Probabilistic Safety Assessment, Summary Report
ML042860095
Person / Time
Site: Browns Ferry Tennessee Valley Authority icon.png
Issue date: 02/23/2004
From: Mikschl T
ABS Consulting
To:
Office of Nuclear Reactor Regulation
References
R05 040921 001
Download: ML042860095 (37)


Text

t 41 R05 040921 001 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT PROBABILISTIC SAFETY ASSESSMENT UNIT 2

SUMMARY

REPORT Revision 2 RIf OSUIGBS Donsulting RISK CON'SULTING DIVISION

TENNESSEE VALLEY AUTHORITY SYSTEMS AND ANALYSIS BROWNS FERRY NUCLEAR PLANT PROBABILISTIC SAFETY ASSESSMENT UNIT 2

SUMMARY

REPORT Revision 2 February 2004

7I Unit 2 Summary Report Browns Ferry Nuclear Plant Probabilistic Safety Assessment REVISION LOG Unit 2 Summary Report e

Description of Revision Date DatChecked Da t By I 0

Initial Issue S. Rodgers D. Bidwell D. McCamy 1

Changes from EPU S. Rodgers D. Johnson H. Jones M. Xlng 5-13-03 2

Resolve minor comments identified in SAMA T. Mikschl/

D. H. Johnson/

H. Jones analysis.

2-23-04 2-23-04 9-21-04 BFNS Unit 2 Summary Rpt (Rev 2).doc i

S1059446-1426-022304

T l

Unit 2 Summary Report TABLE OF CONTENTS Section Page 1.0 EXECUTIVE

SUMMARY

1-1

1.1 BACKGROUND

AND OBJECTIVES.

................................ 1-1 1.2 PLANT FAMILIARIZATION...................................

1-1 1.3 OVERALL METHODOLOGY...................................

1-2 1.4

SUMMARY

OF MAJOR FINDINGS...................................

1-4 1.4.1 Total Core Damage and' Large Early Release Frequency.

1-5 1.4.2 Contributors to Total Core Damage Frequency.1-8 1.4.2.1 Important Core Damage Sequence Groups.

1-8 1.4.2.2 Analysis of Individual Sequences.1-16 1.4.2.3 Important Operator Actions.1-19 1.4.2.4 Important Plant Hardware Characteristics.

1-20 1.4.3 Results for Large Early Release Frequency.1-22 1.4.3.1 Important Plant Hardware Characteristics for Containment Performance.1-22 1.4.3.2 Comparison with the 2002 Browns Ferry Unit 2 PRA, Revision 0.1-23 1.5 INSIGHTS.........

1-23 APPENDIX A Unit 2 Top Ranking Sequences Contributing to CDF BFNJUrut 2 Summary Rpt (Rev 2).doc ii S1059446-14264022304

Unit 2 Summary Report LIST OF TABLES TABLE 1-1 COMPARISON WITH OTHER PRAS..........................................................

1-7 TABLE 1-2 UNIT 2 INITIATING EVENT GROUP CONTRIBUTIONS TO CORE DAMAGE FREQUENCY..........................................................

1-10 TABLE 1-3

SUMMARY

OF THE CORE DAMAGE ACCIDENT SEQUENCE SUBCLASSES..........................................................

1-14 TABLE 1-4 BREAKDOWN OF CORE DAMAGE SEQUENCES IN EACH FREQUENCY RANGE..........................................................

1-16 TABLE 1-5 BROWNS FERRY UNIT 2 IMPORTANT OPERATOR ACTIONS............. 1-20 TABLE 1-6 BROWNS FERRY UNIT 2 IMPORTANT SYSTEMS (REVISE)................. 1-21 TABLE 1-7

SUMMARY

OF REVISED HUMAN ERROR PROBABLITIES................... 1-23 LIST OF FIGURES FIGURE1-1 UNCERTAINTY CURVE FOR BROWNS FERRY UNIT 2 CORE DAMAGE FREQUENCY..................................................................................................................... 1-5 FIGURE1-2 UNCERTAINTY CURVE FOR BROWNS FERRY UNIT 2 LARGE EARLY RELEASE FREQUENCY........................................................

1-6 FIGURE 1-3 BROWNS FERRY UNIT 2 CORE DAMAGE FREQUENCY BY INITIATING EVENT CATEGORY.......................................................

1-9 BFNUnit 2 Summary Rpt (Rev 2).doc

,iii S1059446-1426 022304

Unit 2 Summary Report SECTION 1 EXECUTIVE

SUMMARY

1.1 BACKGROUND

AND OBJECTIVES This documents the performance by the Tennessee Valley Authority (TVA) in updating the Unit 2 PSA. An integrated team of engineers and specialists from TVA and ABS Consulting performed this revision TVAs overall objectives for this revision were to incorporate the Extended Power Uprate into the PSA.

The purpose of this summary is to present the results of the PSA on Browns Ferry Unit

2. These results include an estimate of the total core damage frequency (CDF); data uncertainties in the estimated CDF; and the large early release frequency (LERF) data uncertainties in the estimated LERF.

This summary also provides the sequences, systems, and sources of uncertainty that are the significant contributors to the results.

1.2 PLANT FAMILIARIZATION The Browns Ferry Nuclear Plant is located on the north shore of Wheeler Lake at Tennessee River mile 294 in Limestone County, Alabama. The site is approximately 10 miles southwest of Athens, Alabama, and 10 miles northwest of Decatur, Alabama.

The plant consists of three units, with Unit 1 rated power level of 3,293 MWt and Unit 2 and 3 rated at 3,952 MWt. Unit 2 and Unit 3 are the only units currently operating.

Unit 2 is a single-cycle forced-recirculation boiling water reactor (BWR) nuclear steam supply system supplied by General Electric Corporation.

Major structures at Browns Ferry Unit 2 include a reactor building with a Mark I drywell containment, a turbine building, a control bay, and an intake pumping station.

BFN-Unit 2 Summary Rpt (Rev 2).doc 1-1 S1059446-14264022304

Unit 2 Summary Report A detailed description of the plant site, facilities, and safety criteria is documented in the Browns Ferry Final Safety Analysis Report (Reference 1-2).

1.3 OVERALL METHODOLOGY The Browns Ferry Unit 2 PSA is founded on a scenario-based definition of risk (Reference 1-3). In this application, "risk" is defined as the answers to three basic questions:

1.

What can go wrong?

2.

What is the likelihood?

3.

What are the consequences?

Question I is answered with a structured set of scenarios that is systematically developed to account for design and operating features specific to Browns Ferry Unit 2.

Question 2 is answered with a prediction or estimate of the frequency of occurrence of each scenario identified in the answer to question 1. Since there is uncertainty in that frequency, the full picture of likelihood is conveyed by a probability curve that conveys the state of knowledge, or confidence, about that frequency.

Question 3 is answered in two ways. One measure is the core damage frequency. The loss of adequate core cooling is defined as the rapid increase in fuel clad temperature due to heating and Zircaloy-water reactions that lead to sudden deterioration of fuel clad integrity. For the purposes of the Level 1 PSA a surrogate has been developed that can be used as a first approximation to define the onset of core damage. The onset of core damage is defined as the time at which more than two-thirds of the active fuel becomes uncovered, without sufficient injection available to recover the core quickly, i.e., water level below one-third core height and falling. The other measure is the large, early BFN.Unft 2 Summary Rpt (Rev 2).doc 1-2 S1059446-14264022304

Unit 2 Summary Report release frequency. The original IPE answered question 3 in a Level 2 PSA, in terms of the key characteristics of radioactive material release that could result from the sequences identified. Consistent with recent PSA practice, BFN does not track the entire spectrum of releases. Instead, it tracks the frequency of large, early releases. A large early release is defined as the rapid, unscrubbed release of airborne fission products from the containment to the environment occurring before the effective implementation of off-site emergency response and protective actions. The results reported here are based on the methods that conform to the NRC guidelines (Reference 1-1, Appendix 1) and the IEEE/ANS "PSA Procedures Guide" (Reference 1-4).

A large fraction of the effort needed to complete this PSA was to develop a plant-specific model to define a set of accident sequences. This model contains a large number of scenarios that have been systematically developed from the point of initiation to termination. A series of event trees is used to systematically identify the scenarios.

Given the knowledge of the event tree structures, accident sequences are identified by specifying:

1.

The initiating event.

2.

The plant response in terms of combinations of systems and operator responses.

3.

The end state of the accident sequence.

The RISKMANW PC-based software system (Reference 1-5) was used to construct effectively a single, large tree for Level 1 and LERF. The sequence analyses start with an initiating event and terminate in end states of LERF or no LERF. The sum of these two end states is the CDF.

The initiating events and the event tree branching frequencies are quantified using different types of models and data. The system failures that contribute to these events are analyzed with the use of fault trees that relate the initiating events and event tree branching frequencies to their underlying causes. These causes are quantified, in turn, BFN_Urit 2 Summary Rpt (Rev 2).doc 1-3 S1059446-1426-022304

Unit 2 Summary Report by application of models and data on the respective unavailabilities due to hardware failure, common cause failure, human error, and test and maintenance unavailabilities.

The frequencies of initiating events, the hardware failure rates of the components, and operator errors were obtained using either generic data or a combination of generic and plant-specific data.

Dependency matrices have previously been developed from a detailed examination of the plant systems to account for important interdependencies and interactions that are highly plant specific. To facilitate a clear definition of plant conditions in the scenarios, separate stages of event trees are provided for the response of the support systems (e.g., electric power and cooling water), the frontline systems [e.g., high pressure coolant injection (HPCI) and residual heat removal (RHR)], and the containment phenomena; e.g., containment overpressurization failure. A separate tree is used to determine core damage and develop plant damage classes. This tree provides the interface between the Level 1 and Level 2 event trees.

The systematic, structured approach that is followed in constructing the accident scenario model provides assurance that plant-specific features are identified. It also provides insights into the key risk controlling factors.

1.4

SUMMARY

OF MAJOR FINDINGS The major findings of the Browns Ferry Unit 2 Level 2 PSA are presented in this section.

The results delineate the principal contributors to risk, and provide insights into plant and operational features relevant to safety. The presentation describes both the core damage and large early release results.

BFNUnft 2 Summary Rpt (Rev 2).doc 1-4 S1059446-1426-022304

Unit 2 Summary Report 1.4.1 Total Core Damage and' Large Early Release Frequency The total CDF for Browns Ferry Unit 2 was found to be 2.6 x 10-6 per reactor-year. The results for CDF were developed in terms of a mean point estimate. The CDF data uncertainty curve is shown in Figure 1-1.

The total Large Early Release Frequency (LERF) for Browns Ferry Unit 2 was found to be 3.9 x 10 7 per reactor year. The results for LERF were developed in terms of a mean point estimate. The LERF data uncertainty curve is shown in Figure 1 -2.

}E 43
.4

-.#.3

.A

.M L

4 -'

I I

S 9<~-.

/

x

.s

'3/4 I

.4:

F~re~queno

.C:

Figurel-1 Uncertainty Curve for Browns Ferry Unit 2 Core Damage Frequency BFN-Unit 2 Summary Rpt (Rev 2).doc 1-5 S1059446-1426-022304

Unit 2 Summary Report V-W...

_.S...

... Qatar, 42

.42

'-I Die 33

  • -4 r.-0I.t Ia.

i t/

i:/

II I

t IIkI

.i IkIIIIIII IIII.IIII I

. I 1,

iV4, so

. 'so?.

Oh

.SFx<7

......................................................-................................ I.- I.....................

  • WI

.e Frervenac Figurel-2 Uncertainty Curve for Browns Ferry Unit 2 Large Early Release Frequency BFN_Unit 2 Summary Rpt (Rev 2).doc 1-6 S1059446-14264022304

Unit 2 Summary Report A comparison of this study with other PSAs on other plants that used similar methods, databases, and work scopes is given in Table 1-1.

The calculated mean CDF for Browns Ferry Unit 2 is of the same order of magnitude as Quad Cities, Peach Bottom Unit 2 and Grand Gulf Unit 1, and an order of magnitude lower than that reported for Nine Mile Point Unit 2 (which includes external events).

Table 1-1 Comparison with Other PRAs Plant Flood Included Mean CDF 1 Reference Mean LERF 1 l

(per reactor-year)

(per year)

Quad Cities Yes 4.6E-6 1-7 3.3E-6 Nine Mile Point Unit 2*

Yes 5.7E-5 1-8 1.6E-6 Browns Ferry Unit 2 Yes 2.6E-6 This Study 3.9E-7 Peach Bottom Unit 2 No 4.5E-6 1-9 Not Updated Grand Gulf Unit I No 5.5E-6 1-10 Not Updated

'Includes external events.

Factors that contribute to the results for Browns Ferry Unit 2 are summarized below:

  • The increase in core thermal power resulting from the EPU eliminated the use CRD as an alternative injection source if the vessel remains at high pressure and other injection sources fail. The increase in the CDF estimate from Revision 0 is largely due to the elimination of this success path.
  • The accident sequences that were analyzed are those initiated by internal events and internal floods. Sequences initiated by internal fires, seismic events, and other external events have not been modeled in this internal events model.
  • The current results do not reflect any future plant or procedural changes that TVA may decide to make to improve safety.

This study used plant specific data to update failure rates for selected components and initiating events frequencies. The common cause parameters of the multiple Greek model used in this study were estimated with the benefit of a plant-specific screening of industry common cause event data in accordance BFN-Unit 2 Summary Rpt (Rev 2).doc 1-7 S1 059446-1426402230.4

Unit 2 Summary Report with NUREG/CR-4780 (Reference 1-11). The common cause event data was taken from the NRC database (Reference 1-14). Common cause estimates not screened were taken from NUREG/CR-5497.

1.4.2 Contributors to Total Core Damage Frequency In the quantification of the Level 1 event sequence models, the principal contributors to the CDF were identified from several vantage points. The results and contributors are summarized in this section. Causes for individual system failures are listed in each systems analysis notebook.

1.4.2.1 Important Core Damage Sequence Groups The importance of initiating events was examined by determining the contributions of core damage sequences grouped by initiating event. The ranked results are shown in Figure 1-3 and Table 1-2 for major initiating event categories.

Transients with the Power Conversion System (PCS) unavailable as a result of the initiator account for 34.6% of the CDF. Loss of condenser heat sink, which includes closure of the main steam isolation valves and turbine trip without bypass, are specific examples of initiator in this group.

Transients with the PCS not disabled as a result of the initiator contribute 29.1% to the core damage frequency. The turbine trip, in which the main steam isolation valves and turbine bypass are available, is a specific example of an initiator in this group.

The Loss of Offsite Power (LOSP) initiators include station blackout sequences (failure of all diesel generators) and non-station blackout scenarios in which core damage resulted from other failures.

These other failures include battery board failures (resulting in loss of high pressure injection and failure to achieve low pressure injection)

BFNfUnit 2 Summary Rpt (Rev 2).doc 1-8 S1059446-1426-022304

Unit 2 Summary Report and decay heat removal failures. Overall, the LOSP initiated sequences account for 18.4% of CDF.

03 0)0.

40 35 30 25 20 15 10 5

0

'elo Figure 1-3 Browns Ferry Unit 2 Core Damage Frequency by Initiating Event Category BFN-Unit 2 Summary Rpt (Rev 2).doc 1-9 S1059446-1426-022304

Unit 2 Summary Report Table 1-2 Unit 2 Initiating Event Group Contributions to Core Damage Frequency Initiating Event Category Mean CDF Percentage of Total (per reactor-year)

Transients with PCS Unavailable 9.08E-07 34.6 Transients with PCS Available 7.65E-07 29.1 Loss of Offslte Power 4.82E-07 18.4 Support System Failures 2.22E-07 8.4 Internal Floods 1.01E-07 3.9 LOCAs 9.97E-08 3.8 Stuck-Open Relief valves 4.69E-08 1.8 Total 2.6E-06 100 Support system failure initiators (specifically, loss of plant air, loss of raw cooling water, or loss of either l&C bus 2A or 2B failures) contribute 8.4% to the total CDF.

Scenarios initiated by internal floods contribute 3.9% to the core damage frequency. No internal flooding scenarios lead directly to core damage but require additional hardware failures. Flooding initiators were postulated in the Unit 2 reactor building, in the Unit I or Unit 3 reactor building, and in the turbine building (two sizes).

LOCAs and interfacing systems LOCAs (i.e., when the boundary between a high and a low pressure system fails and the lower pressure system overpressurizes) make up 3.8% of the total CDF.

Scenarios initiated by the inadvertent opening of one or more safety relief valves (SRVs) contribute 1.8% the core damage frequency.

Two distinct initiators are considered: opening of one SRV, and opening of two or more SRVs.

The preceding paragraphs considered the contribution to the total CDF from groups of initiating events. The sequences leading to core damage were also reviewed to identify common functional failures.

BFN_Unit 2 Summary Rpt (Rev 2).doc 1-10 S1059446-14264022304

Unit 2 Summary Report An event sequence classification into five accident sequence functional classes can be performed using the functional events as a basis for selection of end states.

The description of functional classes is presented here to introduce the terminology to be used in characterizing the basic types of challenges to containment.

The reactor pressure vessel condition and containment condition for each of these classes at the time of initial core damage is noted below:

Core Damage RPV Condition Containment Functional Class Condition Loss of effective coolant inventory (includes high and low Intact pressure inventory losses) if Loss of effective containment pressure control, e.g., heat Breached or Intact removal III LOCA with loss of effective coolant Inventory makeup Intact IV Failure of effective reactivity control Breached or Intact V

LOCA outside containment Breached (bypassed)

In assessing the ability of the containment and other plant systems to prevent or mitigate radionuclide release, it is desirable to further subdivide these general functional categories.

In the second level binning process, the similar accident sequences grouped within each accident functional class are further discriminated into subclasses such that the potential for system recovery can be modeled. These subclasses define a set of functional characteristics for system operation which are important to accident progression, containment failure, and source term definition. Each subclass contains front end sequences with sufficient similarity of system functional characteristics that the containment accident progression for all sequences in the group can be considered to behave similarly in the period after core damage has begun. Each subclass defines a unique set of conditions regarding the state of the plant and containment systems, the physical state of the core, the primary coolant systems, and the containment boundary at the time of core damage, as well as vessel failure.

BFNUnit 2 Summary Rpt (Rev 2).doc 1-1 1 S1059446-1426-022304

Unit 2 Summary Report The important functional characteristics for each subclass are determined by defining the critical parameters or system functions that impact key results. The sequence characteristics that are important are defined by the requirements of the containment accident progression analysis.

These include the type of accident initiator, the operability of important systems, and the value of important state variables (e.g., reactor pressure) that are defined by system operation.

The interdependencies that exist between plant system operation and the core melt and radionuclide release phenomena are represented in the release frequencies through the binning process involving these subclasses, as shown in past PRAs and PRA reviews. The binning process, which consolidates information from the systems' evaluation of accident sequences leading to core damage in preparation for transfer to the containment-source term evaluation, involves the identification of 13 classes and subclasses of accident sequence types.

Table 1-3 provides a description of these subclasses that are used to summarize the Level 1 PRA results.

Published BWR PRAs have identified that there may be a spectrum of potential contributors to core melt or containment challenge that can arise for a variety of reasons. In addition, sufficient analysis has been done to indicate that the frequencies of these sequences are highly uncertain; and therefore, the degree of importance on an absolute scale and relative to each other, depends upon the plant specific features, assumptions, training, equipment response, and other items that have limited modeling sophistication.

This uncertainty means that the analyst can neither dismiss portions of the spectrum from consideration nor emphasize a portion of the spectrum to the exclusion of other sequence types.

This is particularly true when trying to assess the benefits and competing risks associated with a modification of a plant feature.

This end state characterization of the Level 1 PRA in terms of accident subclasses is usually sufficient b characterize the CET entry states for most purposes. However, BFN_Unit 2 Sumnmary Rpt (Rev 2).doc 1-12 S1059446-1426-022304

Unit 2 Summary Report when additional refinement is required in the CET quantification, it may be useful to further discriminate among the contributors to the core damage accident classes. This discrimination can be performed through the use of the individual accident sequence characteristics.

BFNUnft 2 Summary Rpt (Rev 2).doc 1-13 S1059446-1426-022304

Unit 2 Summary Report Table 1-3 Summary of the Core Damage Accident Sequence Subclasses Class I WASH-I1400 Definition Designator Example Accident sequences Involving loss of Inventory TQUX makeup In which the reactor pressure remains high.

T Accident sequences involving a station blackout and TEQUV loss of coolant Inventory makeup.

Accident sequences Involving a loss of coolant Inventory Induced by an ATWS sequence with TTCMQU containment Intact.

Accident sequences Involving a loss of coolant Inventory makeup In which reactor pressure has been successfully reduced to 200 psi; i.e., accident TQUV sequences initiated by common mode failures disabling multiple systems (ECCS) leading to loss of coolant inventory makeup.

Accident sequences Involving loss of Inventory makeup In which the reactor pressure remains high and DC power Is unavailable.

Accident sequences Involving a loss of containment heat removal with the RPV Initially Intact; core damage TW Induced post containment failure Accident sequences Involving a loss of containment heat removal with the RPV breached but no Initial core AW damage; core damage after containment failure.

Accident sequences Involving a loss of containment heat removal with the RPV Initially intact; core damage N/A Induced post high containment pressure Class IIA or IIL except that the vent operates as designed; loss of makeup occurs at some time TW following vent Initiation. Suppression pool saturated but intact.

Class II BFN_Unt 2 Summary Rpt (Rev 2).doc 1-14 S1059446-14264022304

Unit 2 Summary Report Table 1-3 Summary of the Core Damage Accident Sequence Subclasses AccidentClass Subclass l Definition Designator Designator Ex___________

ample Class Ill A

Accident sequences leading to core damage LOCA) conditions Initiated by vessel rupture where the R

containment integrity is not breached in the Initial time phase of the accident.

B Accident sequences initiated or resulting in small or medium LOCAs for which the reactor cannot be SQUX depressurized prior to core damage occurring.

C Accident sequences initiated or resulting In medium or large LOCAs for which the reactor Is a low pressure AV and no effective injection is available.

D Accident sequences which are initiated by a LOCA or RPV failure and for which the vapor suppression AD system Is inadequate, challenging the containment integrity with subsequent failure of makeup systems.

Class IV A

Accident sequences Involving failure of adequate (ATWS) shutdown reactivity with the RPV Initially Intact; core TTCMC2 damage Induced post containment failure.

L Accident sequences involving a failure of adequate shutdown reactivity with the RPV Initially breached N/A (e.g., LOCA or SORV); core damage induced post containment failure.

T Accident sequences Involving a failure of adequate shutdown reactivity with the RPV initially intact; core N/A damage induced post high containment pressure.

V Class IV A or L except that the vent operates as designed, loss of makeup occurs at some time N/A following vent initiation. Suppression pool saturated but intact.

Class V Unisolated LOCA outside containment N/A For BFN, functional based plant damage states are used to summarize Level 1 results and to ensure that the Level 2 CETs are sufficient to allow each functional sequence to be addressed.

BFNUunit 2 Summary Rpt (Rev 2).doc 1-15 S1059446-1426 022304

Unit 2 Summary Report 1.4.2.2 Analysis of Individual Sequences A large number of sequences make up the total CDF. Table 1-4 provides information on the distribution of core damage sequences across the frequency range.

Table 1-4 Breakdown of Core Damage Sequences in Each Frequency Range Frequency Range I

Number of Sequences l

Percentage of CDF (events per year)

I I

>1 E-07 1

6

>1E-08 29 31

>1 E-09 294 58

>1E-10 2459 80

>1 E-11 17,251 96

>1E-12 (base case) 36,023 100 The following presents a brief description of the 15 highest-ranking sequences to the CDF.

A loss of condenser heat sink initiates the first sequence. The initiator directly causes a loss of reactor feedwater, degrading high pressure injection capabilities. Subsequent failures of HPCI and RCIC eliminate all of high pressure injection.

The emaining success path of low pressure injection is not viable because of a failure to depressurize.

A lack of inventory causes core damage.

Sequence 2 is a non-minimal version of sequence one, representing a different path in the LERF event tree.

A general transient initiates the third sequence.

A subsequent loss of the main condenser results in a situation identical to the first sequence initiator, a loss of the condenser heat sink. The remainder of sequence three is identical to that of sequence 1.

BFN-Unft 2 Summary Rpt (Rev 2).doc 1-16 S1059446-1426-022304

Unit 2 Summary Report The fourth sequence is that of an interfacing system LOCA that results in core damage.

This sequence represents the total contribution from a variety of interfacing system LOCAs. An interfacing system LOCA is initiated by leakage of reactor coolant through valves that separate the nuclear boiler from the RHR or core spray systems.

Sequence 5 is the classic SBO following a total LOSP. The unit 1/2 diesel generators fail and the Unit 3 diesel generators fail by common cause.

Offsite power is not recovered before core damage occurs.

Sequence 6 is initiated by a loss of offsite power to Unit 2.

Although the diesel generators are successful, this sequence progress to core damage as HPCI and RCIC fail, followed by a failure to depressurize.

A general transient initiates sequence 7. It is similar to sequence 3 but the failure of Feedwater is caused by the failure of the turbine bypass valves.

Sequence 8 is a non-minimal version of sequence 1. The additional failure is Unit 3 at power.

Sequence 9 is similar to sequences 1 and 2 but represents a different path in the LERF event tree.

A general transient initiates sequence 10. It is similar to sequence 3 but the failure of reactor feedwater is caused by the failure of the turbine bypass valves.

Sequence 11 is similar to sequence 5. There is a logic error that fractures sequence five. The sum of sequence five and sequence eleven is correct.

BFNUnit 2 Sunmary Rpt (Rev 2).doc 1-17 S1059446-1426-022304

Unit 2 Summary Report Sequence 12 is also initiated by a loss of offsite power to both units. The combination of failures of emergency diesel generators results in failure of the EECW, which causes core damage due to the failure of components requiring EECW. Note that there are four trains of RHRSW/EECW with the number 3 pump in each train dedicated to EECW.

The number 2 pump in each train is dedicated to RHR heat exchangers, and the number I pump in each train aligned as a back up the number 2 pump but capable of being aligned to backup the number 1 pump.

Furthermore, trains C and D can be realigned via MOVs but trains A and B use manual values that require local operation.

In this scenario DGs B, C, 3EA, and 3EB also fail. The failure of DG B and DG 3EB fail the C train. The failure of DG 3A fails the A3 EECW pump. The failure of DG C fails the B3 EECW pump. Three EECW pumps hae failed and the success criteria for EECW are that two pumps are required. Since the A and C realignment is local, the EECW system cannot be restored before the DGs fail on loss of cooling. Equipment fails due to lack of EECW and offsite power is not recovered in time.

Sequence 13 is similar to sequence 12 except that different combinations of diesel generators fail such that the EECW success criterion is not met. In this case, the C, D, 3EA, and 3ED diesel generators fail.

Sequence 14 is a non-minimal version of sequence three.

Sequence 15 is a non-minimal version of sequence two.

Appendix A of this report presents a listing of the top 50 core damage sequences.

The table below shows the frequency, percentage of total, and the cumulative percentage of total for the sequences discussed above.

BFNUrit 2 Summary Rpt (Rev 2).doc 1-18 S1059-446-1426-022304

Unit 2 Summary Report lSequence l Frequency

% CDF Cumulative %

1 1.58E-07 6.0 6.0 2

5.84E-08 2.2 8.2 3

5.76E-08 2.2 10.4 4

4.63E-08 1.8 12.2 5

4.56E-08 1.7 13.9 6

4.38E-08 1.7 15.6 7

2.96E-08 1.1 16.7 8

2.77E-08 1.1 17.8 9

2.44E-08 0.9 18.7 10 2.42E-08 0.9 19.6 11 2.39E-08 0.9 20.6 12 2.29E-08 0.9 21.4 13 2.29E-08 0.9 22.3 14 2.13E-08 0.8 23.1 15 1.75E-08 0.7 23.8 1.4.2.3 Important Operator Actions The importance of a specific operator action was determined by summing the frequencies of the sequences involving failure of that action and comparing that sum to the total CDF. The importance is the ratio of that sum to the total CDF.

Table 1-5 summarizes the important operator action failures ranked in order of their impact on the total CDF.

The operator actions to recover electric power are not included in Table 1-5 because they are a complex function of the time available and the specific equipment failures involved. No other HEPs are shown because of a dramatic fall off in importance.

BFN-rUnit 2 Summary Rpt (Rev 2).doc 1-19 S1059446-14264022304

Unit 2 Summary Report Table 1-5 Browns Ferry Unit 2 Important Operator Actions Operator Action l

Fraction Importance Depressurize to Allow Low Pressure Injection ORVD2 56.4 Open the Hardened Wetwell Vent OLP2 8.7 Align Alternate Injection to Reactor Vessel via the Unit 3 to Unit 2 U32A 6.8 RHR Crosstie*

Operator Aligns Suppression Pool Cooling OSP1 5.1

  • The importance of the Split Fraction U32A was weighted by the relative contribution of the human action contained In the system analysis 1.4.2.4 Important Plant Hardware Characteristics An importance analysis of plant system failure modes to the total CDF was also performed.

Only hardware failures involving the system itself are considered in Table 1-6, which provides a ranking in order of their impact on the total CDF.

BFN_Unit 2 Summary Rpt (Rev 2).doc 1-20 S1059446-1426-022304

Unit 2 Summary Report Table 1-6 Browns Ferry Unit 2 Important Systems (REVISE)

System

% CDF HPCI 64 RCIC 58 Diesel Generators 17 Feedwater/Condensate 15 RHR 15 RPS 12 Main Steam 11 Standby Liquid Control 4

RHRSW to RHR Loop 11 3

RHRSW to RHR Loop I 3

Control Rod Drive 2

Core Spray 1

The system importance means the fraction of the CDF involving partial or complete failure of the indicated system. These importance measures are not strictly additive because multiple system failures may occur in the same sequence. The importance rankings account for failures within the systems that lead to a plant trip, or failures that limit the capability of the plant to mitigate the cause of a plant trip.

Consequential failures resulting from dependencies on other plant systems [e.g., the loss of drywell control air due to failure of reactor building closed cooling water (RBCCW)] are not included in this importance ranking.

BFNUnit 2 Summary Rpt (Rev 2).doc 1-21 S1059446-1426-22304

Unit 2 Summary Report 1.4.3 Results for Large Early Release Frequency This section summarizes the limited results for the Level 2 analysis, which estimates the large containment failure and subsequent early release of radionuclides known as LERF. In contrast to the IPE submittal, this update concerned itself with two metrics, core damage frequency and large early release frequency. This section presents the LERF results and contributors.

The update results indicate that about 15% of the core damage scenarios result in LERF. Typically, LERF as a percentage of CDF for BWRs ranges from 10% to almost 50%. These are generally highly dependent on the level 1 results. BFN Unit 2 falls in the mid-range for BWRs.

This release category represents the most severe source term scenario.

Here the containment failures are dominated by drywell shell failures (due to thermal interactions with the molten core debris on the drywell floor). The important post-core damage contributors are drywell shell failures, in-vessel recovery, and the effectiveness of the reactor building in scrubbing the release. With respect to pre-core damage top events, the failure of the RPS system dominates.

1.4.3.1 Important Plant Hardware Characteristics for Containment Performance As discussed in the previous Section 1.4.3.1, the dominant contributor to the most significant release category group (large, early containment failure and large bypasses) is drywell shell thermal attack from corium on the drywell floor. This is representative for most Mark I containments. The likelihood of drywell shell thermal attack failure is significantly reduced if the drywell floor is flooded with water prior to vessel breach.

Drywell spray represents an important hardware component since it is the primary means of flooding the drywell.

BFNUnit 2 Summary Rpt (Rev 2).doc 1-22 S1 059446-1426-022304

Unit 2 Summary Report 1.4.3.2 Comparison with the 2002 Browns Ferry Unit 2 PRA, Revision 0 TVA has previously performed an individual plant examination in accordance with the U.S. Nuclear Regulation Commission (NRC) Generic Letter No. 88-20 (Reference 1-1).

The IPE was revised on several occasions. PSA Revision 0 marked the change from IPE to an application and risk informed approach.

This Revision 2 reflects plant operations with the extended power uprate. The increase in thermal power eliminated the use of the CRD system as an effective injection source when the vessel remains at high pressure and the other high pressure injection sources have failed. The increase in thermal power also required revisions to some human actions due to the change in sequence timing. See Table 1 -7.

Table 1-7 Summary of Revised Human Error Probabilities Operator l

Current l

Previous Notes Action HEP HEP HOADI 4.89E-03 3.45E-03 Inhibit ADS During ATWS with Unisolated Vessel HOAD2 9.52E-03 4.64E-03 Inhibit ADS During ATWS with Isolated Vessel HOAL2 1.29E-01 3.91E-02 Lower and Control Vessel Level HOSLI 1.61 E-02 6.71 E-03 Initiate SLCS Given ATWS with Unisolated RPV.

HOSL2 7.71E-02 3.50E-02 Initiate SLCS, Given an ATWS with RPV Isolated 1.5 INSIGHTS The power increase eliminated the use of CRD as a viable high pressure injection if the vessel remains at high pressure. The increase in CDF given EPU as compared to the current model is almost entirely due to this elimination. The high pressure injection systems and the operator action to depressurize are much more important given EPU.

BFN.Unit 2 Summary Rpt (Rev 2).doc 1-23 S1059446-1426-022304

Unit 2 Summary Report BFNUnt 2 Summary Rpt (Rev 2).doc2 1-24 S1059446-1426-022304

Unit 2 Summary Report SECTION 2 REFERENCES 1-1.

U.S. Nuclear Regulatory Commission, "Individual Plant Examination for Severe Accident Vulnerabilities",

10CFR50.54(y, Generic Letter No. 88-20, November 23,1988.

1-2.

Tennessee Valley Authority, "Browns Ferry Nuclear Plant Final Safety Analysis Report".

1-3.

Kaplan, S., and Garrick, B. J., "On the Quantitative Definition of Risk," Risk Analysis, Vol.1, pp.11-37, March 1981.

1-4.

American Nuclear Society and Institute of Electrical and Electronics Engineers, "PRA Procedures Guide; A Guide to the Performance of Probabilistic Risk Assessments for Nuclear Power Plants," sponsored by U.S. Nuclear Regulatory Commission and Electric Power Research Institute, NUREG/CR-2300, April 1983.

1-5.

PLG, Inc., "RISKMAN -

RA Workstation Software", Users Manuals l-IV, Version 5.11,1994.

1-6.

Deleted 1-7.

Conversation between Shawn S. Rodgers, ERIN Engineering and Research, Inc. and Xavier Polanski, Commonwealth Edison Co., May 17, 2000.

1-8.

Conversation between Shawn S. Rodgers, ERIN Engineering and Research, Inc. and Leo Kacanik, Niagra Mohawk, May 17, 2000.

1-9.

Conversation between Shawn S. Rodgers, ERIN Engineering and Research, Inc. and Greg Kreuger, PECO, May 17, 2000.

1-10.

Conversation between Shawn S. Rodgers, ERIN Engineering and Research, Inc. and Gary Smith, Entergy, May 17, 2000.

1-11.

Mosleh, A., et al., "Procedures for Treating Common Cause Failures in Safety and Reliability Studies," Pickard, Lowe and Garrick, Inc., prepared for U.S.

Nuclear Regulatory Commission and Electric Power Research Institute, NUREG/CR-4780, EPRI NP-5613, PLG-0547, Vols. 1-2, January1988.

1-12.

Deleted.

1-13.

Deleted.

BFNUnit 2 Summary Rpt (Rev 2).doc 1-1 S1059446-1426-022304

Unit 2 Summary Report 1-14.

U.S. Nuclear Regulatory Commission, 'Common-Cause Failure Parameter Estimations", NUREG/CR-5497, October, 1998, INEEL/EXT-97-01328 BFNUnit 2 Summary Rpt (Rev 2).doc 1-2 S1059446-1426-022304

.7 Unit 2 Summary Report APPENDIX A UNIT 2 TOP RANKING SEQUENCES CONTRIBUTING TO CDF BFNM Unit 2 Summary Rpt (Rev 2).doc A-1 S1059446-14264022304

t Unit 2 Summary Report Model Name:

U2EPUB Master Frequency File:

EPUALL Sequences for Group:

ALL Sorted by Frequency Rank Index Initiator Frequency Failed and Multi-State Split Fractions Bin 1

41 LOCHS 1.5761E-007

//SDRECF*OXF*/DWF*//IVOF*RVCO*FWHF*RCI1*HPI4 NLERF

  • OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF* /NOCDF*NLERFF* ELF* WWBF* WWF 2

45 LOCHS 5.8376E-008

//SDRECF*OXF*/DWF*//IVOF*RVC0*FWHF*RCI1*HPI4 NLERF

  • OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF*FC2*RBEF 3

116 TRAN 5.7617E- 008

//SDRECF*OXF*/DWF*//MCDl*RVCO*FWHF*RCIl*HPI4 NLERF

  • OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF* /NOCDF*NLERFF* ELF* WWBF*WWF 4

1 ISLOCA 4.6342E-008 LERF 5

424 LOSP 4.5649E-008

/OGSF*OG16F*UB41AF*UB41BF*UB42AF*UB42BF*SHUJT NLERF lF*SHT2F*GAl*GD2*GB4*GC4*EPR303*DGC1*AAF*RQF

  • REF*RMF*ABF*RSF*RHF*UB42CF*DKF*ACF*RRF*RFF*

ADF*RTF*RKF*RLF*RIF*RJF*RNF*DLF*DOF*/UB43AF*

UB43BF*GEF*A3EAF*RXF*ROF*DNF*GGF*A3ECF*GFF*A 3EBF*RYF*RPF*/DWF*/RCWF*EAF*EB F*ECF*EDF*RBCF*SW2AF*SWlAF*SW2BF*SWlBF*SW2CF

  • SWICF*SW2DF*PCAF*DCAF*CADF*/OEEF*IVOF*RVCO*

CDF*EPR63*RCLF*HPLF*/FWAF*HRLF*SUFWF*HSF*CDA F*CRDF*ORPF*R480F*RPAF*RPCF*UlF*RPBF*RPDF*U3 F*OSPF*LPCF*OAIF*/NCDF*RHSWF*/NOCDF 6

12 L500U2 4.3814E-008

/OG5F*/SDRECF*OXP*/DWF*//MCDF*RVCO*FWHF*RCI1 NLERF

  • HP14*OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*C DAF*/NCDF*/NOCDF*NLERFF-ELF*WWBF*WWF 7

205 TRAN 2.9570E-008

//SDRECF*OXF*/DWP*//TB1*RVCO*FWHF*RCIl*HPI4*

NLERF OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/N CDF*/NOCDF*NLERFF*ELF*WWBF*WWF 8

234 LOCHS 2.7727E-008

//SDRECF*OXF*/DWF*U3AP1*//IVOF*RVCO*FWHF*RCI NLERF 1*HP14*OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*

CDAF*/NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 9

43 LOCHS 2.4361E-008

//SDRECF*OXF*/DWF*//IVOF*RVCO*FWHF*RC11*HP14 NLERF

  • OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF*RB12 10 39 TRAN 2.4201E-008

//SDRECF*OXF*/DWF*//BVR1*RVCO*FWHF*RCI1*HPI4 NLERF

  • OBDF*ORVD2*/FWAP*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 11 442 LOSP 2.3927E-008

/OG5F*OG16F*UB41AF*UB41BF*UB42AF*UB42BF*SHUtT NLERF lF*SHT2F*GAl*GD2*GB4*GC4*EPR303*DGCl*AAF*RQF

  • REF*RMF*ABF*RSF*RHF*UB42CF*DKF*ACF*RRF*RFF*

BFNUnit 2 Summary Rpt (Rev 2).doc A-2 S1059446-1426-022304

q, i

Unit 2 Summary Report Model Name:

U2EPUB Master Frequency File:

EPUALL Sequences for Group:

ALL Sorted by Frequency Rank Index Initiator Frequency Failed and Milti-State Split Fractions Bin ADF*RTF*RKF*RLF*RIF*RJF*RNF*DLF*DOF*/UB43AF*

UB43BF*CEF*A3EAF*RXF*ROF*DNF*GGF*A3ECF*GFF*A 3EBF*RYF*RPF*GH7*A3EDF*SDRECF*

IDWF*/RCWF*EAF*EBF*ECF*EDF*RBCF*SW2AF*SW1AF*

SW2BP*SWlBF*SW2CF*SW1CF*SW2DF*SW1DF*PCAF*DCA F*CADF*/OEEF*IVOF*RVCO*CDF*EPR63*RCLF*HPLF*/

FWAF*HRLF*SUFWF*HSF*CDAF*CRDF*ORPF*R480F*RPA F*RPCF*U1F*RPBF*RPDF*U3F*OSPF*LPCF*OAIF*/NCD F*RHSWF*/NOCDF 12 115 LOSP 2.2935E-O0S

/OG5F*OG16F*UB41AF*UB41BF*UB42AF*UB42BF*SHUT NLERF lF*SHT2F*GB1*GC2*EPR303*ABF*RSF*RHF*UB42CF*D KF*ACF*RRF*RFF*/UB43AF*UB43BF*GE1*A3EAF*RXF*

ROF*DNF*GF2*A3EBF*SDRECF*/DWF*/RCWF*EAF*EBF*

ECF*RBCF*SW2BF*SW2CF*SW1CF*PCAF*DCAF*/OEEF*I VOF*RVCO*CDF*EPR63*RCLF*HPLF*/

FWAF*HRLF*SUFWF*HSF*CDAF*CRDF*ORPF*RPAF*RPCF

  • U1F*RPBF*RPDF*U3F*OSPF*LPCF*OAIF*/NCDF*RHSW F*/NOCDF 13 179 LOSP 2.2927E-008

/OG5F*OG16F*UB41AF*UB41BF*UB42AF*UB42BF*SHUT NLERF lF*SHT2F*GDl*GC2*EPR303*UB42CF*ACF*RRF*RFF*A DF*RTF*RIF*RJF*RNF*DLF*DOF*/UB43AF*UB43BF*GE 1*A3EAF*RXF*ROF*GH2*A3EDF*SDRECF*/DWF*/RCWF*

EAF*EBF*EDF*RBCF*SW2BF*SW2DF*SW1DF*PCAF*DCAF

  • /OEEF*IVOF*RVC0*CDF*EPR63*RCL F*HPLF*/FWAF*HRLF*SUFWF*HSF*CDAF*CRDF*ORPP*R PAF*RPCF*UlF*RPBF*RPDF*U3F*OSPF*LPCF*OAIF*/N CDF*RHSWF*/NOCDF 14 120 TRAN 2.1340E-008

//SDRECF*OXF*/DWF*//MCD1*RVCO*FWHF*RCI1*HP14 NLERF

  • OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF*FC2*RBEF 15 42 LOCHS 1.7513E-008

//SDRECF*OXP*/DWF*//IVOF*RVCO*FWHF*RCI1*HP14 NLERF

  • OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF*RBE4 16 16 FLTB2 1.6760E-008

//SDRECF*OXF*/DWF*//MCDF*RVCO*CDF*RCI1*HPI4*

hLERF ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*//NCDF*/

NOCDF*NLERFF*ELF*WWBF*WWF 17 16 L500U2 1.6227E-008

/OG5F*/SDRECF*OXF*/DWF*//MCDF*RVCO*FWHF*RCI1 NLERF

  • HPI4*OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*C DAF*/NCDF*/NOCDF*NLERPFF*ELF*WWBF*WWF*FC2*RBE BFNUnit 2 Summary Rpt (Rev 2).doc A-3 S1059446-1426-022304

Unit 2 Summary Report Model Name:

U2EPUB Master Frequency File:

EPUALL Sequences for Group:

ALL Sorted by Frequency Rank Index Initiator Frequency Failed and Multi-State Split Fractions Bin 18 8

LOAC 1.6038E-008

//SDRECF*OXF*/DWF*//MCDF*RVC0*CDF*RCI1*HPI4*

NLERF ORVD2*/FWAF*HRLF*HRGF*SUFWF*HSF*CDAF*/NCDF*/

NOCDF*NLERFF*ELF*WW8F*WWF 19 14 LRBCCW 1.4274E-008

//SDPECF*OXF*/DWF*/RBCP*DCAF*/IVOF*RVCO*FWHF NLERF

  • RCI1*HPI4*OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*

HSF*CDAF*/NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 20 377 LOSP 1.4118E-008

/OG5F*OG16F*UB41AF*UB41BF*UB42AF*UB42BF*SHUT NLERF lF*SHT2F*GA1*GD2*GB4*GC4*EPR303*AAF*RQF*REF*

RMF*ABF*RSF*RHF*UB42CF*DKF*ACF*RRF*RFF*ADF*R TF*RKF*RLF*RIF*RJF*RNF*DLF*DOF*/UB43AF*UB43B F*GHl*A3EDF*/DWF*/RCWF*EBF*RBCF*SW2AF*SWlAF*

SW2BF*SW2CF*SWlCF*SW2DF*SWlDF*

PCAF*DCAF*/IVOF*RVCO*CDF*EPR63*RCLF*HPLF*/FW AF*HRLF*SUFWF*HSF*CDAF*CRDF*R480F*RPAF*RPCF*

UlF*RPBF*RPDF*U3F*OSPF*LPCF*OAIF*/NCDF*RHSWF

  • /NOCDF 21 3

LOPA 1.3638E-008

//SDRECF*OXF*/DWF*/PCAF*DCAF*/IVOF*RVCO*FWHF NLERF

  • RCI1*HPI4*OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*

HSF*CDAF*LCF/D*/NCDOCDF*NLERFF*LF*WWBF*WW 22 333 TRAN 1.2162E-008

//SDRECF*OXF*/DWF*//RXSl*OSLl*/NAF*FWAF*HRLF LERF

  • HR6F*SUFWF*CDAF*/NCDF*/NOCDF*b'LERFF*CILF*IV R1O*TR6*FCF*DWIF*RBE7 23 339 TRAN 1.2162E-008

//SDRECF*OXF*/DWF*//RXSl*OSLl*/NAF*FWAF*HRLF LERF

  • HR6F*SUFWF*CDAF*/NCDF*/NOCDF*NLERFF*CILF*WW l*IVR10*TR6*FCF*DWIF*RBE8 24 7

L500PA 1.1938E-008

/OGSF*/SDRECF*OXF*/DWF*//MCDF*RVCO*FWHF*RCIl NLERF

  • HPI4*OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*C DAF*/NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 25 3

BOC 1.1808E-008

//SDRECF*OXF*/DWF*//IVOF*RVCO*FWHF*RCIF*HP14 NLERF

  • OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 26 209 TRAN 1.0952E-008

//SDRECF*OXF*/DWF*//TBl*RVCO*FWHF*RCIl*HPI4*

NLERF OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/N CDF*/NOCDF*NLERFF*ELF*WWBF*WWF*FC2*RBEF 27 30 ISCRAM 1.0355E-008

//SDRECF*OXF*/DWF*//MCD1*RVC0*FWHF*RCIl*HPI4 NLERF

  • OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERPFF*ELF*WWBF*WWF 28 238 LOCHS 1.0269E-008

//SDRECF*OXF*/DWF*U3AP1*//IVOF*RVCO*FWHF*RCI bLERF 1*HP14*OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*

BFNUnit 2 Summary Rpt (Rev 2).doc A-4 S1059446-14264022304

Unit 2 Summary Report Model Name:

U2EPUB Master Frequency File:

EPUALL Sequences for Group:

ALL Sorted by Frequency Rank lndex Initiator Frequency Failed and Multi-State Split Fractions Bin CDAF*/NCDF^/NOCDF*NLERFF*ELF*WWBF*WWF*FC2*R8 EF 29 481 TRAN 1.0136E-008

//SDRECF*OXF*/DWF*U3APl*//MCDl*RVCO*FWHF*RCI NLERF 1*HP14*OBDF*ORVD2*/FWAF*H*HRHR6F*SUFWF*HSF*

CDAF*/NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 30 32 LRCW 9.5325E-009

//SDRECF*OXF*/DWF*/RCWP*/MCDF*RVCO*CDF*RCI1*

NLERF HP14*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSP*CDAF*CR DF*/NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 31 56 LOCHS 9.5135E-009

//SDRECF*OXF*/DWF*//IVOF*RVCO*FWHF*RCI1*HP14 LERF

  • OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF*OP3*IVR1*RBE 32 1

ELOCA 9.3900E-009

/NCDF LERF 33 46 LOCHS 9.0226E-009

//SDRECF*OXF*/DWF*//IVOF*RVCO*FWHF*RCI1*HPI4 NLERF

  • OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF*FC2*R8I2*R8E 34 43 TRAN 8.9634E-009

//SDRECF*OXF*/DWF*//BVRl*RVCO*FWHF*RCI1*HPI4 NLERF

  • OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF*FC2*RBEF 35 62 LOCHS 8.9143E-009

//SDRECF*OXF*/DWF*//IVOF*RVC0*FWHF*RCI1*HPI4 NLERF

  • OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*RHSW1*/NOCDF*NLERFF*ELF*WWBF*WWF 36 118 TRAN 8.9053E-009

//SDRECF*OXF*/DWF*//MCDl*RVCO*FWHF*RCIl*HPI4 NLERF

  • OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF*RBI2 37 395 TRAN 8.8426E-009

//SDRECF*OXF*/DWF*/DCAl*/IVOF*RVCO*FWHF*RCI1 NLERF

  • HPI4*OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*C DAF*/NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 38 435 LOSP 7.9802E-009

/005F*OG16F*UB41AF*UB41BF*UB42AF*UB42BF*SHUT NLERF lF*SHT2F*GAl*GD2*GB4*GC4*EPR303*DGCl*AAF*RQF

  • REF*RMF*ABF*RSF*RHF*UB42CF*DKF*ACF*RRF*RFF*

ADF*RTF*RKF*RLF*RIF*RJP*RNF*DLF*DOF*/UB43AF*

UB43BF*GEF*A3EAF*RXF*ROF*DNF*GGF*A3ECF*GFF*A 3EBF*RYF*RPF*/DWF*U3AP1*/RCWF*

EAF*EBF*ECF*EDF*RBCF*SW2AF*SWlAF*SW2BF*SWlBF

  • SW2CF*SWlCF*PCAF*DCAF*CADF*/OEEF*IVOF*RVCO*

CDF*EPR63*RCLF*HPLF*/FWAF*HRLF*SUFWF*HSF*CDA F*CRDF*ORPF*R480F*RPAF*RPCF*UlF*RPBP*RPDF*U3 F*OSPF*LPCF*OAIF*/NCDF*RHSWF*/NOCDF 39 82 TRAN 7.8836E-009

//SDRECF*OXF*/DWF*//MCD1*RVCO*FWHF*OBCF*/FWA NLERF BFNUnit 2 Summary Rpt (Rev 2).doc A-5 S1059446-1426-022304

Unit 2 Summary Report Model Name:

U2EPUB Master Frequency File:

EPUALL Sequences for Group:

ALL Sorted by Frequency Rank Index Initiator Frequency Failed and Multi-State Split Fractions Bin F*HSF*HXA1*HXC2*U12*HXB5*HXD7*U32A*OSPF*OSDF

  • OLP2*/NCDF*/NOCDF 40 10 LOFW 7.7907E-009

//SDRECF*OXF*/DWF*//RVCO*FWHF*RCI1*HPI4*OBD1 NLERF

  • ORVD2*/FWAF*HRLF*HR6F*SUFWF*/NCDF*/NOCDF*NL ERFF*ELF*WWBF*WWF 41 87 L500U2 7.7076E-009

/OGSF*/SDRECF*OXF*/DWF*U3AP1*//MCDF*RVC0*FWH NLERF F*RCI1*HPI4*OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF

  • HSF*CDAF*/NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 42 129 LOCHS 7.3326E-009

//SDRECF*OXF*/DWF*//IVOF*RVCO*FWHF*RC11*HP14 NLERF

  • OIVF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF* C RD11*/NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 43 77 TRAN 7.1699E-009

//SDRECF*OXF*/DWF*//MCD1*RVCO*FWHF*OBCF*/FWA NLERF F*HSF*OSP1*SDC2*OLP2*/NCDF*/NOCDF 44 555 TRAN 6.9274E-009

//DJ1*SDRECF*OXF*/DWF*//TBF*RVCO*FWHF*RCIF*H NLERF P16*OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDA F*LCF*/NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF 45 7

LOSP 6.9202E-009

/OGSF*OG16F*UB41AF*UB41BF*UB42AF*UB42BF*SHUT NLERF 1F*SHT2F*UB42CF*/SDRECF*/DWF*/RCWF*/IVOF*RVC 0*CDF*RCI1*HPI4*ORVD2*/FWAF*HRLF*HR6F*SUFWF*

HSF*CDAF*CRDF*/NnCDP*/NOCDF*N LERFF*ELF*WWBF*W WF 46 14 L50OU2 6.7719E-009

/OGSF*/SDRECF*OXF*/DWF*//MCDF*RVCO*FWHF*RCIl NLERF

  • HPI4*OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*C DAF*/NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF*RBI2 47 117 TRAN 6.4019E-009

//SDRECF*OXF*/DWF*//MCD1*RVC0*FWHF*RCI1*HP14 NLERF

  • OBDF*ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/

NCDF*/NOCDF*NLERFF*ELF*WWBF*WWF*RBE4 48 20 FLTB2 6.2074E-009

//SDRECF*OXF*/DWF*//MCDF*RVC0*CDF*RCI1*HPI4*

NLERF ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/NCDF*/

NOCDF*NLERFF*ELF*WWBF*WWF*FC2*RBEF 49 12 LOAC 5.9399E-009

//SDRECF*OXF*/DWF*//MCDF*RVCO*CDF*RCI1*HPI4*

NLERF ORVD2*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/NCDF*/

NOCDF*NLERFF*ELF*WWBF*WWF*FC2*RBEF 50 15 LOCHS 5.6349E-009

//SDRECF*OXF*/DWF*//IVOF*RVCO*FWHF*OHC1*L8H1 NLERF

  • ORVD3*/FWAF*HRLF*HR6F*SUFWF*HSF*CDAF*/NCDF*

/NOCDF*NLERFF*ELF*WWBF*WWF BFNUrit 2 Summary Rpt (Rev 2).doc A-6 S1059446-1426-022304