L-77-367, Forwards Florida Power & Light Co.'S Response to IE Bulletins 77-05 and 77-05A

From kanterella
Jump to navigation Jump to search
Forwards Florida Power & Light Co.'S Response to IE Bulletins 77-05 and 77-05A
ML18127A613
Person / Time
Site: Saint Lucie, Turkey Point  NextEra Energy icon.png
Issue date: 12/08/1977
From: Robert E. Uhrig
Florida Power & Light Co
To: O'Reilly J
NRC/IE, NRC/RGN-II
References
IEB-77-005, L-77-367
Download: ML18127A613 (3)


Text

))

gjy )

FLORIOA POWER & LIGHT COMPANY December 8, 1977 L-77-367 Mr. James P. O'Reilly, Director, Region Office of Inspection and Enforcement II U. S. Nuclear Regulatory Commission 230 Peachtree Street, N. W., Suite 1217 Atlanta, GA 30303

Dear Mr. O'Reilly:

Re: RII:JPO 50-335 50-250, 50-251 Florida Power & Light Company has reviewed IE Bulletins 77-05 and 77-05A and a response is attached.

Very truly yours, cAp Robert E. Uhrig Vice President REU/MAS/lah Attachment cc: Robert Lowenstein, Esquire Office of Inspection and Enforcement

ATTACHMENT Re: RII:JPO 50-335 50-250, 50-251 Item 1 Determine whether your facility utilizes or plans to utilize electrical connector assemblies of the type tested by Sandia Laboratories, or any other similar type, in systems that are lo-cated inside containment, are subject to a LOCA environment and are required to be operable during a LOCA. (Bulletin 77-05)

Actions requested by Bulletin 77-05 should be expanded to include all connectors in safety systems which ar'e required to function to mitigate an accident where the accident itself could adversely affect the ability of the system to perform its safety function.

The examination is not to be limited to only LOCA's nor to areas only within containment. (Bulletin 77-05A)

Res onse 1 The Turkey Point facility does not use or plan to use electrical connector assemblies in safety related systems.

Based on a review of detail plans of instrument installations in-side containment and a visual inspection of areas outside contain-ment, we have determined that St. Lucie Unit 1 uses four (4) elec-trical connector assemblies in safety related systems. The connec-tors are installed on four radiation detectors inside containment.

The detectors provide signals which are used to initiate contain-ment isolation.

Item 2 If any such applications are identified, review the adequacy of qualification testing for the assemblies and submit the documenta-tion for NRC review.

Res onse 2 We are in the process of acquiring documentation to support the adequacy of the radiation monitor system connectors. Following our review, we will issue a supplemental response to IE Bulletins 77-05 and 77-05A.

Item 3 If evidence is not available to support a conclusion of adequacy, submit your plans and programs toward qualifying existing equipment or your plans for replacing unqualified assemblies with qualified equipment.

~ ~.

I Res onse 3 PSAR Section 3.ll specifies the environmental design categories for the containment radiation monitors. The service condition is the short term containment environment, between the occurrence of a LOCA or a steamline break and initiation of containment isolation.

Once containment isolation has been initiated, the mitigating func, tion of the radiation monitors has been accomplished. During events which could produce an environment adverse to the radiation detec-tor connectors, the radiation monitor . ignal leading to containment isolation is supplemented by redundant containment pressure instru-mentation. Thus, the four connectors under consideration are not.

required to withstand an adverse containment. environment for longer than a few minutes, and are supplemented by a diverse system.

Based on the above evaluation, the subject Bulletins may not be directly applicable to the radiation monitor connectors. However, if any followup action is identified pursuant to our document review, we will submit it with the supplemental response to XE Bulletins 77-05 and 77-05A.