Inservice Inspection Summary Report
ML070100524
Person / Time
Site: Kewaunee 
Issue date: 01/08/2007
From: Gerald Bichof
Dominion Energy Kewaunee
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
06-748
Download: ML070100524 (129)


Text

1)ominion Energy Kewaunee, Inc.

>(I00 l)om1111o11 I I ~ L I I C V ~ ~,

Glen Allcn, VA 2 Z O O 0 January 8, 2007 U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555 Serial No.06-748 KPSILICIGR: R3 Docket No.

50-305 License No. DPR-43 DOMINION ENERGY KEWAUNEE, INC.

KEWAUNEE POWER STATION 2006 INSERVICE INSPECTION

SUMMARY

REPORT As required by American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code Section XI, 10 CFR 50.55a, and Wisconsin Administrative Code Department of Commerce, Comm 41.55(3), various inservice inspection (ISI) examinations were performed during the 2006 refueling outage at the Kewaunee Power Station (KPS). The refueling outage took place from September 2, 2006 through October 26, 2006. This letter transmits the lnservice lnspection Summary Report as required by paragraph IWA-6230 of ASME Section XI.

Two separate ASME Section XI inservice examination programs are implemented at KPS. One program is for pressure retaining pipinglvessels and component supports, and the other program is for the metal containment.

The 2006 refueling outage inservice inspections met the requirements of these two distinct inspection program intervals as listed below:

The second inspection year of the first period of the fourth interval for Class 1, Class 2, and Class 3 component inspections were performed. The inspections met the requirements of ASME Boiler and Pressure Vessel Code Section XI, 1998 Edition, 2000 Addenda with implementation in accordance with the KPS Fourth Ten-Year lnservice lnspection (ISI) Program 2004-201 4.

The second inspection year of the third period of the first interval for Class MC components inspections were performed. The inspections met the requirements of ASME Boiler and Pressure Vessel Code Section XI, 1992 Edition, 1992 Addenda with implementation in accordance with the KPS First Ten-Year lnservice lnspection (ISI) Class MC Program 1996-2006.

Serial No.06-748 Page 2 of 3 The following examinations and tests were performed for Class 1, Class 2, and Class 3 components and their supports:

Reactor vessel upper and lower internals examination, Steam generator shell circumferential weld examination, Reactor coolant pump main flange bolting and Number 1 seal housing bolting examination, Class 1 valve bodies examination, Reactor coolant pump flywheel examination, Class 1, Class 2, and Class 3 piping and component supports and hangers examinations, Class 1 and Class 2 steam generator primary manway bolting, pressurizer manway bolting, flange bolting, and valve bonnet bolting examinations, Class 1 system leakage test, and Class 2 and Class 3 system leakage tests.

The following items were examined for the Class MC reactor building containment vessel:

Accessible surface areas, Circumferential weld, Seals and gaskets, Airlocks, and Pressure retaining components.

In addition, the following examinations were conducted in excess of ASME Boiler and Pressure Vessel Code Section XI, 1998 Edition, 2000 Addenda requirements:

Nuclear Regulatory Commission Regulatory Guide 1.14, Revision 1, "Reactor Coolant Pump Flywheel Integrity," dated August 1975.

Nuclear Regulatory Commission Bulletin 2003-02, "Leakage From Reactor Vessel Lower Head Penetrations and Reactor Coolant Pressure Boundary Integrity," dated August 21, 2003.

The following item was examined in accordance with KPS Technical Specifications:

Eddy current testing of steam generators.

Documentation summarizing the inservice inspection activities and results relative to the KPS 2006 refueling outage is provided in enclosures 1-9 of this letter. The final reports for each of these examinations are maintained in the Quality Assurance/Quality Control Records Vault at KPS.

The next refueling outage at KPS is tentatively scheduled for the spring of 2008.

Serial No.06-748 Page 3 of 3 If you have questions or require additional information, please feel free to contact Mr.

Gerald Riste at 920-388-8424.

Very truly yours, Gerald T. Bischof W Vice President - Nuclear Engineering Enclosures

1. Summary of Recordable Indications (Rls) and Disposition.
2. Summary of Class 1 and Class 2 RepairlReplacement Activities for Components 1 -Inch in Diameter or Smaller.
3. Form NIS-1 Owner's Report for lnservice lnspections of Class 1, Class 2, and Class 3 Components for Fourth Ten-Year Interval.
4. Form NIS-1 Owner's Report for lnservice lnspections for Class MC Components.
5. Form NIS-2 Owner's Report for RepairIReplacement Activities (46 Total).
6. Examination Summary for Class 1, Class 2, and Class 3 lnservice Inspection Program for Fourth Ten-Year Interval.
7. Examination Summary for lnservice lnspection Class MC Program For First Ten-Year Interval.
8. Summary of Examinations That Were Limited by Geometric, Metallurgical, or DesignIAccess Restrictions and Associated Data Sheets (1 Total).
9. Examination Summary for Steam Generator Eddy Current Testing.

Commitments made by this letter: NONE cc:

Regional Administrator U. S. Nuclear Regulatory Commission Region Ill 2443 Warrenville Road Suite 21 0 Lisle, l llinois 60532-4352 Mr. R. F. Kuntz U.S. Nuclear Regulatory Commission Mail Stop 0-7-Dl A Washington, D. C. 20555 NRC Senior Resident Inspector Kewaunee Power Station

Serial No.06-748 2006 INSERVICE INSPECTION

SUMMARY

REPORT

SUMMARY

OF RECORDABLE INDICATIONS (Rls) AND DISPOSITION KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

Serial No.06-748 Docket No. 50-305 Page 1 of 2

SUMMARY

OF RECORDABLE INDICATIONS (Rls) AND DISPOSITION TYPE OR LOCATION OF RECORDABLE INDICATION (RI)

METHOD

1. Steam generator 1 B shell circumferential Volumetric (UT) weld NO. OF Rls 1 weld
2. Reactor vessel upper internals Visual (VT-3) 1 thermocouple conduit
3. Valve bonnet bolting Visual (VT-3) 3 valves
4. Flange bolting Visual (VT-1 and VT-3) 1 flange
5. System leakage pressure tests Visual (VT-2) 30 items
6. Reactor building containment vessel General Visual and VT-3 1 plate

Serial No.06-748 Docket No. 50-305 Page 2 of 2 Dispositioning of Class 1, Class 2, and Class 3 indications has been completed in accordance with the rules of American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code Section XI, 1998 Edition, 2000 Addenda for Fourth Ten-Year Interval examinations, and ASME Boiler and Pressure Vessel Code Section XI, 1992 Edition, 1992 Addenda for Class MC components. Applicable codes, standards, and engineering criteria were used to disposition indications associated with the non-code-required examinations. Recordable indications for Class 1, Class 2, Class 3, and Class MC have been dispositioned as summarized below:

1. Recordable indications were recorded on steam generator 1 B circumferential girth weld SG-W1 0. The 43 separate indications were previously recorded during the 1996 and 2001 refueling outages. A comparison of the length, amplitude, and position of the signal response between 1996, 2001, and 2006 revealed no discernible changes, indicating that the flaws are stable and have not grown in size.

Indications were acceptable either by ASME Boiler and Pressure Vessel Code Section XI, 1998 Edition, 2000 Addenda or by fracture analysis as provided in Westinghouse Electric Corporation WCAP-11476, Revision 3, "Handbook on Flaw Evaluation Kewaunee Unit 1 Steam Generator Upper Shell to Cone Weld," May 1991 and evaluation by Kewaunee Power Station (KPS) during the 1996 and 2001 refueling outages.

2. A recordable indication was recorded on the reactor vessel upper internals upper support plate thermocouple conduit at location C-3. The separated conduit cable was previously recorded in 1995 and 2004. The separated conduit at location C-3 showed no noticeable change in separation and was previously determined to be acceptable under the KPS corrective action program.
3. Visual (VT-3) indications recorded on valve bonnet bolting (3 valves) were repaired, reexamined and accepted by KPS maintenance and inservice inspection personnel and reviewed by the authorized nuclear inservice inspector.
4. Visual (VT-1 and VT-3) indications were recorded on a flange for RCS bypass flow.

The indication involved the actual length of the flange studs versus the length called out on "Quality Part Tag." The indication was evaluated by KPS engineering personnel and found to be acceptable.

5. Visual (VT-2) indications recorded during system leakage pressure tests (30 items) were: (1 ) evaluated and accepted by KPS maintenance engineering, program engineering, or inservice inspection personnel; or (2) repaired, reexamined, and accepted by KPS maintenance engineering, program engineering, or inservice inspection personnel. The 30 items were reviewed by the authorized nuclear inservice inspector.
6. General Visual and VT-3 indication consisting of a 3" x 4" scab type indication located on containment plate 158. This scab type indication was accepted by engineering as a preservice surface imperfection during the 2004 refueling outage.

Reexamination during the 2006 refueling outage revealed no noticeable change in the indication on containment plate 158 and was accepted by KPS structural engineering.

Serial No.06-748 2006 INSERVICE INSPECTION

SUMMARY

REPORT

SUMMARY

OF CLASS 1 AND CLASS 2 REPAIRIREPLACEMENT ACTIVITIES FOR COMPONENTS 1-INCH IN DIAMETER OR SMALLER KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

Serial No.06-748 Docket No. 50-305 Page 1 of 1

SUMMARY

OF CLASS 1 AND CLASS 2 REPAIRIREPLACEMENT ACTIVITIES OF COMPONENTS 1 INCH IN DIAMETER OR SMALLER The following summarizes the repairs and replacements performed following the 2004 refueling outage and during the 2006 refueling outage by grinding, buffing, filing, cutting, or welding on the Class 1 and Class 2 pressure boundaries. These repairs and replacements are in addition to those itemized on the enclosed forms, "NIS-2 Owner's Report for RepairIReplacement Activity."

REPAIRIREPLACMENT METHOD Welding in replacement I

I! valve Welding in replacement I

I, Valve Welding in replacement 314M valve Welding in replacement 3/4u valve COMPONENT 1 " valve RC-46 1 " valve RC-49 314" valve SI-46 314" valve SI-39A 314" valve SI-39B 314" elbow upstream of SI-102A 314" elbow upstream of SI-5A-1 1 " valve CVC-204A 318" tubing to valves RC-403, RC-413 and RC-423 CLASS 2

2 2

2 2

I I

I Welding in replacement REFERENCE XK-100-10 XK-100-10 XK-100-28 XK-100-28 2

2 2

1 1

1 XK-100-44 1 318" tubing to valves RC-403, RC-413 and XK-100-28 318" rupture disc RC-440-3 318" rupture disc RC-441-3 318" valve RC-422 Welding in replacement 3/4,1 valve XK-100-28 XK-100-29 XK-100-35

-~

Welding in replacement 3/4u in Welding in replacement 314u Welding in replacement I

I! valve 1

1 1

1 " valve BT-1 B2 314" valve BT-40B XK-l 00-44 XK-l 00-44 XK-l 00-44 2

2 Welding in replacement 318" rupture disc Welding in replacement 318" rupture disc Welding in replacement 318" valve M-203 M-203 RC-423 Welding in replacement 1 " valve Welding in replacement 314" valve

Serial No.06-748 2006 INSERVICE INSPECTION

SUMMARY

REPORT FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS OF CLASS 1, CLASS 2, AND CLASS 3 COMPONENTS FOR FOURTH TEN-YEAR INTERVAL KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

Page 1 of 9 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - NIA
7. COMPONENTS INSPECTED -

MANUFACTURER OR INSTALLER SERIAL NO.

COMPONENT OR APPURTENANCE MANUFACTURER OR INSTALLER STATE OR NATIONAL PROVINCE NO.

BOARD NO.

Reactor Vessel RV Combustion Engineering Replacement Reactor Vessel Closure Head Pressurizer PZR Steam Generator SG-1A Mitsubishi Heavy Industries W estinghouse Westinghousel Ansaldo Energia Milano Westinghousel Ansaldo Energia Milano Steam Generator SG-1 B Excess Letdown Heat Exchanger AHEL-1A Sentry Excess Letdown Heat Exchanger AHEL-1B Sentry Texas Pipe Bending Class 1 Piping Reactor Coolant Pump RCP-1A Westinghouse Westinghouse Reactor Coolant Pump RCP-1B

Page 2 of 9 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-951 1

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - NIA COMPONENT OR APPURTENANCE Residual Heat Exchanger AHRS1-1A Residual Heat Exchanger AHRS2-1B Charging Pump Pulsation Dampener APD-1A Charging Pump Pulsation Dampener APD-1B Charging Pump Pulsation Dampener APD-1C Seal Water Heat Exchanger AHSW Volume Control Tank MANUFACTURER OR INSTALLER Joseph Oat and Sons Joseph Oat and Sons Greer Hydraulics
7. COMPONENTS INSPECTED -

VCT Sons Greer Hydraulics Greer Hydraulics Atlas Joseph Oat and MANUFACTURER OR INSTALLER STATE OR NATIONAL SERIAL NO.

PROVINCE NO.

BOARD NO.

Page 3 of 9 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - NIA
7. COMPONENTS INSPECTED -

MANUFACTURER OR INSTALLER SERIAL NO.

COMPONENT OR APPURTENANCE MANUFACTURER OR INSTALLER STATE OR NATIONAL PROVINCE NO.

BOARD NO.

Letdown Heat Exchanger AHLD Atlas Seal Water Injection Filter AFSI-1A Commercial Filters Commercial Filters AMF Cuno Seal Water Injection Filter AFSI-1B Reactor Coolant Filter AFRC Seal Water Filter AFS W AMF Cuno Class 2 Piping Texas Pipe Bending Charging Pump APCH-1A Ajax Iron Works Charging Pump APCH-1B Ajax Iron Works Charging Pump APCH-1C Ajax Iron Works Charging Pump APCH-1A Suction Stabilizer Greer Hydraulics

Page 4 of 9 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-951 1

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 542
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - NIA
7. COMPONENTS INSPECTED -

MANUFACTURER MANUFACTURER OR INSTALLER OR INSTALLER SERIAL NO.

STATE OR NATIONAL PROVINCE NO.

BOARD NO.

COMPONENT OR APPURTENANCE Greer Hydraulics Charging Pump APCH-1B Suction Stablizer Greer Hydraulics Charging Pump APCH-1C Suction Stablizer Residual Heat Removal Pump APRH1-1A Byron Jackson Byron Jackson Residual Heat Removal Pump APRH2-1B Diesel Generator AHDG-1A Cooling Water Exchangers (2)

ITT Standard Corp.

Diesel Generator AHDG-1B Cooling Water Exchangers (2)

ITT Standard Corp.

Page 5 of 9 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES I. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - NIA
7. COMPONENTS INSPECTED -

COMPONENT OR MANUFACTURER APPURTENANCE OR INSTALLER Reactor Coolant Perfex Pump RCPC-1A Corporation Lube Oil Cooler Reactor Coolant Senior Pump RCPC-1B Lube Engineering Oil Cooler Company Class 3 Piping Texas Pipe Bending Containment Fan JOY Cooler AHCF-1A Manufacturing and American Air Filter Containment Fan JOY Cooler AHCF-1B Manufacturing and American Air Filter Containment Fan JOY Cooler AHCF-1C Manufacturing and American Air Filter MANUFACTURER OR INSTALLER STATE OR NATIONAL SERIAL NO.

PROVINCE NO.

BOARD NO.

Page 6 of 9 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER -DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - NIA
7. COMPONENTS INSPECTED -

MANUFACTURER COMPONENT OR MANUFACTURER OR INSTALLER STATE OR NATIONAL APPURTENANCE OR INSTALLER SERIAL NO.

PROVINCE NO.

BOARD NO.

Containment Fan JOY GF14400 Cooler AHCF-1D Manufacturing and American Air Filter Safety Injection Flow Serve Pump Lube Oil Cooler AHSC-1A Safety Injection Pump Borg Warner Lube Oil Cooler AHSC-1B Safety Injection Pump Borg Warner 854030:854030 Heat Exchangers (2)

AHSC-1A Safety Injection Pump Borg Warner 854030:854030 Heat Exchangers (2)

AHSC-1B Residual Heat Flowserve 03LEX607100/04 Removal Pump AHRHRP-1A Shaft Seal Heat Exchanger

Page 7 of 9 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - NIA
7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE Residual Heat Removal Pump AHRHRP-1B Shaft Seal Heat Exchanger Component Cooling Pump APCC-1A Component Cooling Pump APCC-1B Service Water Pump APSW-1A1 Service Water Pump APSW-1A2 Service Water Pump APSW-1B1 Service Water Pump APSW-1B2 Spent Fuel Pool Heal Exchanger AHSF MANUFACTURER OR INSTALLER Flowserve Ingersoll Dresser Pump Flow Serv.

Ingersoll Dresser Pump Flow Serv.

Worthington Pump Worthington Pump Worthington Pump Worthington Pump Struther Wells MANUFACTURER OR INSTALLER STATE OR NATIONAL SERIAL NO.

PROVINCE NO.

BOARD NO.

Page 8 of 9 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - NIA
7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE Service Water Pump Strainer ASSW-1A1 Service Water Pump Strainer ASSW-lA2 Service Water Pump Strainer ASSW-1B1 Service Water Pump Strainer ASSW-1B2 Component Cooling Heat Exchanger AHCC1-1A Component Cooling Heat Exchanger AHCC2-1B Component Cooling Surge Tank ATCS Control Room Air Conditioning Unit 1 A Coil MANUFACTURER MANUFACTURER OR INSTALLER STATE OR NATIONAL OR INSTALLER SERIAL NO.

PROVINCE NO.

BOARD NO.

S.P. Kinney 2278 Engineers S.P. Kinney 2279 Engineers S.P. Kinney 2280 Engineers S.P. Kinney 2281 Engineers Engineers and S-26125 U39499 Fabricators Co.

Engineers and Fabricators Sharpsville Steel Trane Company

Page 9 of 9 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - NIA
7. COMPONENTS INSPECTED -

MANUFACTURER COMPONENT OR MANUFACTURER OR INSTALLER APPURTENANCE OR INSTALLER Control Room Air Trane Company Conditioning Unit 1B Coil Control Room Air ITT Bell and Gossett Conditioning Expansion Tank 1A Control Room Air ITT Bell and Gossett Conditioning Expansion Tank 1B SERIAL NO.

KlH202003 STATE OR PROVINCE NO.

NATIONAL BOARD NO.

FORM NIS-1 (Back)

Examination Dates: --

February 16, 2005 -

to October 26, -

2006 Inspection Period Identification:

1 st Inspection Interval Identification:

4th Applicable Edition of Section XI:

1998 Addenda:

2000 DateIRevision of Inspection Plan:

February 2 1,2006 Rev. 1 Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan.

Reference Tab C Abstract of Results of Examinations and Tests.

Reference Tab B and Tab F Abstract of Corrective Measures.

Reference Tab B and Tab F Utilization of ASME Boiler - and Pressure Vessel Code Section XI Code Case: N-460 and

.- N-566-1.

We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (If applicable):

200 b Signed:

Dominion-Kewaunee By:,&(& &. Auks, Owner f

I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of WIXO,IJS/W and employed by fim7caeo 5Ww( do/&-&

of

~ o ~ ~ ~ f c f i c u / c have inspected the components described in this Owner's Report during the period

/& FtbkutW ZC85 to 26 aim Z m L

, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.

By signing this certif cate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected w i t h m e c t i o n.

/ +c/AL!%-~L~-

Inspector's Signahre Commissions N8//6zz A&/&, &r /o0,3/

National Board. State, Province, and Endorsements

Serial No.06-748 2006 INSERVICE INSPECTION

SUMMARY

REPORT FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS FOR CLASS MC COMPONENTS KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42 KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - NIA
7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE Reactor Building Containment Vessel Personnel Airlock MANUFACTURER MANUFACTURER OR INSTALLER STATE OR NATIONAL OR INSTALLER SERIAL NO.

PROVINCE NO.

BOARD NO.

Chicago Bridge C4454 U11423 and Iron Company Chicago Bridge C4454 U11423 and Iron Company

FORM NIS-I (Back)

Examination Dates:

A ril 11 200G to

-.. October 26, 2006 Inspection Period Identification: -- 3 rd Inspection Interval Identification:

I st Applicable Edition of Section XI:

1992 Addenda:

1992 DateIRevision of Inspection Plan:

June 17,2005 Revision 3 Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan.

Reference Tab C Abstract of Results of Examinations and Tests.

Reference Tab B and Tab F Abstract of Corrective Measures.

Reference Tab B and Tab F We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (If applicable):

Not Applicable Expiration Date:

Not Applicable Date: ~ & & b 20 Oh Signed:

Dominion-Kewaunee By: P&&, mw A

CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of LU~SCON~M and employed by ~iwrmb s 7 - a ~

do/-

of COEJNN Zt cur have inspected the components described in this Owner's Report during the period I / &M'/L 2005 to 26 oci't5k2006, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected Commissions NU 44-22 dB/#, LVr(00/3/

Nat~onal Board, Stare, Province, and Endorsements Date:

30 OC~UBEZ 20 OG

Serial No.06-748 2006 INSERVICE INSPECTION

SUMMARY

REPORT FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITIES (46 TOTAL)

KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerav-Kewaunee N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Hiahwav 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerav-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 10/30/2006 Sheet 1 of 2 Unit Work Order 98-215433 Type Code Sym. Stamp NA Authorization No. Not Ap~licable
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not A~plicable
5. (a) Applicable Construction Code ASME SEC.111-1986 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, o r Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped CVC-6 FLOWSERVE 04-BGF N A CSOO2-016 2006 INSTALLED N

CORPORATION 7 Descript~on of Work INSTALL REPLACEMENT CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-6 AND CONNECTING 2 SOCKET WELDS.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 2241 psi Test Temp.

116 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/30/2006 Name of Component: CVC-6 Work Order Number: 98-215433 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp I Certificate of Authorization No.

Not A ~ ~ l i c a b l e Expiration Date Not Applicable Signed Date N&%&L 7

2 0 a Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6ff60s to ? L o ~ ~ ~ b,

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ss~ons NB 11622, I, N, B, A WlS 100131 Inspector's S~gnature Nat~onal Board, State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqv-Kewaunee N490 Hiahway 42. Kewaunee, Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiahwav 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerav-Kewaune N490 Hiahwav 42. Kewaunee, Wisconsin 54216-951 1 Date 1 1/06/2006 Sheet 1 of 2 Unit Work Order 02-002234 Type Code Sym. Stamp @

Authorization No. Not Amlicable

4. Identification of System 06 Class 2 MAIN STEAM AND STEAM DUMP Expiration Date Not A~plicable
5. (a) Applicable Construction Code 631.1-1967 (c) Applicable Section XI Code Case &$

(b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda

6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped SD-38 FISHER CONTROLS CO.

4950742 N A SD022-002 1969 CORRECTED N

7 Description of Work CORRECT DUE TO LEAKAGE PAST THE SEAT CLASS 2 MAlN AUXILIARY STEAM AND STEAM DUMP SYSTEM 6" VALVE SD-38.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 983 psi Test Temp.

543 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 11/06/2006 Name of Component: SD-JB Work Order Number: 02-002234 r-CERTIFICATE OF COMPLIANCE 1 I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

I Type Code Symbol Stamp Certificate of Authorization No.

Not A~plicable Expiration Date Not Applicable Signed Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /&%6a5 to ~~~~~06, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected w~th th~s mspection Comm~ss~ons NB 11622, I, N, B, A WIS 100131 Inspector's S~gnature National Board, State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 2 Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsm 54216-951 1 Date OW 8/2OO5 Sheet 1 of 2 Unit Work Order 04-007183

3. Work Performed By Dominion Enerqv-Kewaune Type Code Sym. Stamp N490 Hiqhway 42. Kewaunee, Wisconsin 54216-951 1 Authorization No. Not A~plicable
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not A~~licable
5. (a) Applicable Construction Code ASME Ill CLASS C (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped AHLD (CLASS ATLAS

2) 1206 1031 00060 1970 INSTALLED Y
7. Description of Work REPLACED 19 STUDS AND 38 NUTS ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM LETDOWN HEAT EXCHANGER.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 0311 812005 Name of Component: AHLD (CLASS 2)

Work Order Number: 04-007183 CERTIFICATE OF COMPLIANCE I certtfy that the statements made ~n the report are correct and that th~s INSTALLED conforms to the requ~rernents of the ASME Code, Sectton XI I

Type Code Symbol Stamp I Certificate of Authorization No.

Not Applicable Expiration Date Not Ap~licable Signed fw~. -

&&)-

A f-6%-

Date hlawl\\(*n. 7.20 d k

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 16 fa05 to ZG I X T O ~

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personai injury or property damage or a loss of any kind arising from or connected with this inspection Commissions NB 11622. I, N, 8, A

WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enersv-Kewaunee N490 Hiqhwav 42. Kewaunee, Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiahwav 42. Kewaunee. Wisconsin 54216-951 1 Date 10/16/2006 Sheet 1 of 2 Unit Work Order 04-008470 3 Work Performed By Dominion Enerav-Kewaune Type Code Sym. Stamp @

N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1 Authorization No. Not Ap~licable

4. Identification of System 33 Class 2 SAFETY INJECTION Expiration Date Not Applicable 5 (a) Applicable Construction Code 816.5-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacernent Activity 1998 Edition 2000 Addenda 6 ldentrfication of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped SI-300A CRANE COMPANY 546K1 16878BN NA S1007-001 1972 CORRECTED N

7 Description of Work CORRECT BODY TO BONNET LEAK ON CLASS 2 SAFETY INJECTION SYSTEM 1 0 VALVE SI-300A. REPLACED 16 VALVE BONNET STUDS AND 32 VALVE BONNET NUTS.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt other 0 Pressure 105 psi Test Temp.

80 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 1011 612006 Name of Component:

SI-3OOA Work Order Number: 04-008470 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that th~s CORRECTED conforms to the requirements of the ASME Code, Sect~on XI Type Code Symbol Stamp I Certificate of Authorization No.

Not A~plicable Expiration Date Not Ap~licable Signed f&

c &~'--f-0-

Date ~avhdszr 7

.20 @

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period f 6 F e d to 26 0 ~ 7 0 6,

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ss~ons NB

-- 11622, I, N, B, A WIS 100131 Inspector's S~gnature Nat~onal Board, State, Prov~nce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Eneruv-Kewaunee N490 Hiahwav 42. Kewaunee. Wisconsin 54216-951 1 2 Plant Kewaunee Power Station N490 Hiuhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 10/31/2006 Sheet 1 of 2 Unit Work Order 04-008627 3 Work Performed By Dominion Enerav-Kewaune Type Code Syrn. Stamp NA N490 Hiuhwav 42. Kewaunee. Wisconsin 54216-951 1 Authorization No. Not Applicable
4. Identification of System 2 Class 2 SAFETY INJECTION Expiration Date Not Applicable 5 (a) Applicable Construction Code 831.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda 6, Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RSI-H99 ITT GRINNELL VALVE NA COMPANY N A N A 1967 INSTALLED N

7 Description of Work INSTALL REPLACEMENT CLASS 2 SAFETY INJECTION SYSTEM 2" HYDRAULIC SNUBBER RSI-H99 DUE TO OIL LEAK.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/31/2006 Name of Component:

RSI-H99 Work Order Number: 04-008627 CERTIFICATE OF COMPLIANCE I certify that the statements made ~n the report are correct and that th~s INSTALLED conforms to the requ~rements of the ASME Code. Sect~on XI Type Code Symbol Stamp 1 Certificate of Authorization No.

Not Ap~licable Expiration Date Not Applicable Signed f&&. &

b

~

~

y y

t

~

a n

r f

Date ~mhnleh 1

2 0 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6F&05 to ZC6Lfab, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/

Inspector's Signature 3 Commissions NB 11622, I, N, B, A WIS 100131 National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Eneruy-Kewaunee N490 Hiahwav 42. Kewaunee. Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiuhwav 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerqy-Kewaune N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1 Date 10/30/2006 Sheet 1 of 2 Unit Work Order 04-01 3277 Type Code Sym. Stamp Authorization No. Not Applicable
4. Identification of System 3 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Amlicable
5. (a) Applicable Construction Code ASME SEC. 111-1986 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped CVC-201A FLOWSERVE 03-BGF N A CSOO2-006 2006 INSTALLED N

CORPORATION

7. Description of Work INSTALL REPLACEMENT CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-2O1A AND CONNECTING 2" SOCKET WELDS.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 2241 psi Test Temp.

116 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 1 O/30/2OO6 Name of Component: CVC-201A Work Order Number: 04-01 3277 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Ap~licable Expiration Date Not Applicable Signed f%&+w~

&I~WIUU-L~A.

A P-b~nn, ate hl&

1

,ZO Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period I C f @ 0s to 26 oc706, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ssions NB 11622, I, N, B, A WIS 100131 J

Inspector's Signature National Board, State, Province, and Endorsements Date 3 IvOV~MBER

,20 04- - -

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerav-Kewaunee N490 Hiahway 42. Kewaunee, Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiahwav 42. Kewaunee, Wisconsin 54216-951 1
3. Work Performed By Dominion Enerav-Kewaune N490 Hiqhwav 42, Kewaunee, Wisconsin 54216-951 1 Date 0311 112005 Sheet 1 of 2 Unit Work Order 05-000161 Type Code Sym. Stamp Authorization No. Not A~olicable
4. Identification of System 2 Class 2 CONTAINMENT SPRAY Expiration Date Not Amlicable
5. (a) Applicable Construction Code 831.1-1 967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped ICS-H9 ITT GRINNELL VALVE CO.

NA N A N A 1967 CORRECTED N

7 Description of Work CORRECT BY REPAIRING OIL LEAK ON CLASS 2 CONTAINMENT SPRAY SYSTEM 6" HYDRAULIC SNUBBER ICS-H9.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other 0 Pressure psi Test Temp.

deg. F 9 Remarks NOT APPLICABLE, Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 0311 112005 Name of Component:

ICS-H9 Work Order Number: 05-000161 r-CERTIFICATE OF COMPLIANCE I certify that the statements made ~n the report are correct and that th~s CORRECTED conforms to the requirements of the ASME Code, Sect~on XI Type Code Symbol Stamp I Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable s i g n e d f & ~. & & ~ ~ ~ w w u ~ + ~ ~ u m k %

D a

t e

h l

d

?

, 2 0 4 k Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period / 6 F a 0 5 to 76 ecro6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor hls employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Cornm~ss~ons NB

- 11622, I, N, 0, A WIS 100131 Inspector's S~gnature Nat~onal Board. State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiahway 42. Kewaunee, Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiahway 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Eneray-Kewaune N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1 4 Identification of System 23 Class 2 CONTAINMENT SPRAY
5. (a) Applicable Construction Code B31.1-1967 Date 0311 112005 Sheet 1 of 2 Unit Work Order 05-000175 Type Code Sym. Stamp NA Authorization No. Not A ~ ~ l i c a b l e Expiration Date Not Aoolicable (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped ICS-H12 ITT GRINNEL VALVE N A COMPANY N A N A 1967 CORRECTED N

7 Description of Work CORRECT BY REPAIRING OIL LEAK ON CLASS 2 CONTAINMENT SPRAY SYSTEM 6" HYDRAULIC SNUBBER ICS-H12. -

8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other [7 Pressure psi Test Temp.

deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 0311 1 I2005 Name of Component:

ICS-H12 Work Order Number: 05-0001 75 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

I Type Code Symbol Stamp Certificate of Authorization No.

Not Aoolicable Expiration Date Not Aoolicable d

Signed ~ U L

& b ~ - ~ : f y u & w b Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 16fi-805 to z60cro6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622, I, N. 6, A WIS 100131 National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqy-Kewaunee N490 Hiqhwav 42, Kewaunee. Wisconsin 5421 6-951 1 2 Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 5421 6-951 1 Date 10125/2006 Sheet 1 of 2 Unit Work Order 05-000185 3 Work Performed By Dominion Enerqv-Kewaune Type Code Sym. Stamp N490 Hiqhwav 42, Kewaunee, Wisconsin 54216-951 1 Authorization No. Not Ap~licable

4. Identification of System 36 Class 1 REACTOR COOLANT Expiration Date Not A ~ ~ l i c a b l e 5 (a) Applicable Construction Code 816.5-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda 6 ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RC-1036 VELAN VALVE CORP.

N F N A RC009-002 1967 CORRECTED N

7 Description of Work CORRECT CLASS 1 REACTOR COOLANT SYSTEM 3" VALVE RC-1038 DUE TO LEAKAGE FROM THE SEAT.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 2240 psi Test Temp.

547 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/25/2006 Name of Component: RC-1 O3B Work Order Number: 05-000185 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that th~s CORRECTED conforms to the requirements of the ASME Code, Sect~on XI.

I Type Code Symbol Stamp I Certificate of Authorization N o Not Ap~iicable Expiration Date Not Applicable Signed P-C U

V b

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /bfc60b to 76 OcTo6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ssions NB 11622, I, N, B, A WIS 100131

/

Inspector's Signature 3 National Board, State. Province, and Endorsements Date 7 ~ o v e m 6 6 k _ --

2 0 0 6 -

FORM NIS-2 OWNER'S REPORT FOR REPAIWREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42. Kewaunee, Wisconsin 54216-951 1 2 Plant Kewaunee Power Station N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1 3 Work Performed By Dominion Enerav-Kewaune N490 Hiqhwav 42. Kewaunee, Wisconsin 54216-951 1 Date 1 1/06/2006 Sheet 1 of 2 Unit Work Order 05-00041 7 Type Code Sym. Stamp NA Authorization No. Not Applicable

4. Identification of System 06 Class 2 MAIN STEAM AND STEAM DUMP Expiration Date Not Applicable 5 (a) Applicable Construction Code 831.1-1 967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepaidReplacernent Activity 1998 Edition 2000 Addenda 6 ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped SD-2B WILLIAM POWELL CO.

N F N A SD004-002 1972 CORRECTED N

7 Description of Work CORRECT DUE TO LEAKAGE PAST THE SEAT CLASS 2 MAlN AUXILIARY STEAM AND STEAM DUMP SYSTEM 8" VALVE SD-2B AND REPLACED 16 VALVE BONNET NUTS.

8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other 0 Pressure 983 psi Test Temp.

543 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 11/06/2006 Name of Component: SD-2B Work Order Number: 05-000417 I

CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that thls CORRECTED conforms to the requirements of the ASME Code, Sect~on XI Type Code Symbol Stamp I

Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Date hl&

7

.20 Qk Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period / C f W O S to ZCofl06, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor h ~ s employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comrn~ss~ons NB 11622, I. N, B, A WIS 100131 - -. -

/

Inspector's Signature J

National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerqv-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 1013012006 Sheet 1 of 2 Unit Work Order 05-000423 Type Code Sym. Stamp Authorization No. Not Ap~licable 4 Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable
5. (a) Applicable Construction Code ASME SEC. 111-1986 (c) Applicable Section XI Code Case %

(b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda

6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped CVC-5A FLOWSERVE 05-BGF N A CSO02-013 2006 INSTALLED N

CORPORATION

7. Description of Work INSTALL REPLACEMENT CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-5A AND CONNECTING 2" SOCKET WELDS.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt 0 Other Pressure 2241 psi Test Temp.

116 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 1013012006 Name of Component: CVC-5A Work Order Number: 05-000423 CERTIFICATE OF COMPLIANCE I certlfy that the statements made ~n the report are correct and that th~s INSTALLED conforms to the requirements of the ASME Code, Sect~on XI Type Code Symbol Stamp I Certificate of Authorization N o Not Amlicable Expiration Date Not Ap~licable Signed f&

E UI-7hlfdkfv-Date unu*mlcn.l.20 ek Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period / 6 ~ 9 05 to Zbdci 06, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Comrn~ss~ons NB 11622, I, N, B, A WIS 100131 f Inspector's Signature 3

National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqv-Kewaunee N490 Hishwav 42. Kewaunee. Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 1011 912006 Sheet 1 of 2 Unit Work Order 05-002493 3 Work Performed By Dominion Enerqv-Kewaune Type Code Sym. Stamp NA N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Authorization No. Not Ap~licable 4 Identification of System 3 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not A ~ ~ l i c a b l e
5. (a) Applicable Construction Code 831.1-1 967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda 6, ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped CVC-2 ANCHOR VALVE CO.

NF N A CSO34-001 1970 CORRECTED N

7 Description of Work CORRECT BODY TO BONNET LEAK ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 4" VALVE CVC-2.

8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other n Pressure 137 psi Test Temp.

90 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/19/2006 Name of Component: CVC-2 Work Order Number: 05-002493 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

I Type Code Symbol Stamp Certificate of Authorization No.

Not Applicable Expiration Date Not A~plicable Signed f&&-~h&Mw&

Date 7,20 Qk Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period l L F k 3 0 5 to 76 aro6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code.Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Comm~ss~ons NB 11622, I, N, 9, A WIS 100131 Nat~onal Board, State. Prov~nce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42. Kewaunee, Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 10/25/2006 Sheet 1 of 2 Unit Work Order 05-002550 3 Work Performed By Dominion Eneruv-Kewaune Type Code Sym. Stamp N490 Hishwav 42. Kewaunee, Wisconsin 54216-951 1 Authorization No. Not Applicable 4 Identification of System 3 Class 1 REACTOR COOLANT Expiration Date Not Applicable
5. (a) Applicable Construction Code 831.I-1 967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacernent Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped FE-459 VICKERY SIMMS INC.

NF N A 27040 1970 INSTALLED N

7. Description of Work INSTALL 8 REPLACEMENT STUDS AND 16 REPLACEMENT NUTS ON CLASS 1 REACTOR COOLANT SYSTEM 3" FLANGE FE-459. REPLACE GASKETS ON CLASS 1 REACTOR COOLANT SYSTEM 3" FLANGE FE-459.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt 0 Other Pressure 2240 psi Test Temp.

547 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 1 O/25/2OO6 Name of Component: FE-459 Work Order Number: 05-002550 CERTIFICATE OF COMPLIANCE I certlfy that the statements made ~n the report are correct and that thls INSTALLED conforms to the requirements of the ASME Code, Sect~on XI Type Code Symbol Stamp Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable 4

Signed P a d.

&&ddlnr~l~wc~&y~+&&

f ? - Date 1(1 & 7

,20&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 1 6 F E B d to 76°cTo~,

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code.Section XI.

By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/

Inspector's Signature J Cornm~ss~ons NB 11622, I, N, B A WIS 100131 National Board, State. Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enersv-Kewaunee N490 Hiqhwav 42. Kewaunee, Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiahway 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerav-Kewaune N490 Hiqhway 42. Kewaunee. Wisconsin 54216-951 1 Date 1011 712006 Sheet 1 of 2 Unit Work Order 05-003825 Type Code Sym. Stamp Authorization No. Not A~~licable
4. Identification of System 3 Class 2 SAFETY INJECTION Expiration Date Not A ~ ~ l i c a b l e
5. (a) Applicable Construction Code B16.5-1967 (c) Applicable Section XI Code Case (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6.

ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped SI-208 VELAN VALVE CORP.

32096 N A S1110-002 1970 CORRECTED N

7 Description of Work CORRECT SEAT LEAKAGE ON CLASS 2 SAFETY INJECTION SYSTEM 12" VALVE SI-20B.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 740 psi Test Temp.

88 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 1011 712006 Name of Component:

SI-20B Work Order Number: 05-003825 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed f

(

~

~

~

b w

~

/

1 D

a t

e r

~

7

,20&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commiss~on issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6f-&

to Z 6 ~ 7 - d ~

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622. I, N, B, A - WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 7

~ov&@&

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enersv-Kewaunee N490 Hishwav 42, Kewaunee. Wisconsin 54216-9511
2. Plant Kewaunee Power Station N490 Hishwav 42. Kewaunee. Wisconsin 54216-9511
3. Work Performed By Dominion Enerav-Kewaune N490 Hiahway 42. Kewaunee. Wisconsin 54216-951 1 Date 1012512006 Sheet 1 of 2 Unit Work Order 05-003831 Type Code Sym. Stamp Authorization No. Not Amlicable
4. Identification of System 3 Class 1 SAFETY INJECTION Expiration Date Not A ~ ~ l i c a b l e
5. (a) Applicable Construction Code 816.5-1967 (c) Applicable Section XI Code Case b&

(b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda

6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped SI-3038 VELAN VALVE NF CORPORATION N A S11 16-004 1967 CORRECTED 7 Description of Work CORRECT BY SEAL WELDING BODY TO BONNET ON CLASS 1 SAFETY INJECTION SYSTEM 6" VALVE SI-3038 DUE TO EVIDENCE OF LEAKAGE.

8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt 0 Other Pressure 2240 psi Test Temp.

108 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/25/2006 Name of Component:

Sl-303B Work Order Number: 05-003831 CERTIFICATE OF COMPLIANCE I I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA I Certificate of Authorization No.

Not Applicable Expiration Date Not Acmlicable Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 16ft-6 to 76 =TOG, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection

/

Inspector's Signature J Commlss~ons NB 11622, I, N. B. A WIS 100131 National Board. State. Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enersy-Kewaunee N490 Highwa~

42, Kewaunee. Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Energy-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-9511 Date 10/06/2006 Sheet 1 of 2 Unit Work Order 05-006098 Type Code Sym. Stamp Authorization No. Not Amlicable
4. Identification of System 3 Class 2 SAFETY INJECTION Expiration Date Not Applicable
5. (a) Applicable Construction Code 831.l-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda 6, Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RSI-H78 ITT GRINNELL VALVE CO.

NA N A N A 1967 CORRECTED N

7. Description of Work CORRECT DUE TO LEAKING SEALS CLASS 2 SAFETY INJECTION SYSTEM 3" HYDRAULIC SNUBBER RSLH78.

8 Tests conducted Hydrostatic Pneumatic 0 Nominal Operating Pressure 0 Exempt 8 Other Pressure psi Test Temp.

deg. F 9 Remarks NOT APPLICBALE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 1010612006 Name of Component: RSI-H78 Work Order Number: 05-006098 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

I Type Code Symbol Stamp I Certificate of Authorization No.

Not A ~ ~ l i c a b l e Expiration Date Not A~plicable Signed P&d.

& & / I ~ M U L ~ U C L ~ + P ?

&wr~n Date 7

.20 (&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 16 fa 05 to Z 6 m G, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ss~ons NB

- 11622, I, N, 8, A WIS 100131 Nat~onal Board. State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY A s Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee. Wisconsin 54216-951 1 Date 0211 712006 Sheet 1 of 2 Unit Work Order 05-008470
3. Work Performed By Dominion Enerw-Kewaune Type Code Syrn. Stamp N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Authorization No. Not Amlicable
4. Identification of System &3 Class 2 MAIN STEAM AND STEAM DUMP Expiration Date Not Ap~licable
5. (a) Applicable Construction Code 831.l-1967 (c) Applicable Section XI Code Case @

(b) Applicable Edition of Section XI Used for RepairIReplacernent Activity 1998 Edition 2000 Addenda 6 ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped MSRH-HI ITT GRINNELL VALVE CO.

NA N A N A 1967 CORRECTED N

7. Description of Work CORRECT BY TIGHTENING LOOSE JAM NUT ON CLASS 2 MAlN AUXILIARY STEAM AND STEAM DUMP SYTSEM 6" SUPPORT MRSH-H1.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 0211 712006 Name of Component:

MSRH-HI Work Order Number: 05-008470 i-CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that thts CORRECTED conforms to the requ~rements of the ASME Code, Sect~on XI Type Code Symbol Stamp I Certificate of Authorization No.

Not A~plicable Expiration Date Not A~plicable Signed %&& t,

. r i t r k d ~ h M W & y d h f%WMku QW Date NI&

1 2 0 Q k Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 16F=605 to Z 6 a T 0 6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622, I, N, B, A WIS 100131 National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1 2 Plant Kewaunee Power Station N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1

3. Work Performed By Dominion Enerqv-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 10/25/2006 Sheet 1 of 2 Unit Work Order 05-01061 1 Type Code Sym. Stamp Authorization No. Not Applicable 4 Identification of System 3 Class 1 REACTOR COOLANT Expiration Date Not Applicable 5 (a) Applicable Construction Code 016.5-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped PS-1 B MASONEILAN H-20694-1-2 N A RC013-001 1970 CORRECTED N

INTERNATIONAL 7 Description of Work DISSASSEMBLE AND REBUILD CLASS 1 REACTOR COOLANT SYSTEM 3" VALVE PS-1B WITH A REPLACMENT BELLOWS SEAL AND REPLACEMENT UPPER SPOOL PIECE DUE TO VALVE PACKING LEAK.

8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 2240 psi Test Temp.

547 deg. F 9 Remarks NOT APPLICABLE Applcable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/25/2006 Name of Component:

Work Order Number: 05-01 061 1 CERTIFICATE OF COMPLIANCE I I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp

( Certificate of Authorization No.

Not Applicable Expiration Date Not A~plicable Signed P R ( ~ L

& ~ - l + f m

&MWb Date M&

7

,20 06 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6*605 to ZLoci06, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected w~th th~s lnspect~on 3

Commissions NB 11622, I, N, 6, A WIS 100131 nspector's S~gnature Nat~onal Board, State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42. Kewaunee, Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerqv-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 10/06/2006 Sheet 1 of 2 Unit Work Order 05-01 0832 Type Code Sym. Stamp Authorization No. Not Ap~licable
4. Identification of System 2 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable
5. (a) Applicable Construction Code 831.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped LD-27 MASONEILAN H-40688-1-6 N A CSO21-001 1970 CORRECTED N

INTERNATIONAL, INC.

7 Description of Work CORRECT BY REPAIRING LEAKS ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 3 VALVE LD-27, 2" INLET FLANGE AND 2 - 2" OUTLET FLANGES. REPLACE GASKET ON 3 VALVE LD-27 FLANGE LEAK OFF LINE.

8. Tests conducted Hydrostatic

[7 Pneumatic Nominal Operating Pressure Exempt Other Pressure 135 psi Test Temp.

3 deg. F 9 Remarks NOT APPLICABLE Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/06/2006 Name of Component:

L&!J Work Order Number: 05-010832 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp I Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed pRl(j/ue & & T ~ A W U A T ~ + P W ) ~ V L,

Date s20 O k

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /kftBo5 to Z60cT-

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Commissions NB 11622, I, N, B, A

. -- WIS

.... 100131 Inspector's Signature National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIFUREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerw-Kewaunee N490 Hiqhway 42, Kewaunee. Wisconsin 54216-9511
2. Plant Kewaunee Power Station N490 Hiqhway 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerav-Kewaune N490 Hiahway 42. Kewaunee. Wisconsin 54216-951 1 Date 11/28/2005 Sheet 1 of 2 Unit Work Order 05-01291 1 Type Code Sym. Stamp Authorization No. Not Applicable
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable
5. (a) Applicable Construction Code 831.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RCVC-HI 86 ITT GRINNEL COMPANY NA 1967 CORRECTED 7 Description of Work CORRECT CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" HYDRAULIC SNUBBER RCVC-HI86 DUE TO HYDRAULIC SNUBBER PADDLE BEING TIGHT WITH THE PIPE CLAMP.

8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure

[7 Exempt Other Pressure psi Test Temp.

deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 11/28/2005 Name of Component:

RCVC-HI86 Work Order Number: 05-01291 1 CERTIFICATE OF COMPLIANCE I certify that the statements made ~n the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Sect~on XI Type Code Symbol Stamp I

Certificate of Authorization No.

Not A ~ ~ l i c a b l e Expiration Date Not Ap~licable signed P&

A A

W

~

d f

~

~

4 Date N&

7

,20 O&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period lLF'E29 05 to 26 o c i 0 6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the exammations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622, I, N, B, A WIS 100131

'Inspector's Signature -2 National Board. State. Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerav-Kewaunee N490 Hiqhwav 42, Kewaunee, Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiqhway 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerqv-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 10106l2006 Sheet 1 of 2 Unit Work Order 05-014043 Type Code Sym. Stamp Authorization No. Not Applicable
4. Identification of System 3 Class 2 SAFETY INJECTION Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda 6 ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RSI-H61 ITT GRlNNELL VALVE N A COMPANY N A N A 1967 CORRECTED N

7 Description of Work CORRECT SAFETY INJECTION SYSTEM 6" HYDRAULIC SNUBBER RSI-H61 DUE TO MISALIGNMENT.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other 0 Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10106/2006 Name of Component: RSI-H61 Work Order Number: 05-014043 I

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the

~

ASME Code,Section XI.

Type Code Symbol Stamp I Certificate of Authorization No.

Not Ap~licable Expiration Date Not Applicable Signed f& t.

&~ncQYnuCPl

-&urnUL 4

Date &

7

,20 U Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6 fa 09 to z6m-oC, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commlss~ons NB 11622, I, N, 6, A

WIS 100131 Inspector's S~gnature Nat~onal Board, State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42, Kewaunee, Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiahwav 42. Kewaunee, Wisconsin 54216-951 1
3. Work Performed By Dominion Enerav-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 10/05/2006 Sheet 1 of 2 Unit Work Order 05-014458 Type Code Sym. Stamp NA Authorization No. Not Applicable
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable
5. (a) Applicable Construction Code 831.I -1 967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped CVC-H216 ITT GRINNEL CORP.

N A N A N A 1967 CORRECTED N

7. Description of Work MODIFY CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" SPRING CAN HANGER CVC-H216.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other 0 Pressure psi Test Temp.

deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/05/2006 Name of Component:

CVC-HZ16 Work Order Number: 05-014458 CERTIFICATE OF COMPLIANCE 1 I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

( Type Code Symbol Stamp Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed &$& i&&d-f h & ~

8.-

Date I\\/&

7 2 0 a&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /bFEbo5 to Z Q o c t o d, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

~.

.. ~~

Commissions NB 11622, I. N, B, A WIS 1001

. 31 Inspector's Signature National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerav-Kewaunee N490 Hiahway 42. Kewaunee. Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerqv-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 04/24/2006 Sheet 1 of 2 Unit Work Order 05-014580 Type Code Sym. Stamp Authorization No. Not Ap~licable 4 ldent~fication of System 3 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable
5. (a) Applicable Construction Code SEC.111 CL2-1980 ADD (c) Applicable Section XI Code Case @

(b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda 6 Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped APSS-1 C GREER HYDRAULICS GH1-10236 570 162-937 1981 CORRECTED Y

7. Description of Work 8 Tests conducted REPAIR CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING PUMP 1C SUCTION STABILIZER DUE TO REDUCED FLOW RATE.

Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 24 psi Test Temp.

115 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 04/24/2006 Name of Component:

APSS-1 C Work Order Number: 05-014580 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp I

Certificate of Authorization No.

Not Apdicable Expiration Date Not A~plicable Signed ?&

E T

~

f b A & w @W Date N&

7 2 0 Qk Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6rg6oS to 26 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Cornm~ss~ons NB 11622, I, N, B, A WIS 100131 Inspector's Signature 3 National Board, State. Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee, Wisconsin 54216-951 1 3 Work Performed By Dominion Enerqv-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 0711 7I2OO6 Sheet 1 of 2 Unit Work Order 05-01 4608 Type Code Sym. Stamp Authorization No. Not Applicable 4 Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL Expiration Date Not A~plicable 5 (a) Applicable Construction Code ASME Ill CLASS C (c) Applicable Section XI Code Case @4 (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped AHRS2-1 B JOSEPH OAT AND SONS 1817-1F 345 00126 1970 INSTALLED Y

(CLASS 2) 7 Description of Work REMOVE AND INSPECT CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM RESIDUAL HEAT EXCHANGER STUDS AND NUTS DUE TO EVIDENCE OF LEAKAGE. REPLACED 2 FLANGE STUDS AND 4 FLANGE NUTS.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 481 psi Test Temp.

336 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 07/17/2006 Name of Component: AHRS2-1 B (CLASS 2)

Work Order Number: 05-014608 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that th~s INSTALLED conforms to the requ~rements of the ASME Code, Sect~on XI I Type Code Symbol Stamp fi Certificate of Authorization No.

Not Amlicable Expiration Date Not Amlicable Signed P

~

~

~

~

Q W

I M

Date &Wm&

7

.20 &

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6fe=- to Z60cro6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Comm~ss~ons NB 11622. I, N. 8, A WIS 100131 Inspector's Signature National Board, State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerav-Kewaunee N490 Hiahwav 42. Kewaunee, Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerav-Kewaune N490 Hi~hwav
42. Kewaunee. Wisconsin 54216-951 1 Date 02/20/2006 Sheet 1 of 2 Unit Work Order 06-001 027 Type Code Sym. Stamp Authorization No. Not Ap~licable 4 Identification of System 2 Class 2 RESIDUAL HEAT REMOVAL Expiration Date Not Ap~licable
5. (a) Applicable Construction Code %

(c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda

6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

1 D Built Installed Stamped APRHI-1A BRYON JACKSON 681 NO277 N A 001 27 1970 INSTALLED N

7. Description of Work REMOVE AND INSPECT CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM RESIDUAL HEAT REMOVAL PUMP 1A CASNG STUDS (2) AND NUTS (2) DUE TO EVIDENCE OF LEAKAGE. REPLACED 2 RESIDUAL HEAT REMOVAL PUMP 1A CASING STUDS AND 2 RESIDUAL HEAT REMOVAL PUMP 1A CASING NUTS.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 180 psi Test Temp.

18 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 02/20/2006 Name of Component:

APRH1-1A Work Order Number: 06-001 027 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that this INSTALLED conforms to the requ~rements of the ASME Code,Section XI I Type Code Symbol Stamp Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed

&lmw Date N&

7,20 Q k Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6Fa05 to Z6@cro6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622, I, N, B. A WlS 100131

- Inspector's Signature 2 National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerqv-Kewaune N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1
4. ldentification of System 2 Class 2 RESIDUAL HEAT REMOVAL Date 0113012006 Sheet 1 of 2 Unit Work Order 06-001059 Type Code Sym. Stamp Authorization No. Not A~plicable Expiration Date Not A ~ ~ l i c a b l e
5. (a) Applicable Construction Code 831.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda 6, Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RHR-HI OH ITT GRINNELL VALVE CO.

NF N A N A 1967 CORRECTED N

7. Description of Work CORRECT CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" HYDRAULIC SNUBBER RHR-HIOH DUE TO MISSING NUT.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 01130/2006 Name of Component: RHR-HlOH Work Order Number: 06-001 059 I

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

I Type Code Symbol Stamp I Certificate of Authorization No.

Not A ~ ~ l i c a b l e Expiration Date Not A ~ ~ l i c a b l e Signed

6. &&uWa&&+&ru

~

~

Q U

~

~

U L

Date N&

7

.20 eh_

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period / 6 m o 5 to 26 wf 06, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622, I, N, B, A WIS 100131

/

Inspector's Signature National Board, State, Province, and Endorsements Date ---- 7 !J?e!?-3

,20 O C

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42, Kewaunee, Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerav-Kewaune N490 Hiqhwav 42. Kewaunee. W~sconsin 54216-951 1 Date 02/23/2006 Sheet 1 of 2 Unit Work Order 06-001 078 Type Code Sym. Stamp ?4J Authorization No. Not Applicable
4. Identification of System 2 Class 2 RESIDUAL HEAT REMOVAL Expiration Date Not A~plicable
5. (a) Applicable Construction Code (c) Applicable Section XI Code Case (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped APRH2-I B BRYON JACKSON 681 NO276 N A 001 28 1970 INSTALLED N

7. Description of Work REMOVE AND INSPECT CLASS 2 RESIDUAL HEAT REMOVAL SYTSEM RESIDUAL HEAT REMOVAL PUMP 16 CASNG STUDS AND NUTS DUE TO EVIDENCE OF LEAKAGE. REPLACED 2 RESIDUAL HEAT REMOVAL PUMP 16 CASING STUDS AND 2 RESIDUAL HEAT REMOVAL PUMP 1 B CASING NUTS.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other 0 Pressure psi Test Temp.

18 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 02/23/2006 Name of Component: APRH2-1 B Work Order Number: 06-001078 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that th~s INSTALLED conforms to the requirements of the ASME Code, Sectlon XI Type Code Symbol Stamp I

Certificate of Authorization No.

Not A ~ ~ l i c a b l e Expiration Date Not Ap~licable Signed p Date fdlyW$f% 7

.20 &

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period lbE605 to 2 6 0 ~ ~ 6,

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ss~ons NB 11622, I, N, B. A WIS 100131 Inspector's S~gnature Natlonal Board, State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqv-Kewaunee N490 Hiahwav 42, Kewaunee. Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hishwav 42. Kewaunee. Wisconsin 54216-951 1 Date 10101 12006 Sheet 1 of 2 Unit Work Order 06-003154
3. Work Performed By Dominion Enersv-Kewaune Type Code Sym. Stamp NA N490 Hishwav 42, Kewaunee. Wisconsin 54216-951 1 Authorization No. Not A ~ ~ l i c a b l e 4, Identification of System 2 Class 2 RESIDUAL HEAT REMOVAL Expiration Date Not Ap~licable
5. (a) Applicable Construction Code 831.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RHR-H1OH ITT GRINNELL VALVE CO.

NF N A N A 1967 CORRECTED N

7. Description of Work CORRECT CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" HYDRAULIC SNUBBER RHR-HI OH BY ADDING LOCTITE TO 314" NUT ONTO REPLACEMENT BOLT ON PIPE BRACKET.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure a Exempt Other 0 Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/01/2006 Name of Component: RHR-HIOH Work Order Number: 06-003154 r --

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code.Section XI.

Type Code Symbol Stamp I

Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed ~&E.&L~MOMHALI:A f ~ d ~ c c l e / ~

Date N&

7

,20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of W~sconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6k805-to 26 0 ~ 7 0 6,

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622, I, N, B, A WIS 100131 National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerw-Kewaunee N490 Hiahwav 42. Kewaunee. Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiahwav 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerav-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 1011 712006 Sheet 1 of 2 Unit Work Order 06-003259 Type Code Sym. Stamp Authorization No. Not A ~ ~ l i c a b l e
4. ldentif~cation of System 33 Class 2 SAFETY INJECTION Expiration Date Not Awlicable
5. (a) Applicable Construction Code 816.5-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped St-9A VELAN VALVE 1304 N A S1012-001 1967 CORRECTED N

CORPORATION

7. Description of Work CORRECT BODY TO BONNET LEAK ON CLASS 2 SAFETY INJECTION SYSTEM 3" VALVE SI-9A. REPLACED 12 VALVE BONNET STUDS AND 12 VALVE BONNET NUTS.

8 Tests conducted Hydrostatic

[7 Pneumatic Nominal Operating Pressure Exempt Other Pressure 2100 psi Test Temp.

88 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 1011 7/2OO6 Name of Component:

Work Order Number: 06-003259 CERTIFICATE OF COMPLIANCE I cert~b that the statements made ~n the report are correct and that thls CORRECTED conforms to the requirements of the ASME Code, Sect~on XI Type Code Symbol Stamp NA I

I Certificate of Authorization N o Not Apolicable Expiration Date Not Aoplicable I

Signed f&

L.

P ? -

Date r\\l&

7.20 &

Owner or Owner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 16 F-05 to 26 O Q Q G, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Comm~ss~ons NB 11622, I, N, 8, A

WIS 100131 Natlonal Board, State, Prov~nce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiahway 42. Kewaunee. Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 1011 712006 Sheet 1 of 2 Unit Work Order 06-004589 3 Work Performed By Dominion Enerqv-Kewaune Type Code Sym. Stamp N49O Hiahwav 42. Kewaunee, Wisconsin 54216-951 1 Authorization No. Not A~plicable 4 Identification of System 3 Class 2 RESIDUAL HEAT REMOVAL Expiration Date Not Apolicable 5 (a) Applicable Construction Code NA (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped APRH2-1 B BRYON JACKSON 681 NO276 N A 001 28 1970 INSTALLED N

7. Description of Work INSTALLED 24 REPLACEMENT PUMP CASING STUDS AND 24 REPLACEMENT PUMP CASING NUTS ON CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM RESIDUAL HEAT REMOVAL PUMP 18.
8. Tests conducted Hydrostatic Pneurnatlc Nominal Operating Pressure Exempt Other Pressure 385 psi Test Temp.

J3J deg. F 9 Remarks NOTAPPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/17/2006 Name of Component: APRH2-1 B Work Order Number: 06-004589 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that th~s INSTALLED conforms to the requirements of the ASME Code,Section XI.

I Type Code Symbol Stamp NA 1 Certificate of Authorization No.

Not A~plicable Expiration Date Not A ~ ~ l i c a b l e Signed f&d.&~nv?UMHur~..p.;"~d.-

Date N&?

.20&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period J6-a-to 26OcrO6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ss~ons NB 11622, I, N, B, A WIS 100131 National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Dominion Enerav-Kewaunee N490 Hiahwav 42. Kewaunee. Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiahwav 42. Kewaunee. Wisconsin 54216-9511
3. Work Performed By Dominion Ener~v-Kewaune N490 Hiahwav 42. Kewaunee. Wisconsin 54216-951 1 Date 0511 912006 Sheet 1 of 2 Unit Work Order 06-005853 Type Code Sym. Stamp NA Authorization No. Not A ~ ~ l i c a b l e
4. Identification of System 058 Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code 831.l-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacernent Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped FDW-ti40 ITT GRINNEL COMPANY NF N A N A 1967 CORRECTED N

7. Description of Work CORRECT CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" HANGER FDW-H40 DUE TO MISSING NUT.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 0511 912006 Name of Component:

FDW-H40 Work Order Number: 06-005853 CERTIFICATE OF COMPLIANCE I certify that the statements made tn the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Sect~on XI

( Type Code Symbol Stamp M Certificate of Authorization No.

Not A~plicable Expiration Date Not Applicable Signed P

~

L A

A

~

T

~

eR6Mam,~umUL Date NAI

$20 a Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 16 -05 to Zbocro6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ss~ons NB 11622, I, N, B, A WIS 100131 Inspector's Signature Nat~onal Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAlRlREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerav-Kewaunee N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 2 Plant Kewaunee Power Station N490 Hiahway 42. Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerqv-Kewaune N490 Hiahway 42. Kewaunee, Wisconsin 54216-951 1 Date 10/3112006 Sheet 1 of 2 Unit Work Order 06-00681 0 Type Code Sym. Stamp NA Authorization No. Not A~olicable 4, Identification of System 3 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Amlicable
5. (a) Applicable Construction Code 831.I-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Name of Name of pp Corrected, ASME Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped CVC-443 ITT GRINNELL VALVE CO.

NF N A CSOO5-132 1972 INSTALLED N

7. Description of Work INSTALL STAINLESS STEEL NUT ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-443.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/31/2006 Name of Component: CVC-443 Work Order Number: 06-006810 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that th~s INSTALLED conforms to the requ~rements of the ASME Code,Section XI Type Code Symbol Stamp I Certificate of Authorization No.

Not A~plicable Expiration Date Not A~plicable Signed ~

~

~

~

~

P Date &d%

7 2 0 Qk Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 16 F F 8 6 to 7 6 o c G s and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Commwons NB 11622, I, N, B, A WIS 100131 Inspector's S~gnature Nat~onal Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enersv-Kewaune N490 Hishwav 42. Kewaunee. Wisconsin 54216-951 1 Date 1 O/IO/Z'OO6 Sheet 1 of 2 Unit Work Order 06-006960 Type Code Sym. Stamp Authorization No. Not Applicable
4. Identification of System 33 Class 2 SAFETY INJECTION Expiration Date Not Applicable
5. (a) Applicable Construction Code 816.5-1967 (c) Applicable Section XI Code Case N-566-1 (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda 6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RHR-299A ALOYCO INC.

N F N A S1008-001 1970 CORRECTED N

7. Description of Work CORRECT BY REPLACING BODY TO BONNET GASKET ON CLASS 2 SAFTY INJECTION SYSTEM 6" VALVE RHR-299A DUE TO EVIDENECE OF BORIC ACID.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 145 psi Test Temp.

101 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/10/2006 Name of Component: RHR-299A Work Order Number: 06-006960 CERTIFICATE OF COMPLIANCE I I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI Type Code Symbol Stamp I Certificate of Authorization No.

Not A~dicable Expiration Date Not A ~ ~ l i c a b l e Signed P - F ~ ~ # & V Py bumv~, Date N&

7 -20 Q k

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period IbFBo5 to 26OtToC, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ssrons NB 11622, I, N, 8, A

WIS 100131 Inspector's S~gnature Natronal Board, State, Prov~nce, and Endorsements

KEWAUNEE NUCLEAR POWER PLANT I

INSERVICE INSPECTION INDICATION EVALUATION RECORD FOR CODE CASE N-566-1 COMPLIANCE I System or Component:

Safety Injection Pumps Suction Piping: Safety Injection System Drawing ISIM-933: ISIXKIOO-29 Component Identification:

R H R - ~ ~ ~ A (XK-100-1377)

I ASME Section XI 1998 Edition 2000 Addenda: Article IWA-5000 Section: IWA-5250(a)(2)

I Indication Detection Method:

VT-1 (

)

VT-2 (X)

VT-3 (

)

I Leakage Stopped: YES:

NO: Ig I

If YES Evaluate in accordance with below:

If NO Evaluate in accordance with IWB-3142.4 and below.

EVALUATION FOR SUSCEPTIBILITY OF THE BOLTING T O CORROSION AND FAILURE Number and Service Age of the Bolts: 16 Studs and 32 Nuts; Service Age: 1970; VT-3 of 16 Studs Disassembled and 32 Nuts I Disassembled were on May 7.2003 for Work Order 03-005353 with Acceptable No Indications recorded.

Bolt and Component Material: Studs: A-193 B-7 Carbon Steel; Nuts: A-194 2H Carbon Steel; Valve Bonnet: A-351 CF8M; Valve Body: A-35 1 CF8M Corrosiveness of Process Fluid: From Evaluation in CAP 022003 the following was determined: Per GNP-08.06.01 Boric Acid Corrosion Control Inspection and Evaluation RHR-299A Leakage is a Low Risk Leak with potential degradation rates of 0.002 to 0.007 inches/year but requires cleaning and a follow up Visual examination to complete the evaluation. RHR-299A will be monitored under the Boric Acid Corrosion Control Program.

I Leakage Location and System Function: Active Wet Boric Acid Between Valve Body and Valve Bonnet with Wet Boric Acid In Contact with Bonnet Studs: System Function: Safety Injection and Residual Heat Removal Leakage History at the Connection or Other System Components: From Inservice Inspection Program: Evidence of Leakage at Body to Bonnet in 1987. Moderate Dry Boric Acid at Bonnet Seal Weld Surface in 1996 & tight Dry Boric Acid at Bonnet Seal Weld Interface in 2001. Boric Acid, Rust & Corrosion on Studs in 1985 and possible Corrosion of Studs in 1996. tight Dry Boric Acid on Studs in 1998.

Visual Evidence of Corrosion at the Assembled Connection: Unknown until cleaning. Scaffold Building, Cleaning and VT-3 examination has been scheduled under the GNP-08.06.01 Boric Acid Corrosion Control Inspection and Evaluation Program.

Root Cause Analysis:

Possible Body to Bonnet Gasket Failure due to Insufficient Gasket Compression.

Work Request 04-002109 will confirm Root Cause Analysis I

Recommendation:

RepaidReplace Per GMP-207 (X)

Work 0rdeT WR: 04-002 109 Accept As Is and Monitor (XI CAP: 022003 I

Not Applicable

(

1 Comments:

Repairrneplace: Work Request: 04-002 109; Accept As Is and Monitor: CAP: 022003 I

Evaluation Performed By:

Date:

I

Title:

v Inservice Inspection Review:

Date:

,&,~LX~.JOOY J

Level I11 Review:

Date:

9-3-04 I

Engineering Supervisor

.'I Review:

/',I?+-, T;,.,,

/La 4

Date:

$ - 6 -dL/

w I

/

Authorized Nuclear Inservice Inspector Review:

Date:

8-9-0 4

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Eneray-Kewaunee N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiahwav 42. Kewaunee. Wisconsin 5421 6-951 1 3 Work Performed By Dominion Eneray-Kewaune N490 Hiahway 42. Kewaunee, Wisconsin 54216-951 1 Date 10101/2006 Sheet 1 of 2 Unit Work Order 06-010293 Type Code Sym. Stamp Authorization No. Not A ~ ~ l i c a b l e
4. Identification of System 2 Class 2 RESIDUAL HEAT REMOVAL Expiration Date Not Applicable 5 (a) Applicable Construction Code 831.1 -1 967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda 6 ldent~fication of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped N A N A 1969 CORRECTED N

7 Description of Work CORRECT BY TIGHTENING LOOSE CLAMP BOLT ON CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 6 HYDRAULIC SNUBBER RHR-H21A.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/01/2006 Name of Component:

RHR-H21A Work Order Number: 06-010293 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

I Type Code Symbol Stamp I Certificate of Authorization No.

Not Ap~licable Expiration Date Not Applicable Signed

~&&4%~4&1'&+&&

f?

Date &

V h

h

~

7

.20 o&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6rrB&

to z6f1°6

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622, I, N, B, A WIS 100131 Inspector's Signature National Board. State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy-Kewaunee N490 Hiahwav 42. Kewaunee. Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiahway 42, Kewaunee. Wisconsin 54216-951 1 Date 1 O/O4/2OO6 Sheet 1 of 2 Unit Work Order 06-010295
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Hiohway 42. Kewaunee. Wisconsin 54216-951 1 Authorization No. Not Ap~licable
4. Identification of System 36 Class 1 REACTOR COOLANT Expiration Date Not A ~ ~ l i c a b l e
5. (a) Applicable Construction Code 831.l-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6.

Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RTD-HI 1 ITT GRINNEL NF N A N A 1967 CORRECTED N

7 Description of Work CORRECT BY REBUILDING CLASS 1 REACTOR COOLANT SYSTEM 2" HYDRAULIC SNUBBER RTD-HI 1 DUE TO CYLINDER OIL LEAKAGE.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other U Pressure psi Test Temp.

deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/04/2006 Name of Component: RTD-HI 1 Work Order Number: 06-010295 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Sect~on XI Type Code Symbol Stamp I Certificate of Authorization No.

Not A ~ ~ l i c a b l e Expiration Date Not Applicable Signed T!%!@L

&hWd&

?nrnvII bwru Date ~m*1.lu.

7

.20 &

Owner or Owner's Designee, {tle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period f 6 m o 5 to z6°0-06

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Comm~ss~ons NB 11622, I, N, B, A WIS 100131 Nat~onal Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiqhway 42, Kewaunee, Wisconsin 5421 6-951 1 2 Plant Kewaunee Power Station N490 Hiqhway 42. Kewaunee. Wisconsin 5421 6-951 1

3. Work Performed By Dominion Ener~v-Kewaune N490 Hiqhwav 42, Kewaunee, Wisconsin 54216-951 1 Date 09/24/2006 Sheet 1 of 2 Unit Work Order 06-010326 Type Code Sym. Stamp Authorization No. Not Ap~licable
4. Identification of System 31 Class 3 COMPONENT COOLING Expiration Date Not A~plicable
5. (a) Applicable Construction Code (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda 6 ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped AHRHRP-1A FLOWSERVE 03LEX607100/04 NA 145-141 2003 CORRECTED 7 Description of Work CORRECT BY REPAIRING LEAK ON THE CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM SIDE OF RESIDUAL HEAT REMOVAL PUMP 1A SHAFT SEAL HEAT EXCHANGER.

8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 138 psi Test Temp.

87 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 09/24/2006 Name of Component: AHRHRP-1A Work Order Number: 06-01 0326 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that th~s CORRECTED conforms to the requ~rements of the ASME Code.Section XI Type Code Symbol Stamp Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed f a r.

&&Z-X-

~-QW Date h)&k?m&% 7

,20 Ob_

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6rn@O5 to Z'ocrOC, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ss~ons NB 11622, I, N, 8, A

WIS 100131 Inspector's Signature Nat~onal Board, State, Prov~nce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqy-Kewaunee N490 Hiahwav 42. Kewaunee, Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-9511 Date 1010412006 Sheet 1 of 2 Unit Work Order 06-010465
3. Work Performed By Dominion Enerav-Kewaune Type Code Sym. Stamp NA N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Authorization No. Not Ap~licable
4. Identification of System 3 Class 2 SAFETY INJECTION Expiration Date Not Applicable
5. (a) Applicable Construction Code 831.1-1 967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda 6 Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped pp RHR-H12A ITT GRINNELL VALVE CO NF N A N A 1967 CORRECTED N

7 Descr~ption of Work CORRECT DUE TO OIL LEAKAGE CLASS 2 SAFETY INJECTION SYSTEM 6 HYDRAULIC SNUBBER RHR-H12A.

8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10104/2006 Name of Component:

RHR-HI 2A Work Order Number: 06-010465 CERTIFICATE OF COMPLIANCE I I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA I Certificate of Authorization No.

Not AD~licable Expiration Date Not A~olicable Suned f-

~

~

Y U

S P

W

&&WL Date #A?

-20 G k Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6fm*5 to Z6oci-a, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

- Inspector's Signature Comm~ss~ons NB 11622, I. N, B, A WIS 100131 National Board. State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 1010412006 Sheet 1 of 2 Unit Work Order 06-010466
3. Work Performed By Dominion Enersv-Kewaune Type Code Sym. Stamp NA N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1 Authorization No. Not A ~ ~ l i c a b l e
4. Identification of System 2 Class 2 SAFETY INJECTION Expiration Date Not Applicable
5. (a) Applicable Construction Code 831.l-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda 6, ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RHR-H12B ITT GRINNELL VALVE CO.

NF N A N A 1967 CORRECTED N

7. Description of Work CORRECT DUE TO OIL LEAKAGE CLASS 2 SAFETY INJECTION SYSTEM 6" HYDRAULIC SNUBBER RHR-H12B.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/04/2006 Name of Component:

RHR-H12B Work Order Number: 06-010466 I

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable S

i g

n e

d f

~

~

~

~

date^&^

.20 C&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 1 6 f w to 26-06

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected w~th th~s lnspect~on Comm~ss~ons NB 11622, I, N, 6, A WIS 100131 Inspector's S~gnature Nat~onal Board, State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqy-Kewaunee N490 Hiqhwav 42. Kewaunee, Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiqhway 42, Kewaunee, Wisconsin 54216-951 1 Date 1011 212006 Sheet 1 of 2 Unit Work Order 06-01 0473
3. Work Performed By Dominion Enerqv-Kewaune Type Code Sym. Stamp N490 Hiqhwav 42, Kewaunee, Wisconsin 54216-951 1 Authorization No. Not A ~ ~ l i c a b l e
4. Identification of System 34 Class 1 RESIDUAL HEAT REMOVAL Expiration Date Not Ap~licable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacernent Activity 1998 Edition 2000 Addenda 6, ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RHR-1 B VELAN VALVE N F CORPORATION N A AC104-003 1972 CORRECTED N

7. Description of Work CORRECT DUE TO EVIDENCE OF LEAKAGE BY SEAL WELDING BODY TO BONNET CLASS 1 RESIDUAL HEAT REMOVAL SYSTEM 8" VALVE RHR-1B.
8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 15 psi Test Temp.

93 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 1011 212006 Name of Component:

RHR-1B Work Order Number: 06-010473 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that th~s CORRECTED conforms to the requ~rements of the ASME Code, Sect~on XI Type Code Symbol Stamp I Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed P&

d. & r - ~ d P

b Date hgu6nlUL 1

-20 (&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period IbRBo5 to ZL M T O 6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commlsslons NB 11622. I, N, B, A WIS 100131 Inspector's S~gnature Nat~onal Board. State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIWREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqv-Kewaunee N490 Hiqhway 42, Kewaunee, Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiohwav 42, Kewaunee. Wisconsin 54216-951 1
3. Work Performed By Dominion Enerqv-Kewaune N490 Hiahway 42. Kewaunee, Wisconsin 54216-951 1 Date 10109/2006 Sheet 1 of 2 Unit Work Order 06-010481 Type Code Sym. Stamp NA Authorization No. Not Applicable 4 Identification of System 3 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable
5. (a) Applicable Construction Code 831.l-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RCVC-H191 ITT GRINNEL COMPANY NA N A N A 1967 CORRECTED N

7 Description of Work CORRECT BY REBUILDING CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" HYDRAULIC SNUBBER RCVC-HI91 DUE TO EXCESSIVE CLEARANCE IN THE PIPE CLAMP TO SNUBBER FASTENER.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 1 O/O9/2OO6 Name of Component:

RCVC-HI91 Work Order Number: 06-010481 I

CERTIFICATE OF COMPLIANCE I certlfy that the statements made ~n the report are correct and that thls CORRECTED conforms to the requirements of the ASME Code, Sect~on XI Type Code Symbol Stamp NA 1 Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable S i g n e d f ? & ~. & ~ / y L o y L y L c L L ~ & ~ ? ~ t y l l ( n D a t e ~ o y h n l U T.20O&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /6RW.5 to 26 oflO6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected wlth thls mspect~on

< 3 - - ~

.- -'y -

Comm~ss~ons NB 11622, - -

I, N,.

8, A

WlS 100131 Inspector's S~gnature Natlonal Board. State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqv-Kewaunee N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-9511

3. Work Performed By Dominion Enersv-Kewaune N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Date 10/24/2006 Sheet 1 of 2 Unit Work Order 06-01 1440 Type Code Sym. Stamp Authorization No. Not Ap~licable 4 identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Ap~licable 5 (a) Applicable Construction Code 831.I-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda 6, Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped CVC-10 KEROTEST MFG CORP NV-143 N A CSIOO-005 1973 CORRECTED N

7 Description of Work CORRECT DUE TO NOT SEATING PROPERLY CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE cvc-10.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt 0 Other Pressure 2236 psi Test Temp.

96 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/24/2006 Name of Component:

CVC-10 Work Order Number: 06-01 1440 I

CERTIFICATE OF COMPLIANCE I certify that the statements made ~n the report are correct and that th~s CORRECTED conforms to the requlrernents of the ASME Code,Section XI.

Type Code Symbol Stamp I

Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed P@

L &XWWWG~+.&U h Date d&

7,20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period i6fF6e5 to z L e T &, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commiss~ons NB

- 11622, I, N, 8, A WIS 100131 Inspector's Signature 4 Date 7

EJov&~c)ER 2 0 0' National Board, State. Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner
2. Plant Dominion Ener~v-Kewaunee N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 Kewaunee Power Station N490 Hiqhwav 42. Kewaunee. Wisconsin 54216-951 1 3 Work Performed By Dominion Enerav-Kewaune N490 Hiohwav 42, Kewaunee. Wisconsin 54216-951 1
4. ldentification of System 33 Class 2 SAFETY INJECTION Date 1011 712006 Sheet 1 of 2 Unit Work Order 06-01 1623 Type Code Sym. Stamp g Authorization No. Not Amlicable Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.l-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, AS ME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RHR-H12A ITT GRINNELL VALVE CO.

NF N A N A 1967 CORRECTED N

7. Description of Work CORRECT BY VERIFYING TIGHTNESS OF TIE ROD HEX NUTS ON CLASS 2 SAFETY INJECTION SYSTEM 6" HYDRAULIC SNUBBER RHR-HI 2A.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp.

deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/17/2006 Name of Component: RHR-H1 2A Work Order Number: 06-01 1623 CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that th~s CORRECTED conforms to the requ~rements of the ASME Code, Sectlon XI Type Code Symbol Stamp I Certificate of Authorization No.

Not Amlicable Expiration Date Not Applicable S

e n

e d

f

~

~

k W

+

t

~

P

/

I d

M a

r n

~

~

a t

e N&?

.200&

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period / 6 f a o 5 to 26°crOL, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Cornmiss~ons NB 11622, I. N, B, A WIS 100131 Inspector's Signature Natlonal Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqv-Kewaunee N490 Hiqhway 42. Kewaunee, Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hiqhwav 42. Kewaunee, Wisconsin 54216-951 1
3. Work Performed By Dominion Enerqv-Kewaune N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1 4 ldentification of System 2 Class 2 SAFETY INJECTION Date 1011 712006 Sheet 1 of 2 Unit Work Order 06-01 1623 Type Code Sym. Stamp N4 Authorization No. Not Applicable Expiration Date Not A~plicable
5. (a) Applicable Construction Code 831.I-1 967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RHR-H12B ITT GRINNELL VALVE CO.

NF N A N A 1967 CORRECTED N

7 Description of Work CORRECT BY VERIFYING TIGHTNESS OF TIE ROD HEX NUTS ON CLASS 2 SAFETY INJECTION SYSTEM 6" HYDRAULIC SNUBBER RHR-HIZB.

8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other 0 Pressure psi Test Temp.

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 1011 712006 Name of Component:

RHR-H12B Work Order Number: 06-01 1623 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

I Type Code Symbol Stamp Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed f-I-~WB-Date NM&&

1.20 O Owner or Owner's Designee, T~tle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period /b/eOd to 7 6 6 0 6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected w~th thls lnspect~on Comm~sstons NB 11622, I, N, B, A WIS 100131 Inspector's Signature Nat~onal Board, State, Prov~nce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1 Owner Dominion Enerqy-Kewaunee N490 Hiqhwav 42, Kewaunee, Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhwav 42, Kewaunee. Wisconsin 54216-951 1 3 Work Performed By Dominion Enerav-Kewaune N490 Hiqhway 42. Kewaunee. Wisconsin 54216-951 1 Date 10/24/2006 Sheet 1 of 2 Unit Work Order 06-01 1629 Type Code Sym. Stamp Authorization No. Not A ~ ~ l i c a b l e
4. Identification of System 3 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Aoolicable 5 (a) Applicable Construction Code 831.l-1967 (c) Applicable Section XI Code Case NA (b) Apphcable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6. ldentification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

1 D Built Installed Stamped CVC-10 KEROTEST MFG CORP NV-143 N A CS100-005 1973 CORRECTED N

7. Description of Work CORRECT BODY TO BONNET LEAK BY SEAL WELDING CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-10.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure 2236 psi Test Temp.

96 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/24/2006 Name of Component: CVC-I0 Work Order Number: 06-01 1629 I

CERTIFICATE OF COMPLIANCE I certtfy that the statements made ~n the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Sectlon XI I

Type Code Symbol Stamp I Certificate of Authorization No.

Not A~plicable Expiration Date Not A ~ ~ l i c a b l e Signed P ? L / ~ C J B C J I -.. ~ ~

BW Date NbYknl*lr 7

.2O &-

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 16-05 to 26Ocro6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622,. I, N, - B, A.... WIS 100131

-..-.- -~ --

Inspector's Signature National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enersv-Kewaunee N490 Hishway 42, Kewaunee. Wisconsin 54216-951 1
2. Plant Kewaunee Power Station N490 Hishwav 42. Kewaunee. Wisconsin 54216-951 1 Date 1013112006 Sheet 1 of 2 Unit Work Order 06-01 1685
3. Work Performed By Dominion Enerqv-Kewaune Type Code Sym. Stamp N490 Hiahwav 42, Kewaunee. Wisconsin 54216-951 1 Authorization No. Not Applicable
4. Identification of System 23 Class 2 CONTAINMENT SPRAY Expiration Date Not Applicable
5. (a) Applicable Construction Code 816.5-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for RepairIReplacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped ICS-202 FISHER CONTROLS 4950736 N A ICSO13-001 1972 CORRECTED N

INTERNATIONAL 7 Description of Work CORRECT DUE TO NOT HOLDING PRESSURE CLASS 2 CONTAINMENT SPRAY SYSTEM 2" VALVE ICS-202.

8 Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt other 0 Pressure 420 psi Test Temp.

87 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/31/2006 Name of Component:

ICS-202 Work Order Number: 06-01 1685 I

CERTIFICATE OF COMPLIANCE I cert~fy that the statements made ~n the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp 1 Certificate of Authorization No.

Not Apolicable Expiration Date Not Applicable Signed P W

4 P % % W ~ B. W Date ~d 7

.20 Qk Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period m& to 76-06, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected w~th th~s lnspect~on Comm~ss~ons NB 11622. I, N, B, A WIS 100131 Inspector's S~gnature Nat~onal Board, State, Provmce, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAlWREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Dominion Energy-Kewaunee N490 Highway 42, Kewaunee, Wisconsin 54216-951 1

2. Plant Kewaunee Power Station N490 Hiqhway 42, Kewaunee, Wisconsin 54216-951 1
3. Work Performed By Dominion Enerqy-Kewaune N490 Hiqhway 42. Kewaunee. Wisconsin 54216-951 1 Date 10/24/2006 Sheet 1 of 2 Unit Work Order 06-01 1694 Type Code Sym. Stamp NA Authorization No. Not Applicable
4. ldentif~cation of System 23 Class 2 CONTAINMENT SPRAY Expiration Date Not Amlicable
5. (a) Applicable Construction Code 816.5-1967 (c) Applicable Section XI Code Case NA (b) Applrcable Edition of Section XI Used for RepairlReplacement Activity 1998 Edition 2000 Addenda
6. ldentificatron of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped ICS-4A TRW MISSION 47571 N A ICSOO4-003 1970 CORRECTED N

MANUFACTURING 7 Description of Work OPEN FOR CORRECTION DUE TO NOT BEING ABLE TO VERIFY CLOSURE CLASS 2 CONTAINMENT SPRAY SYSTEM 6" VALVE ICS-4A.

8. Tests conducted Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other 0 Pressure 225 psi Test Temp.

81.5 deg. F 9 Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/24/2006 Name of Component:

ICS-4A Work Order Number: 06-01 1694 CERTIFICATE OF COMPLIANCE I I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp I Certificate of Authorization No.

Not Ap~iicabie Expiration Date Not A ~ ~ l i c a b l e Signed ~ % & L & ~ x / W Z V H E. L U I X, ~ ~ Q W D

a t

e b

7

.20*

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 16-05 to Z6mrOC, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comm~ss~ons NB 11622, I, N, 8, A -

WIS 100131 --

Natronal Board, State, Provmce, and Endorsements

Serial No.06-748 2006 INSERVICE INSPECTION

SUMMARY

REPORT EXAMINATION

SUMMARY

FOR CLASS 1, CLASS 2, AND CLASS 3 INSERVICE INSPECTION PROGRAM FOR FOURTH TEN-YEAR INTERVAL KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

KEWAUNEE POWER STATION 2PdD OUTAGE: 1ST PERIOD: 3TH INTERVAL 2006 EXAMINATION

SUMMARY

INTRODUCTION An Inservice Inspection (ISI) Program (Scheduled and Augmented) was performed at the Kewaunee Power Station from February 16,2005 through November 8, 2005 (Non Refueling Outage) and September 2, 2006 through October 26,2006 (Closing of GI following Refueling Outage) by Kewaunee Power Station, Lambert, MacGill, and Thomas, Inc.(LMT) and Great Lakes Testing examination personnel.

Examinations were performed to satisfy the requirements o f ASME Boiler and Pressure Vessel Code Section XI 1998 Edition 2000 Addenda United States Nuclear Regulatory Comn~ission Generic Letter 88-05 "Boric Acid Corrosion of Carbon Steel Reactor Coolant Boundary Components in PWIi Plants" United States Nuclear Regulatory Commission Bulletin 2003-02 "Ixakage From Reactor Pressure Vessel Lower Head Penetrations and Reactor Coolslrit Pressure Boundary Integrity" United States Nuclear Regulatory Commission Regulatory Guide 1.14 Revision 1 Reactor Coolant Pump Flywheel Integrity Materials Reliability Program MRP-129 Generic Guidance For Alloy 600 Management

  • Materials Reliability Program MRP-139 Primary System Piping Butt Weld Inspection and Evaluation Guideline The Inservice Inspection Program Plan and Augmented Inspection Program Plan 1oca.ted undcr Tab C was prepared by Kewaunee Power Station Plant for the 2nd Outage: 1st Pcriod: 4th Interval as identified in the Kewaunee Power Station Fourth 10-Year Inservice Inspection (ISI)

Program 2004 - 2014. Examinations during this Refueling Outage were performed to complete 1 Period; 4th Interval Examination Requirements of ASME Boiler and Pressure Vessel Code Section XI 1998 Edition 2000 Addenda and Kewaunee Power Station Fourth 10-Year Inservicc Inspection (ISI) Program 2004-20 14.

The following iiems were examined:

Reactor Vessel Upper and Lower Internals

  • Reactor Vessel Closure Head Bare Metal Reactor Vessel Bottom Head Barc Metal for MRP-129 Generic Guidance for Alloy 600 Management Page 1 of 4

Steam Generator Sllell Circumferential Weld Reactor Coolant Pump Main Flange Bolting and No. 1 Seal Housing Bolting Reactor Coolant Pump Flywheel

  • Class 1 Valve Bodies Class 1 Piping welds for MRP-139 Generic Guidance For Alloy 600 Management Class 1, Class 2 and Class 3 Piping and Component Supports and Hangers Class 1 and Class 2 Steam Generator Primary Manway Bolting, Pressurizer Manway Bolting, Flange Bolting and Valve Bonnet Bolting Class 2 Feedwater Nozzle to Pipe Welds Class 1 System Leakage Test Class 2 and Class 3 System Leakage Tests EXAMINATIONS The examinations performed were in accordance with an approved Inservice Inspection Program Plan located under Tab C of the final report. Examination Procedures were approved prior to the start of examinations and certification docun~ents relative to personnel, equipment and materials were reviewed and determined to be satisfxtory.

Some of the arrangement:, and details of the Kewaunee Power Station Components and Piping Systems were designed and fabricated before ASME Boiler and Pressure Vessel Code Section XI Code requirements were established. Examinations performed were intended to examine 100% of the required surface or volume. In some cases, examinations were limited by geometric, nletallurgical or designlaccess restrictions. In each case, the occurrence and cause of the limitation was documented. In all cases the rnaxinlum amount achievable was examined.

\\

Witnessing and surveillance of the examinations were conducted by personnel from: the Nuclear Regulatory Commission and Hartford Steam Boiler Illspection and Insurance Company of CT.

RESULTS Examinations resulted with the following Recordable Indications being noted on the basis of procedure recording criteria, which are generally more restrictive than specified 4SME Boiler and Pressure Vessel Code Section XI Acceptance Standards.

Recordable Indications detected during the 2006 Refueling Outage are listed in Table 1 with a brief summary following. Specific data relative to all Recordable Indications and their dispos~tions by either corrective measures, acceptance by ASME Boiler and Pressure Vessei Cock Section XI 1998 Edition 2000 Addenda Acceptance Criteria, Repair or Replacement or Evaluation are located in Tab F of the Final Report Page 2 of 4

TABLE 1 TYPE OR LOCATION OF RECORDABLE INDICATION (RI)

METHOD NO. OF RI'S Steam Generator 1 B Shell Circumferential Volumetric (UT) 1 Weld Weld SG-WlO Reactor Vessel Internals Visual (VT-3) 1 Thermocouple Conduit Flange Bolting Visual (VT-1 and VT-3) 1 Flange Valve Bonnet Bolting Visual (VT-3) 3 Valves System Leakage Pressure Tests Visual (VT-2) 30 Items

1. Recordable Indications were recorded on Steam Generator 1B Circumferential Girth Weld SG-W 10. The 43 Separate Indications were previously recorded during the 1996 and 2001 Refueling Outages. A comparison of the length, amplitude, and position of the signal response between 1996, 2001 and 2006 revealed no discernible changes, indicating that the flaws are stable and have not grown in size. Indications were acceptable either by ASME Boiler and Pressure Vessel Code Section XI 1998 Edition 2000 Addenda or by Fracture Analysis as provided in Westinghouse Electric Corporation WCAP 1 1476 Rev. 3 Handbook on Flaw Evaluation Kewaunee Unit 1 Steam Generator Upper Shell to Cone Weld, May 1991 and evaluation by Kewaunee Power Station during the 1996 and 2001 Refueling Outages.
2. Recordable Indication was recorded on the Reactor Vessel Upper Internals Upper Support Plate Thermocouple Conduit at Location C-3. The separated conduit cable was previously recorded in 1995 and 2004. The separated conduit at location C-3 showed no noticeable change in separation and was previously acceptable under the Kewaunee Power Station Corrective Action Program.
3. Visual (VT-1 and VT-3) Indications were recoded on 1 Flange. The discrepancy in the actual length of the flange studs and the Quality Part Tag was evaluated by Kewaunee Power Station Engineering Personnel and accepted.
4. Visual (VT-3) Indications recorded on Valve Bonnet Bolting (3 Valves) were: Repaired, Reexamined and Accepted by: Kewaunee Power Station Maintenance and Inservice Inspection Personnel and reviewed by the Authorized Nuclear Inservice Inspector.

Page 3 of 4

5. Visual (VT-2) Indications recorded during System Leakage Pressure 'Tests (30 Items) were:

(1) Evaluated and Accepted or (2) Repaired, Reexamined and Accepted by: Kewaunee Power Station Maintenance Engineering, Program Engineering or Inservice Inspection Personnel and reviewed by the Authorized Nuclear Inservice Inspector.

SUMMARY

An Inservice Inspection Program Plan was performed at the Kewaunee Power Station from February 16,2005 through November 8, 2005 (Non Refueling Outage) and September 2,2006 through October 26, 2006 (Closing of Gl following Refueling Outage). Examinations were performed as scheduled in the Kewaunee Power Station Foui-tl~ 10-Year Inservice Inspection (ISI) Program 2004 -2014 to complete examinations for the 1st period, 4th Interval; A total of 36 Recordable Indications were detected. All Recordable Indications were corrected or accepted by ASh4E Boiler and Pressure Vessel Code Section XI 1998 Edition 2000 Addenda Acceptance Criteria, RepairIReplacement or Evaluarion.

Phillip E. Bukes Date Engineering Programs Inservice Inspection Program Owner Page 4 of 4

Serial No.06-748 2006 INSERVICE INSPECTION

SUMMARY

REPORT EXAMINATION

SUMMARY

FOR INSERVICE INSPECTION CLASS MC PROGRAM FOR FIRST TEN-YEAR INTERVAL KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

KEWAUNEE POWER STATION 2ND OUTAGE: 3RD PERIOD: 1ST INTERVAL 2006 EXAMINATION

SUMMARY

INTRODUCTION An Inservice Inspection (ISI) Program for the Class MC Reactor Building Containment Vessel was performed at the Kewaunee Power Station from April 1 1,2005 through October 26,2006 (Closing of G1 following Refueling Outage) by Kewaunee Power Station and Lambert, MacGill and Thomas Inc. examination personnel.

Examinations were performed to satisfy the requirements of:

ASME Boiler and Pressure Vessel Code Section XI 1992 Edition up to and including 1992 Addenda The Inservice Inspection Program Plan located under Tab C was prepared by Kewaunee Power Station for the 2nd Outage; 3rd Period; 1 st Interval as identified in the Kewaunee Power Station First 10-Year Inservice Inspection (ISI) Program 1996-2006. Examinations during this Refueling Outage were performed to complete the 3rd Period, 1 st Interval Examinations and to complete the 1 st Ten Year Interval examination requirements of ASME Boiler and Pressure Vessel Code Section XI 1992 Edition 1992 Addenda and Kewaunee Power Station First 10-Year Inservice Inspection (ISI) Program 1996-2006.

The following items were examined for the Class MC Reactor Building Containment Vessel:

Accessible Surface Areas Circumferential Weld Seals and Gaskets Airlocks Pressure Retaining Components EXAMINATIONS The examinations performed were in accordance with an approved Inservice Inspection Program Plan located under Tab C of the final report. Examination Procedures were approved prior to the start of examinations and certification documents relative to personnel, equipment and materials were reviewed and determined to be satisfactory.

Page 1 of 3

Some of the arrangements and details of the Kewaunee Power Station Components and Piping Systems were designed and fabricated before ASME Boiler and Pressure Vessel Code Section XI Code requirements were established. Examinations performed were intended to examine 100% of the required surface or volume. In some cases, examinations were limited by geometric, metallurgical or desigdaccess restrictions. In each case, the occurrence and cause of the limitation was documented. In all cases the maximum amount achievable was examined.

Witnessing and surveillance of the examinations were conducted by: Nuclear Regulatory Commission and Hartford Steam Boiler Inspection and Insurance Company of CT.

RESULTS Examinations resulted with the following Recordable Indication being noted on the basis of procedure recording criteria, which are generally more restrictive than specified ASME Boiler and Pressure Vessel Code Section XI Acceptance Standards.

The Recordable Indication detected during the 2006 Refueling Outage is listed in Table 1 with a brief summary following. Specific data relative to the Recordable Indication disposition by acceptance per ASME Boiler and Pressure Vessel Code Section XI 1992 Edition 1992 Addenda Acceptance Criteria, RepairIReplacement or Evaluation is located in Tab F of the Final Report.

TABLE 1 TYPE OR LOCATION OF RECORDABLE INDICATION (RI)

METHOD NO. OF RI'S Reactor Building Containment Vessel General Visual and VT-3 1 Plate

1. General Visual and VT-3 Indication consisting of a scab type indication 3" x 4" located on Plate 158. This scab type indication was accepted by Structural Engineering as a Preservice Surface Imperfection during the 2004 Refueling Outage. Reexamination during the 2006 Refueling Outage revealed no noticeable change in the indication on Plate 158 and was accepted by Kewaunee Power Station Structural Engineering.

Page 2 of 3

SUMMARY

An Inservice Inspection Program for the Class MC Reactor Building Containment Vessel was performed at the Kewaunee Power Station from April 1 1,2005 through October 26,2006 (Closing of G1 following Refueling Outage). Examinations were performed as scheduled in the Kewaunee Power Station First 10-Year Inservice Inspection (ISI) Program 1996-2006. One (1)

Recordable Indication was detected. The Recordable Indication was Accepted by: ASME Boiler and Pressure Vessel Code Section XI 1992 Edition 1992 Addenda Acceptance Criteria and Kewaunee Power Station Structural Engineering Evaluation.

~ ~ u, a o o &

Date Engineering Programs Inservice Inspection Program Owner Page 3 of 3

Serial No.06-748 2006 INSERVICE INSPECTION

SUMMARY

REPORT

SUMMARY

OF EXAMINATIONS THAT WERE LIMITED BY GEOMETRIC, METALLURGICAL, OR DESIGNIACCESS RESTRICTIONS AND ASSOCIATED DATA SHEETS (1 TOTAL)

KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

Serial No.06-748 Docket No. 50-305 Page 1 of 1

SUMMARY

OF EXAMINATIONS THAT WERE LIMITED BY GEOMETRIC, METALLURGICAL, OR DESIGNIACCESS RESTRICTIONS

% Recorded as Not Examined and Limitation 2006 Method of Examination Year Component Identification Steam generator 1 B shell circumferential weld SG-W 10 UT 7.9%

3 - 2" nozzles, 3 - welded pads each 7 314"x 10 314" and weld crown

Serial No.06-748 2006 INSERVICE INSPECTION

SUMMARY

REPORT EXAMINATION

SUMMARY

FOR STEAM GENERATOR EDDY CURRENT TESTING KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

Kcwauncc Powcr Station Steam Generator Eddy Current Jnspcction Summary During the fall 3006 KPS rcfucling outagc, a stcam gcucrator insgcction in accordance with KPS Technical Specification 6.33 was completed for both steam generators 1A and 113.

Each of the following was performed in BOTH steam generators 1 A and 1 B

+

100% Full-Lengtli Inspection utilizing Bobbin Coil

+ 20% Mot Lcg Top of Tubeslicct (+/- 2") utilizing Rotating Coil, biased toward the pcriphcral tubes

+ 20% Row 1 u-bend region utilizing Rotating Coil

+

100'!40 of Dings, Dents, and Bulges > 2 volts with Rotating Coil

+

100% of Bobbin identified Possible Loosc Parts with Rotating Coil

+

100% of Bobbin identified I-codes with Rotating Coil N o active degradation mcclianisms were discovered during the fall 2006 inspection.

No tubes required plugging or in situ pressurc testing during the fall 2006 inspection.

To date, following the fall 2006 inspection, there are zero total tubes plugged in both steam generator 1 A and 1 B.

Condition Monitoring was completed. Ncither steam generator 1 A nor 1 B exceeded any performance criteria during the last inspcction cycle (since spring 2003 inspection). No damage mechanisms were required to be evaluated due to the lack of a degradation nicclianisrn being found during the inspection. Steam Generator Operational Assessment from spring 2003 inspection was concluded to be conservative and no corrective actions were required.

There are zero tubes plugged and zero sleeves installed in both steam generator 1A and 1B. Therefore, effective plugging is 0% (zero) in both steam generator 1A and 1B.

Brent R. Dunn Date Engineering Programs Steam Generator Program Owner