IR 05000456/1981002

From kanterella
Jump to navigation Jump to search
IE Insp Repts 50-456/81-02 & 50-457/81-02 on 810127-28.No Noncompliance Noted.Major Areas Inspected:Diesel Generator Installation & Records,Raceway Support Welding & Records & 5 Kv Switchgear Installation & Records
ML19350B633
Person / Time
Site: Braidwood  
Issue date: 02/09/1981
From: Richard Lee, Niesler J, Williams C
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML19350B627 List:
References
50-456-81-02, 50-456-81-2, 50-457-81-02, 50-457-81-2, NUDOCS 8103230162
Download: ML19350B633 (4)


Text

. _ _ _ _ _ _

.

..

,

.

mb t

U.S. NUCLEAR REGULATORY COMMISSION l

OFFICE OF INSPECTION AND ENFORCEMENT l

REGION III

Reports No. 50-456/81-02; 50-457/81-02 Docket Nos. 50-456; 50-457 Licenses No. CPPR-132; CPPR-133 Licensee: Commonwealth Edison Company P. O. Box 767 Chicago, IL 60690 Facility Name:

Braidwood Nuclear Power Station, Units 1 and 2 Inspection At:

Braidwood Site, Braidwood, IL Inspection Conducted: January 27-28, 1981 S!/

/

Inspectors:

J. H. Neisler fe

fi f'

f./9/B)

R. L. Lee-L24AA~

'

Approved By:

C. C. Willia Chief M J/9/[f.

,

Projects Section

/

.

Inspection Summary Inspection on January 27-28, 1981 (Report No. 50-456/81-02; 50-457/81-02)

Areas Inspected: Diesel generator installation and records. DC system installation and records. Raceway support welding and records. SKV switchgear installation and records. This inspection involved a total of 20 inspector-hours by two NRC inspectors.

Results: No items of noncompliance or deviations were identified during this inspection.

l-

,

II 0323 0IGO-

-m_

_. _ _. - - - - - - _ _ _ _ -. - - - _ _ _. - - _ - -

l

'

.

'

DETAILS Persons Contacted Principal Licensee Employees

  • R. Cosaro, Site Construction Superintendent
  • T. R. Sommerfield, Quality Assurance Superintendent
  • C Hennecke, Lead Electrical Engineer
  • R.

C. Schluter, Project Construction

  • D. A. Brown, Quality Assurance Supervisor, Electrical L. J. Tapella, Quality Assurance Engineer Contractor and Other Personnel R. A. Brown, Quality Control Manager, L. K. Comstock Company
  • Denotes those persons attending exit interview.

Program or Functional Areas Inspected 1.

Emergency Diesel Generator The inspectors observed partially completed installation of the emergency diesel generator units. All four of the units have been placed in their respective locations. Two of the units have been bolted to their foundations and bed plates grouted. Material used for grout is an epoxy based grout recommended by the diesel manu-facturer. The grout used is Sika Chemical Corporation's "Sikadur."

Examination of records of grout compressive strength tests indicates that the compressive strength of the grout cubes exceeded the strength requirements for 7, 14, and 28 day tests. The inspectors examined documentation relative to receipt inspections and procurement.

No items of noncompliance or deviations were identified in this crea.

2.

Electrical Switchgear The inspectors observed partially completed installation of Class 1E electrical switchgear including 4160 volt and 480 volt distribution center. The switchgear cabinets have been set in place, welded to steel embed base plates, and grouted. Licensee is awaiting arrival of an alignment template from the manufacturer to complete circuit breaker alignment within the switchgear cubicles. The'switchgear room was heated and lockable, and is kept locked when work is not being performed in the room to prevent inadvertent construction damage to the switchgear.

No items of noncompliance or deviations were identified in this area.

-2-

--

.

.

'

3.

Audits and Surveillances The inspect af v reviewed four reports of audits conduc+cd by licensee's Quality Assarsace department of electrical activities performed since the restart of construction at Braidwood. The audit scopes included corporate QA, contractor organization, welding material control, welder qualification, QC inspector qualification, QC inspections, nonconfor-mance report and hold tags, control of test and measuring equipment, and receiving inspections.

The inspectors examined twenty-five surveillance reports of surveil-lances performed by licensee's site Quality Assurance personnel of site electrical construction activities.

No items of noncompliance or deviations were identified in this area.

4.

Cable Tray Installation The inspectors observed cable tray installation activities in the lower cable spreading room. Welding of cable tray hangers was being performed by a qualified welder using qualified procedures. The inspectors examined qualification records of three 'selders and two inspectors. Qualified weld procedures (WPS), for use when welding both carbon and stainless steel and carbon steel to stainless steel, were reviewed by the inspectors. Weld material control procedures provided storage, issue and use requirements for low hydrogen and stainless steel welding electrodes.

5.

DC System

.

The inspectors observed two 125 volt batteries installed in Unit 1.

The batteries are connected to temporary power supplies to maintain charged conditions. The battery enclosures are complete on three walls.

,

The fourth wall is temporarily installed as wire mesh. Discussion with

!

licensee representatives indicate that the fourth battery enclosed wall

.

will be constructed of wire mesh screening.

In the room with the bat'ery enclosure are inverters, battery chargers, and DC Control, and distribution panels. The inspectors questioned whether battery room design would afford adequate protection from hydrogen gas accumulation and possible explosion resulting from operation of the equipment in the battery rooms. This matter is unresolved

'.56-4_,. 31-02-01; 50-457/81-02-01)

Unresolved Items Unresolved items are matters about which more information is required in.

order to ascertain whether they are acceptable items, items of noncompli-ance, or deviations. An unresolved item disclosed during this inspection is discussed in paragraph 5 of this report.

,

-3-

.

.

.

Exit Interview

.

The inspectors met with licensee representatives at the conclusion of the inspection. The inspectors summarized the scope and findings of the inspection. The licensee acknowledged the findings as reported.

,