 741,742, 742 All samples were ductile in appearance and all breaks occurred in pipe section with no separations at the fusion joints 500F 150psi 6'R Tensile DDOT 192.283(a)(3)

PASS: Elongation of greater 11 5 samples I ASTM D 638 than 400% on all samples

_tested j

Quick Burst DOT PASS: Burst Pressures (psi) 5 samples 192.283(a)(1)(i) of 687,742, 695, 696, 700 tested ASTM D 2513 All samples were ductile in ASTM D 1599 appearance and all breaks occurred in pipe section with no separations at the fusion.

________________ joints 500F 75 psi 4" DR

[Tensile F DOT 192.283(a)(3)

PASS: Elongation of greater 11 I5 samples IASTM D 638 than 300% on all samples I tested Quick Burst DOT PASS: Burst Pressures (psi) 5 samples 192.283(a)(1 )(i) of 687, 743, 692, 728, 740 tested ASTM D 2513 All samples were ductile in ASTM D 1599 appearance and all breaks occurred in pipe section with f no separations at the fusion SJ......

J jintsi

Page 3 Performance Pipe Test Requests:

Tests using Performance Pipe Fusion Parameters (430F / 75 psi interfacial pressure)

TR 1430:

4" DRI 1, XT1 0 fused to 4" DR1 1, XT1 0 (Butt Fusion)

Quick Burst Tensile Elongation TR 1432:

6" DR1 1, XT10 fused to 6" DR1 1, XT10 (Butt Fusion)

Quick Burst Tensile Elongation Tests using Driscopipe 8000 Fusion Parameters (500F / 150 psi interfacial pressure)

TR 1445:

6" DR11, XT10 fused to 6" DR11, XT10 (Butt Fusion)

Quick Burst Tensile Elongation Tests using Driscopipe HDPE Fusion Parameters (50OF / 75 psi interfacial pressure)

TR 1465:

4" DR1 1, XT10 fused to 4" DRI 1, XT10 (Butt Fusion)

Quick Burst Tensile Elongation Revised Relief Request Pages

Requirements for Polyethylene Piping Request for Relief Serial Number 06-CN-003

-4422 Identification of Joints by Fusing Operator Each fusing operator shall apply the identification mark assigned to him by Duke Power Company LLC adjacent to allI permanent fused joints or series of joints on which he fuses.

The marking shall be 1 ft (.3 m) or less from the fusion bead and shall be done with permanent metallic paint marker or stenciling marker.

Paragraph 4421.1 should have been paragraph 4422.1 but is now deleted.

-4423 Repairs Repairs of a fused Joint is not allowed. All unacceptable joints shall be cut out and replaced.

-4430 Fusing Data Acquisition Recorder The fusion machine will have an automatic acquisition data recorder attached to it. The recorder shall record essential variables of the fusion process.

a) Failure to run the recorder during the fusion process shall be cause to fail the, fusion joint being made.

b) The butt fusion joint record should be compared to the Fusion Procedure Specification (FPS) to ensure that the proper butt fusion parameters~and procedures were followed. Any parameter out of the approved range will be cut out and re-fused using the correct FPS.

-4500 ASSEMBLY AND ERECTION

-45 t0 General Distortion resulting in a pipe bending radius > 30 times the pipe outside diameter is acceptable for piping with a DR of 9 and 11.

-4520 Flanged Joints using PE material a) Flanged connections are only permitted for the joining of polyethylene pipe to metallic pipe or piping components. The polyethylene flange connection shall be constructed using a polyethylene flange adapter having a DR ratio equal to the attached PE pipe and shall be fusion joined to the attached polyethylene piping.

b) The polyethylene flange adapter shall be connected to the metal flange using a metallic backing ring and as a minimum having the same pressure rating as the mating metallic flange.

c) Before bolting up, flange faces shall be aligned to -the design plane within 1/16 in/ft measured across any diameter; flange bolt holes shall be aligned within 1/8 in. maximum offset. Any damage to the gasket seating surface on the PE flange which would prevent gasket seating shall be evaluated.

Page 25

Requirements for Polyethylene Piping Request.tbr Relief Serial Number 06-CN-003

-5000 EXAMINATION

-5100 GENERAL REQUIREMENTS

-5110 Procedures

-5111 Examination of manufactured PE piping subassemblies, -fittings and installed PE piping systems shall be in accordance with the requirements of this section of this Relief Request.

-5112 Examination Procedures. All examinations performed under this Relief Request shall be executed in accordance with detailed written procedures which have been proven by actual demonstration, to the satisfaction of the ANil. Written procedures, records of demonstration of procedure capability, and personnel qualification shall be made available by the Manufacturer or Duke Power Company LLC to the ANII on request.

-5120 Visual Examination of Fused Joints a) A VT-i visual examination shall be performed on all fused joints b) The VT-i visual examination shall be conducted:

1) Upon the completion of cooling period and
2) after the fused joint data obtained in -4430 has been reviewed.

c) The visual examination by QC Inspection is required before piping with fused joints is permanently covered in the burial trench.

-5300 ACCEPTANCE STANDARDS

-5310 General Requirements Unacceptable joints shall be removed. Repair of unacceptable joints is not permitted.

-5320 Visual Acceptance Criteria.

-5321 Thermal fusion butt joints shall meet the following:

a) shall not have an improper fusion bead configuration, b) shall not show evidence of cracking or incomplete fusion, c) shall not be visually angled or offset. The ovality offset shall be less than 10% of the minimum wall thickness of the fused components, d) the cleavage between fusion beads shall not extend to or below the outside diameter pipe surface see (Figure -5321-1),

Page 27