ML041040208
| ML041040208 | |
| Person / Time | |
|---|---|
| Site: | FitzPatrick (DPR-059) |
| Issue date: | 03/31/2004 |
| From: | Carrasco J Division of Reactor Safety I |
| To: | |
| References | |
| FOIA/PA-2004-0107 | |
| Download: ML041040208 (15) | |
Text
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT Concerns Resolution/Corrective Action NRC proposed response to concerns:
1.-"Management has not pursued concerns with need to upgrade the
-The technical evaluation performed by Design The licensee initiated qualification of several vital and protected area doors, specifically the new Engineering on the safety classification issue AQCR Adverse Quality control room door.-
No. 92.360 were reviewed and determined to be Condition Report CAQCR) adequate with the exception of a failure to consider 92-0360 to address the one design issue of one cable tunnel door. New action vital and protected area items have been developed to address these issues.
door [V&PAD) issues. It appears that the licensee has completed the resolution of AQCR No.92-360 with the following exceptions: a) classifying the Electrical Bay doors and b) omission from the evaluation of one cable tunnel door. The licensee has developed new action items to address these
/c-
& s Adz 2 ~ g
~issues.
The NiRC
/t~
& ?
/e~'.concluded that the Am w
censee actions to Zig r
\\address this concern ww
)Cto know about h licensee plans to close AQCR 92-360.
QQ7 V
1
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT I
T 2.- 'Management was not responsive to concerns raised with the hot water boiler modification to that NYPA failed to qualify the existing 170,000 gallons if 2 fuel oil tank to NFPA 30 standards, but used a loophole allowing qualification to NFPA 31. This is a concern due to the proximity of the tank to the control room and its air intakes."
IA r.-
2 6
-Plant drawings were reviewed to establish the minimum separation between the control room (including Its air intakes) and the fuel oil storage tank (AQCR 92-360). These distances are fully In compliance with NFPA 31 and the fuel oil storage tank does not poses a threat to the control room or its air intakes.
The licensee reviewed and compared the applicability of NFPA 31 and NFPA 30 standards used to determine the minimum separation between the control room and the fuel storage-tank.
The licensee concluded that standard NFPA 31 is the correct standard for this application. Further, the licensee found no safety concerns In the regarding the uses of standard NFPA 31 to qualify the existing 170,000 gallon capacity tank. The distances between the control room and the fuel oil storage tank are above the minimum separation distances prescribed In NFPA 31 Standard. The licensee's actIon to address this concern was adequate. Therefore, no NRC follow-up Is needed.
2
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT f
3.-"ACTS item 8977 (involving a DER written in 1993-1994) regarding a building/structures configuration has not been approved. There is a letter of commitment to the NRC in this matter (i.e., GL 83-28 response).
-There was no design or licensing basis for the evaluation of a System 52' component since system 52 was not included in the MCM-6A (System Safety Function Sheet). -System 52 was added to MCM-6A and components presently existing in system 52 were reviewed for appropriate designation.
-.-.- A review of the system 52 Work Requests in a maintenance database did not find safety significant concerns.
The licensee self-assessed their response to the NRC Generic Letter 83-28. This self-assessment showed that they made no commitments to the NRC.
However, the licensee noted that there was no design or licensing basis to evaluate System 52 and Its associated components. They attributed this omission to the fact that they did not include System 52 in the MCM-6A (System Safety Function Sheet).
Subsequently, the licensee reviewed the components presently existing within the scope of System 52 to ensure their appropriate safety designation. In addition, a review of System 52 Maintenance Work Requests IMWRs) did not find safety significant concerns. The licensee's actions to address these concerns were adequate.
Therefore, no NRC follow-up Is needed.
I I
3
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT 6-1Wle
/2 Concerns Resolution/ Corrective Action NRC proposed response to concerns:
4.- 'The corrective actions to DERs94-111
- 97-045 & 95-997 have not yet
-DER 94-111: The FA and FB, standard Although the licensee started some been completed."
stick drawings do not show the present corrective actions prescribed in DERs plant configuration.-licensee's94-111, 97-045, and 95-997, we assessment Is unclear on the status of may review the licensee actions listed DER 94-111.
in DERs94-111, 97-045 and 95-997 v
X DER 97-045:Type A drawings have not to ensure the proper and timely been updated. -
2 out of 3 corrective closing of these DERs. The licensee's actions of DER 97-045 are closed, but the actions to address these concerns 3th remain open.
were adequate. Therefore, no NRC
-DER 95-0997: The single boiler may not follow-up Is needed.
f meet the single failure criteria of FSAR 1section 8.7.2.3. -
Corrective action for
,(t 1 the DER proposed installation of a redundant boiler was completed.
(a s7wll/0 4
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT 5.- 'The response to DERs and/or corrective actions is given back to the concernee (and others) to handle in addition to regular duties."
-Frequently DERs written within engineering disciplines will be returned to the writer for evaluation since this Individual is the most knowledgeable person available to perform this task.
Regarding concerns about DERs that were given back to the originator, the NRC assessed the licensee distribution of DERs for disposition, and it appears that frequently the licensee supervisors return DERs that are written within engineering disciplines to the DER originator for evaluation.
This Is done because the DER originator Is the most knowledgeable person available to disposition DERs; this approach appears logical to the NRC. The NRC concluded that the distribution Is an internal responsibility of the licensee, and unless safety Is compromised by starting a poor work distribution, then the NRC may Intervene to ensure that the Ncensee work distribution does not create a negative Impact on the overafl safety of the plant. Therefore, this concern Is closed.
5
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT r
6.-'Concernee's supervisors discouraged the writing of DERs.
-Engineering supervisors, and managers have been instructed to not discourage the use of DERs to report problems.
Overall in this concern, it appears that the licensee has instructed engineering supervisor, and managers not to discourage the use of DERs to report problems. Therefore, the alleger's concern is not substantiated because there is no specific indication that employees, including the alleger, are systematically discouraged from using the DER process.Therefore, the alleger's concern Is not substantiated because there Is no specific evidence that employees, Including the alleger, are systematically discouraged from using the DER process. Here, no NRC follow-up Is required.
I ________________________
I. ______________________
Concerns Resolution/ Corrective Action NRC proposed response to concerns:
7.- Concerns expressed regarding NYPA's follow-on actions committed to
- Through interviews with personnel Through licensee's interviews with their 10CFR 50.54(f) reply.'
assigned to the preparation of the personnel assigned to the preparation 10CFR50.54(f) response. No adverse of the 10CFR50.54(f) response, it data of safety related the noncompliance appears that no adverse data of safety was found.
related nature was found. In conclusion, In routine Inspections at FitzPatrick the NRC will further assess the licensee ability to maintain the configuration of the plant current.
6
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT T
r 8.- "Concerns expressed with an instrument air system moisture sensor and NYPA's response to GL 88-14 involving instrument air systems."
AN S-9
- The plant Instrument Air System meets design requirements for moisture, Instrurment air dewpoint is measured on a quarterly basis per procedure No. RT-01.01. -This meets the plant's commitment relative to NRC GL 88-14 for moisture in the Instrument Air System.
as Itoo cc-Ce The alleger's concern expressed with regard to instrument air system moisture sensors is not substantiated.
Since at FitzPatrick, the plant Instrument Air System meets design requirements for moisture, the licensee measures instrument air dewpoint quarterly per procedure No.
RT-01.01. These licensee actions meet the plant's commitment about NRC GL 88-14 for moisture in the Instrument Air System. These licensee actions meet the plant's commitment about NRC GL 88-14 for moisture In the Instrument Air System.
Therefore, this concern Is closed, and no NRC follow-up Is required.
9.-"NYPA purportedly knew in the 1989 time frame that snubbers were past theirs rebuild date and took no immediate action."
,§g 7_-
fefsv te e
- An evaluation of snubber elastomeric seals service life was performed. This evaluation determined longer life span of the snubbers.
'1 On November of 1989, the licensee performed an evaluation of snubber elastomeric seals. This evaluation determined a longer life span of the snubbers. Recently, the licensee Quality Assurance (OA) reviewed the snubber program as presently carried out and concluded that the snubber technical documentation was accurate. The licensee's actions to address these concerns were adequate. No NRC follow-up Is needed.
I ____________________
I ___________________
7
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT Concerns Resolutionl Corrective Action NRC proposed response to concerns:
10.- Concerns were expressed with the Speakout Program, specifically: 1)
- During the 1993-1994 period there The Speakout program Is Independent no action was taken with a list of concerns brought to speakout in a 1993-were a Senior Speakout investigator and of the site or Nuclear Generation 1994 time frame by OA inspector, and 2) since the speakout representative two contractor Investigators. According management. The purpose of the communicates directly with senior management, employees are discouraged to information available in Speakout files, program is to provide an outlet for from raising issues."
the concernee did not clearly annunciate employees and contractors to express his intentions at the time he came to nuclear safety concerns. An Speakout.
evaluation of concern No. 10 showed that during the 1993-1994 period
-The Speakout program Is independent there was a Senior Speakout of the site or Nuclear Generation Investigator and two contractor management. The purpose of the program investigators. According to is to provide an outlet for employees and information available in Speakout files, contractors to express nuclear safety the alleger did not clearly annunciate concerns.
his intentions at the time the alleger came to Speakout. The NRC closed this concern due to a lack of specifics.
Therefore, no NRC follow-up Is needed.
8
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT t
7 11.- "(Related to Concern # 6) Examples provided were DERs were turned back to the writer, purportedly as 'punishment': ACTs 25549, ACTS 22356. ACTS 8997. DER 95-0997 and an issue with the auxiliary boiler room oil water separator being radiologically contaminated."
(Note: There is no text in this cell)
To decide if the alleger was singled out for 'punishment' by having DER responses assigned to him (the alleger) by his supervisor, the licensee started an Investigation that shows that plant supervision did not treat him unfairly with respect to the assignment of DERs. About the issue of contamination of the boiler rooms oil water separator, the licensee is aware that these rooms and the components inside the rooms have the potential to be radiologically contaminated. Therefore, the licensee has radiation contamination controls for these rooms and the components in these rooms through the use of procedure SP-01.1 1, 'Unmonitored Paths Sampling and Analysis." The NRC concluded that the alleger was not singled out by his supervisor. The NRC found the licensee actions to control radiation contamination controls for these rooms and the components In these rooms adequate.
No NRC follow-up Is required.
L
_ I 9
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT 12.- '(Related to Concern #4) System 52 buildings not on SSC List; no list The Issue of designation of System The alleger's concern involving the of components on PEDB for 'structures,' e.g. doors. (References made to 052 for buildings, and addition of issue of designation of System 52 for GL 83-28 response and DER 93-061 1).
components assigned to the system to buildings and associated components the PEDB is discussed in response to was extensively discussed in concern 3 (therefore, Response 3 responses to concern No.3. This provides the response for concern 12, as concern Is closed. No NRC follow-up well).
Is needed.
13.- 'The reactor Building roof started leaking in 1995 and is near of its
-Currently, as leaks are Identified, Regarding the condition of the Reactor useful life. As a result, the steel roof decking may be rusting, potentially corrective action is planned, The reactor Building Roof, it appears that the impacting on the future operation of the Standby Gas Treatment System."
building roof has sustained only minor licensee has successfully performed leaks, which have been successfully repairs to this roof in the past. The repaired.
current condition of this roof and the existence of minor leaks do not Design Basis for the Secondary Containment '
-The current condition of the Reactor adversely affect the functional and
_ The Reactor Building (RB) is designed to be sufficiently leak tightto allow Building roof and the existence of roofing structural integrity of the secondary the Standby Gas Treatment System ISGTS) to reduce the reactor building Yaks do not adversely affect secondary containment. Therefore, the licensee pressure to a minimum subatmospheric pressure of 0.25 in. of water (under cotA inment integrity. Because of the maintains the secondary containment neutral wing conditions) when the SGTS fans are exhausting RS atmosphere followinlo.
design basis by using Technical.
at a rate of 200% (6,000 cfm) per day of RB free volume. -
This safety
/
Specifications surveillance and basis takes into account expected leakage into a structure of the size of the JAF Technical Sp cifications contain maintenance rule walkdowns. The RB.
surveillance requirements to ensure this NRC considers these actions safety design basis (0) is met (last test acceptable and no follow-up Is was performed on Octoberl 6, 1996.).
required.
-To support 10CFR 50.56 (Maintenance Rule) performance monitoring, a baseline walkdown of the RB roof was performed in 1996. Further inspection is required once every two l___
years.
10
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT 7
1 14.- '(Related to Concern i 1i A question regarding the adequacy of tornado missile protection for the new control roorii door to the administration building."
-A new Control Room door was installed in accordance with plant modification F1-90-013. This mod. installed a new OA Cat. I door designed for tornado pressure loading along with other design attributes.
The licensee has installed a new Control Room (CR3 door following plant modification No. F1-90-013.
This modification Installed a new GA Category "I" door designed for tornado pressure loading along with other design attributes. However, regarding the adequacy of tornado missile protection of the new control room door, the licensee upgraded the access bridge installed between the new support and administration building and the control room. The new access bridge was Installed to provide missile protection to the new CR door. The licensee has Initiated a DER to further assess the adequacy of the missile protection for the CR door.
The NRC needs additional Information on the general layout of the missile protection for the CR door.
4 i.
- 15. 'Concern expressed with ESW pump room ventilation isolation due to a possible fire damper isolation.'
-This problem was previously described to the NRC in LER 91-021-00. -.
Inadequate ventillation following fire damper closure resulted from Inadequate analysis of the effects of the closure of dampers installed to meet NRC requirements in 1980.-m-* Corrective actions described in LER 91-021-00 have all been completed.
Regarding the alleger's concern expressed with the emergency service water (ESWM pump room ventilation as is described in License Event Report (LER) 91-021-00. It appears that the licensee has completed the corrective actions described In LER 91-021-00.'t Therefore, the NRC considers this concern closed with no further follow-up.
g
.'d I g
OX 41 11
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT Concerns Resolution/ Corrective Action NRC proposed response to concerns:
16.- 'Concern expressed with the design of a contaminated drain line from
- Resulting from a review of modification The licensee evaluated piping the administration building RCA since it is a standard line buried In gravel F1-90-013, the Radiological and configuration of drains for the without a guard pipe."
Environmental Services (RES) department personnel and equipment evaluated this configuration against the decontamination located under and Question for the licensee:
guidance of Regulatory Guide 1.143.
between the administration building
'There was no documentation of the basis for choices made by the design RES determined the design was and the power block. This evaluation engineering organization with respect to the modified piping configuration acceptable since the regulatory guide was perfomed following the guidance Included with ECN-024." We need more Information on this Issue.
exempts drain lines from requiring welded of NRC Regulatory Guide 1.143. As a connections, result of this evaluation, the licensee How many branches of this piping was hydro tested?
- ECN 024 was issued against Issued ECN 024 to install welded modification Fl 90-013 to Install welded piping in place of bell and spigot piping In place of bell and spigot connections. Further, the licensee connections. -
ECN A hydrostatic test performed a hydrostatic test of-the of the drain line (prior to construction drain line (before the construction outlined on ECN-024) demonstrated outlined on ECN-024) that showed satisfactory leak tightness.
satisfactory leak tightness, It appears that the licensee has taken the proper steps to address this concem.
However, the NRC has requested additional Information on this Issue.
12
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT 17.- Concern expressed with the resolution of DER 97-45. Mod F1-92-145 involving seismic 11 over I piping.
- Three corrective actions were specified in response to DER 97-045: 1)
Engineering Change Notice (ECN) was written against mod. F1-92-145 documenting the current as-left configuration of the nitrogen purge vaporizer stem and condensate piping and to updateapplicable type 'A' drawings.
This corrective action is completed 2) complete a calculation justifying the acceptability of abandoning portions of the nitrogen purge vaporizer steam and condensate piping in place. The results of the calculation concluded that this piping will not have impact on the safe shutdown of the plant during a seismic event. 3) The 3th corrective action was to address the issue of a partially installed mod. by revising the mod. to delete the remaining and then closing the mod. The action will be completed October 22.
1997.
About the concern expressed with the resolution of DER 97-45. the licensee addressed Modification No. FI 145 involving seismic II over I piping in corrective action No. 2 of DER 97-045. Specifically, the licensee completed a calculation Justifying the acceptability of abandoning portions of the nitrogen purge vaporizer steam and condensate piping in place. The results of the calculation concluded that this piping will not have an adverse impact on the safe shutdown of the plant nor will create seismic 11 over I situation during a seismic event.
The licensee's analysis to address this concern was adequate. No NRC follow-up Is needed.
.4
-1 13
JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT 18.- AQCns92-289, 92-290 and 92-291 were never entered into the corrective action system and resolved."
AOCR 92-289 was initiated on 8/28192 and closed on 01/15/93.
AOCR 92-290 was initiated on 10/2/92 and was closed 1/12/93.
ACOR 92-291 was not issued.
The licensee's document control record showed the following:
AQCR 92-289 was initiated on August 28. 1992 with concurrence from GA management. OA management accepted response to AQCR 92-289 (following independent verification of corrective action) and closed the document on January 15, 1993.
AOCR 92-290 was initiated on October 2, 1992 with concurrence from QA management. QA management accepted response to AQCR 92-290 (following independent verification of corrective action) and closed the document on January 12, 1993.
The licensee did not issue AOCR 92-291. The same Individuals who were Involved with preparation of AQCRs92-289 and 92-290 had also originally
.reserved' AQCR 92-291. There Is no indication that they did not allow items into the system. Rather, It appears that after initiating the first two AOCRs, the individuals found that they did not need to use the third reserved number. Therefore, the alleger has no substantiation for his concerns regarding AQCR 92-291.
Therefore, the alleger has no substantiation for his concerns
_I 14
f JOSEPH E. CARRASCO, ENGINEERING INSPECTOR ASSESSMENT OF THE LICENSEE RESPONSE TO CONCERNS RAISED TO THE NRC REGARDING ACTIVITIES AT FITZPATRICK NUCLEAR POWER PLANT 19.- 'The resolution of DERs related to the CAD steam line modification/condensate thermosiphon heat exchanger mod provided an example of the overall safety culture at FitzPatrick."
The issue regarding the condensate thermosiphon heat exchanger modification is as follows:
(1)
PID 55112, written December 21, 1993 and subsequently converted Into WR 93-04347-00 documented the following: 'CST tank temperature Is not maintained by the reboiler or the auxiliary boiler system (the steam supply to the thermosiphon heat exchangers was Isolated in the late 1970's) as described In the FSAR Section 10.9.3. Instead, the licensee use condensate transfer pump minimum flow to maintain CST teperature above the FSAR prescribed 400 F required by the FSAR. In 1991, the licensee prepared Safety Evaluation No. JAF-SE-91-095 to address the substitution of Auxiliary Boiler Steam Supply.
In 1994, the licensee prepared DER 94-0471 to revise SE No. [[::JAF-SE91-095|JAF-SE91-095]], or to prepare a new SE. The contents of DER 94-0471 is described as follows:
(2)
The thermosiphon heat exchangers, 33E-24A/B, are steam supplied heat exchangers that were designed to maintain the water in condensate storage tank [CST) above 40° F. 40° Fis mentioned in the FSAR Section 4.2 as being nil-ductility transition temperature (NDTT for carbon steel. The NDTT is the temperature below which ferritic steel breakage is brittle rather than ductile.
The CAD steam line DER (97-0045) was discussed in the response to concern 4 and 17.
Regarding the issue of the condensate thermosiphon heat exchanger modification as is described in (1) and (2).
Corrective actions for DER 94-0471 included evaluating whether it was possibly for CST temperature to lower to 40° F. revising FAF-SE-91-095 is incomplete.
Issues concerning the Containment Air Dilution (CAD) steam line DER (97-0045) were discussed in the response to the alleger's concerns No.4 and No.17. Regarding the condensate thermosiphon heat exchanger modification, the licensee Is in the process of carrying out the corrective actions prescribed in DER 94-0471 that include an evaluation to decide if the present configuration can maintain the CST temperature to above 40° F.
The corrective actions of DER 97-0471 are Incomplete. About the Issue of nuclear safety culture, an independent study conducted late in 1996 concluded that the licensee made significant progress at FtzPatrick In establishing a strong nuclear safety culture. The NRC will need additional Information to ensure that the corrective actions prescribed by DER 97-0471 are addressed In reasonable time.
I _____________________
15