BW060043, April 2006 Steam Generator Inservice Inspection Report
| ML061280652 | |
| Person / Time | |
|---|---|
| Site: | Braidwood |
| Issue date: | 05/08/2006 |
| From: | Polson K Exelon Generation Co, Exelon Nuclear |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| BW060043 | |
| Download: ML061280652 (2) | |
Text
___
Exe~n Company, LLC w~w exeIcncoTp~co~
Nuc] ear
~t7C May 8, 2006 BW060043 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 205550001 Braidwood Station, Unit 1 Facility Operating License No. NPF 72 NRC Docket No. STN 50-456
Subject:
April 2006 Steam Generator Inservice Inspection Report In accordance with Technical Specification 5.6.9, Steam Generator (SG) Tube Inspection Reports, Exelon Generation Company, LLC is reporting the number of tubes plugged or repaired during the SG inservice inspection activities conducted during the Braidwood Station Unit 1 April 2006, twelfth refueling outage, (Al R12). Technical Specification 5.6.9.a requires that following each inservice inspection of the SG tubes, the number of tubes plugged or repaired in each SG shall be reported to the NRC within 15 days.
The Braidwood Station Al Rl 2 SG tube eddy current inspection scope included 100% full-length bobbin coil inspection, and 20% +PointM inspection of the hot leg top of tubesheet region of the lA, 1 B, 1 C and 1 D SGs. Additionally, +PointTM was conducted on bobbin coil indications classified as requiring additional diagnostic testing.
The SG tube inspections were completed on April 26, 2006. No tube sleeving was performed this outage. The following table provides the number of tubes removed from service during Al Rl2 and the total number of tuhe~removed from service to date by tube plugging.
Braidwood Unit 1 Steam Generator Tube Plugging Summary SG A SG B SG C SG D Total
~reviously Plugged 10 14 5
1 30 Plugged During Al Ri 2 11 17 0
0 28 Total 21 31 5
1 58
May 8, 2006 U.S. Nuclear Regulatory Commission Page 2 Please direct any questions regarding this submittal to Dale F. Ambler, Braidwood Regulatory Assurance Manager, at (815) 417-2800.
Sincerely, Keith fPolson Site Vice President Braidwood Station