-ERRATA-
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555-0001
August 8, 2001
NRC INFORMATION NOTICE 2001-12 (ERRATA):
HYDROGEN FIRE AT NUCLEAR
POWER STATION
Addressees
All holders of operating licenses or construction permits for nuclear power reactors except those
who have ceased operations and have certified that fuel has been permanently removed from
the reactor vessel.
Discussion
Two editorial errors have been identified in NRC Information Notice 2001-12, Hydrogen Fire at
Nuclear Power Station (ADAMS Accession No. ML010310258), issued on July 13, 2001. The
errors occurred in the Related Generic Communications section on Page 2. The number for
the information notice titled Hydrogen Storage on the Roof of the Control Room should read
IN 89-44, not IN 88-44. The number for the information notice titled Compressed Gas
Cylinder Missile Hazard should read IN 91-37, not IN 91-27.
If there are any questions about this matter, please contact the staff members listed below or
the appropriate Office of Nuclear Reactor Regulation (NRR) project manager.
/RA John R. Tappert Acting for/
Ledyard B. Marsh, Chief
Operational Experience and
Non-Power Reactors Branch
Division of Regulatory Improvement Programs
Technical contacts:
D. M. Frumkin, NRR
M. H. Salley, NRR
301-415-2280
301-415-2840
E-mail: dmf@nrc.gov
E-mail: mhs@nrc.gov
Attachment: List of Recently Issued NRC Information Notices
ML010310258), issued on July 13, 2001. The
errors occurred in the Related Generic Communications section on Page 2. The number for
the information notice titled Hydrogen Storage on the Roof of the Control Room should read
IN 89-44, not IN 88-44. The number for the information notice titled Compressed Gas
Cylinder Missile Hazard should read IN 91-37, not IN 91-27.
If there are any questions about this matter please contact the staff members listed below or
the appropriate office of Nuclear Reactor Regulation (NRR) project manager.
/RA John R. Tappert Acting for/
Ledyard B. Marsh, Chief
Operational Experience and
Non-Power Reactors Branch
Division of Regulatory Improvement Programs
Technical contacts:
D. M. Frumkin, NRR
M. H. Salley, NRR
301-415-2280
301-415-2840
E-mail: dmf@nrc.gov
E-mail: mhs@nrc.gov
Attachment: List of Recently Issued NRC Information Notices
DISTRIBUTION
PUBLIC
______________________________________________________________________________________
OL = Operating License
CP = Construction Permit
Attachment
IN 2001-12 (Errata) LIST OF RECENTLY ISSUED
NRC INFORMATION NOTICES
_____________________________________________________________________________________
Information
Date of
Notice No.
Subject
Issuance
Issued to
______________________________________________________________________________________
2001-12
Hydrogen Fire at Nuclear
Power Stations
7/13/01
All holders of operating licenses
or construction permits for
nuclear power reactors except
those who have ceased
operations and have certified that
fuel has been permanently
removed from the reactor vessel
2001-11
Thefts of Portable Gauges
07/13/01
All portable gauge licensees
2001-10
Failure of Central Sprinkler
Company Model GB Series
Fire Sprinkler Heads
06/28/01
All holders of licenses for nuclear
power, research, and test
reactors and fuel cycle facilities
2001-09
Main Feedwater System
Degradation in Safety-Related
ASME Code Class 2 Piping
Inside the Containment of a
Pressurized Water Reactor
06/12/01
All holders of operating licenses
for pressurized water nuclear
power reactors, except those who
have permanently ceased
operations and have certified that
fuel has been permanently
removed from the reactor vessel
2001-08
Supplement 1
Update on the Investigation of
Patient Deaths in Panama,
Following Radiation Therapy
06/06/01
All Medical Licensees
2001-08
Treatment Planning System
Errors Result in Deaths of
Overseas Radiation Therapy
Patients
06/01/01
All medical licensees
2001-07
Unescorted Access Granted
Based on Incomplete and/or
Inaccurate Information
05/11/01
All holders of nuclear reactor
operating licenses who are
subject to Section 73.56 of Title
10, of the Code of Federal
Regulations (10 CFR 73.56),
Personnel Access Authorization
Requirements of Nuclear Power
Plants.