IR 05000454/2019011

From kanterella
(Redirected from IR 05000455/2019011)
Jump to navigation Jump to search
Fire Protection Inspection; Inspection Report 05000454/2019011 and 05000455/2019011 (DRS-A.Shaikh)
ML19108A225
Person / Time
Site: Byron  
(NPF-037, NPF-066)
Issue date: 04/18/2019
From: Robert Daley
NRC/RGN-III
To: Bryan Hanson
Exelon Generation Co, Exelon Nuclear
References
IR 2019011
Download: ML19108A225 (9)


Text

April 18, 2019

SUBJECT:

BYRON STATION, UNITS 1 AND 2FIRE PROTECTION INSPECTION; INSPECTION REPORT 05000454/2019011 AND 05000455/2019011

Dear Mr. Hanson:

On March 8, 2019, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at your Byron Station, Units 1 and 2 and discussed the results of this inspection with Mr. Mark Kanavos and other members of your staff. The results of this inspection are documented in the enclosed report.

The NRC inspectors did not identify any finding or violation of more-than-minor significance.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations, Part2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely,

/RA/

Robert C. Daley, Chief Engineering Branch 3

Docket Nos. 50-454; 50-455 License Nos. NPF-37; NPF-66

Enclosure:

IR 05000454/2019011; 05000455/2019011

Inspection Report

Docket Numbers:

05000454 and 05000455

License Numbers:

NPF-37 and NPF-66

Report Numbers:

05000454/2019011 and 05000455/2019011

Enterprise Identifier: I-2019-011-0025

Licensee:

Exelon Generation Co., LLC

Facility:

Byron Station, Units 1 and 2

Location:

Byron, IL

Inspection Dates:

February 04, 2019, to March 08, 2019

Inspectors:

I. Hafeez, Reactor Inspector

G. Hausman, Senior Reactor Inspector

A. Shaikh, Senior Reactor Inspector

Approved By:

Robert C. Daley, Chief

Engineering Branch 3

Division of Reactor Safety

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a Fire Protection Inspection at Byron Station, Units 1 and 2, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information. Findings and violations being considered in the NRCs assessment are summarized in the table below.

List of Findings and Violations

No findings were identified.

Additional Tracking Items

None.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs)in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html.

Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

71111.05T - Fire Protection B.5.b Inspection Activities (IP Section 02.03)

The inspectors evaluated the following B.5.b Mitigating Strategies:

(1) Makeup to Refueling Water Storage Tank
(2) Manual Operation of Auxiliary Feedwater Pump

Fire Protection Inspection Requirements (IP Section 02.02) (4 Samples)

The inspectors evaluated Fire Protection Program implementation in the following selected areas and/or fire zones, including analyzed electrical circuits:

(1)11.4C-0; Radwaste and Remote Shutdown Panel Control Room

Analyzed Circuits:

(2)5.5-2; Unit 2 Auxiliary Electric Equipment Room

Analyzed Circuits:

  • Valve Control Tank Outlet Isolation Valves 2CV112B & 2CV112C

(3)5.2-2; Division 21 Engineered Safety Feature Switchgear Room

Analyzed Circuits:

Analyzed Circuits:

  • Valve Control Tank Outlet Isolation Valves 2CV112B & 2CV112C

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors confirmed that proprietary information was controlled to protect from public disclosure.

  • On March 8, 2019, the inspector presented the Fire Protection Inspection results to Mr. Mark Kanavos and other members of the licensee staff.

DOCUMENTS REVIEWED

AR 00256389; PZR WR Level Indicator at RSD Panel Needs Repair; 09/23/2004

AR 00294699; Instrument Out of Tolerance (Indicator); 01/27/2005

AR 00481555; Heat Related Damage Noted on 2FW-0534 NSC Card; 04/21/2006

AR 00524664; Testing of Remote Shutdown Panel Switches; 08/28/2006

AR 00599367; SXCT Operability Concerns Require PED and RA Assistance; 03/05/2007

AR 00762615; B1R15 New Procedure Enhancement; 04/12/2008

AR 00763056; Tech Spec Indicator Failure, Unplanned LCOAR Entry; 04/14/2008

AR 00765886; 1FI-AF013A Failed Low; 04/21/2008

AR 00781340; 2MS018B M/A Station Did Not Transfer to RSP as Expected; 05/30/2008

AR 00809625; Damper 0VC20Y Did Not Fully Open in Purge Mode; 08/21/2008

AR 00856580; Unit Two Intermediate Range Channel Indications; 12/15/2008

AR 00862477; Unit 1 RSDP PPC Access Terminal Not Functioning; 01/04/2009

AR 01023545; RSDP AF Flow Indication Appears Failed Low; 01/30/2010

AR 02609407; Install Temperature Gauges in RSDP Rooms; 01/07/2016

AR 02692394; Station Page Console Does Not Work at U2 RSP; 07/13/2016

AR 02692395; U2 RSP Sound Power Page System Boosters; 07/13/2016

AR 02732846; 1AF005F RSP Controller Porting Air; 10/26/2016

AR 03986790; 1AF005F RSP Controller Porting Air; 03/19/2017

AR 03962506; U1 RSP Overhead Lighting Needs Relamping; 01/12/2017

AR 03976794; U1 RSP Sound Powered Phone Boosters Are Not Working; 02/21/2017

AR 04057804; B2R20 M2 U2 RSP Clock Not Operating; 10/01/2017

AR 04082497; Radwaste and RSP HVAC Supply, 0VI01C, Keeps Tripping; 12/09/2017

AR 04082875; 1PL04J RSP Light Socket; 12/11/2017

AR 04140171; 1D-13 RSP FD Zone Fire Alarm Toggling Randomly; 05/22/2018

AR 04207577; PMS for Switch Checks at RSPs Coming Due; 01/02/2019

AR 03971352; Unit 1CAF Fire Protection Issues; 02/07/2017

AR 04162840; Fire Protection Piping Broken; 08/08/2018

AR 01403934; Fire Protection Piping Broken; 08/08/2018

AR 04204023; 0B Diesel Fire Pump 0FP03PB Coolant Sightglass Dirty/Stained; 12/18/2018

AR 04204029; Diesel Drive Fire Pump 0FP03PB Head Gasket Leaking Coolant; 12/18/2018

AR 04209641; FP Pipe Frozen/Ruptured; 01/10/2019

BOA ELEC-5; Local Emergency Control of Safe Shutdown Equipment Unit 1; Revision 106

BOA ELEC-5; Local Emergency Control of Safe Shutdown Equipment Unit 2; Revision 107

BOP FR-1T7; Fire Zone 11.4C-0 Radwaste/Remote Shutdown Control Room 1D-13; Revision 7

BOP FR-1T35; Fire Zones 5.5-1 & 5.5-2 Unit 1/Unit 2 Auxiliary Electrical Equipment Rooms

1D-69/2D-69; Revision 12

BOP FR-1T39; Fire Zones 11.6-1, 11.6-2 Unit 1/Unit 2 Containment Electrical Penetration Area

1D-76, 2D-76; Revision 7

BOP FR-1T40; Fire Zones 5.2-1 & 5.2-2, 5.1-1 & 5.1-2 Unit 1/Unit 2 ESF Switchgear Rooms

1D-77/1D-78/2D-77/2D-78; Revision 9

CC-AA-211; Fire Protection Program; Revision 8

I1-OA-XL-16; BOA PRI-5, Control Room Inaccessibility, Revision 10; 10/28/2016

Byron Technical Specifications; Section 3.3.4 Remote Shutdown Monitoring Instrumentation;

Amendments 141, 171, & 106

Byron Technical Specifications; Table 3.3.4-1 Remote Shutdown System; Amendment 106

GL 86-10 Evaluation BYR-25; Fire Protection Evaluation for Fire Zones 11.3D-2 and 11.3-0

Boundary to Demonstrate Separation Equivalent to BTP CMEB 9.5-1, C5.b (2); Revision 0

LORT Cycle 18-4 BOA PRI-5; BOA PRI-5 Control Room Inaccessibility Review PowerPoint

Presentation; 05/21/2018

ML042310332; Byron Station, Units 1 and 2 NRC Inspection Report 05000454/2004005(DRS);

05000455/2004005(DRS); 08/18/2004

ML072211020; Byron Station, Units 1 and 2 NRC Integrated Inspection Report 05000454/2007003 and 05000455/2007003; 08/08/2007

N-BYLORT4; Byron Licensed Operator Requalification Training (LORT) Cycle 4 Roster;

2/22/2019

N-BYNLOR5; Byron Non-Licensed Operator Requalification Training Cycle 5 Roster;

2/22/2019

N-BY-TQ-ILT; BOA PRI-5, Control Room Inaccessibility PowerPoint Presentation; 10/28/2016

P1-SBY-1758; BOA PRI-5 Equipment Operator PowerPoint Presentation, Revision 0;

08/07/2017

RS-18-144; Byron/Braidwood Updated Fire Protection Report (FPR), Amendment 28;

2/17/2018

Safe Shutdown Database Amend 27; Microsoft Access Byron Fire Protection Safe Shutdown

Analysis Database; 09/07/2018

WO 01925533 01; 2BOSR 3.1.13-2, Reactor Coolant Pump Breaker Position; 10/17/2017

WO 01915176 01; BOSR PL-R2-CV.2, RSDP C/S Functionals, F.1 (Letdown); 10/06/2017

WO 01915176 02; BOSR PL-R2-CV.2, RSDP C/S Functionals, F.2 (Emerg Boration);

10/05/2017

WO 01915176 03; BOSR PL-R2-CV.2, RSDP C/S Functionals, F.3 (Charging CV121);

10/06/2017

WO 01867315 01; 1BOSR 3.1.13-2, RCP Breaker Position 18M Surveillance; 03/19/2017

WO 01860381 01; BOSR PL-R2-MS.1, RSDP C/S Functional Check (MSIVS); 03/23/2017

EC-EVAL 395681; Evaluation of Non-Rated Ventilation Dampers in Technical Requirements

Manual (TRM) Fire Walls at the SX Cooling Towers; Revision 0

EC-EVAL 392627; Evaluation for High Energy Line Break (HELB) Modifications to Elevation

401/426 L-Line Fire Doors; Revision 000

EC-EVAL 381603; Evaluation of Deviations from NFPA 13-1983 for Foam Sprinkler System in

the Unit 1 and Unit 2 Diesel Oil Storage Tank (DOST) Rooms; Revision 0

EC-EVAL 403747; Evaluation for Use of Alternate Compensatory Measures Associated with

Missing Fire Proofing on Structural Beams Due to Attached Secondary and Auxiliary Steel;

Revision 1

EC-EVAL 395449; Evaluation of New Steel Support Members in the Diesel Generator 1B/2B

and Switchgear Room Air Shafts; Revision 000

Calculation BYR-97-118; Hydraulic Calculation for Fire Protection System Area 2-T1 Diesel Oil

Storage Tank Room; Revision 1

Procedure EN-AA-501-0001; Controlled Material Program Approval and Evaluation Process;

Revision 2

Work Order 01881564; Freezing Temperature Protection - Protected Area BLDGS Vent System

and Tanks; 10/23/2016

AR 04226946; NRC Identified - Damper Sticking Open; 03/06/2019

AR 04226906; NRC Identified - Improperly Stored Ladder; 03/06/2019

EC-EVAL 389723; Performance Based Evaluation of Selected Fire Protection Testing in Order

to Extend the Surveillance Interval; Revision 0

Work Order 04722242-01; LR - Inspection of Fire Doors; 04/16/2018

Procedure 0BMSR 3.10.g.4; Fire Door Semi-Annual Inspection; Revision 25

Work Order 04775063-01; LR - Inspection of Fire Doors; 10/02/2018

AR 01375417; 0DSD629 Degraded; 06/07/2012

AR 04056071; Security - D629 Will Not Secure; 09/26/2017

AR 01563626; Fire Doors at the SX Cooling Towers are Degraded; 09/25/2013

AR-00577295; Exelon/AmerGen B.5.B Phase 2/3 fleet response; 01/10/2007

6E-0-3687C; Cable Pans Routing Auxiliary Building Plan E

L. 463-5 Columns L-Q, 10-1B;

Revision AM

6E-0-3691; Cable Pans Riser Routing Auxiliary Building Sections EL. 330-0 - 463-5;

Revision F

6E-0-3773; Lighting Auxiliary Building Plan E

L. 451-0 Rows L-Q, Columns 23-26; Revision AC

6E-0-3779B; Station Emergency Lighting Battery Operated Light Units; Revision L

6E-0-3797P; Wiring Diagram Radio Communication System; Revision A

6E-1-4030AF05; Schematic Diagram Auxiliary Feedwater Regulating Valves 1A, 1B, 1C & 1D

1AF005A, B,C & D; Revision N

6E-1-4030AF07; Byron-Unit 1 SCH. Diag. Steam Gen. 1A Aux. FW. Isolation Valves 1AF013A

from pump 1A and 1AF013E From Pump 1B; Revision Q

6E-1-4087G; Internal-External Wiring Diagram Remote Shutdown Control PNL. 1PL04J Part-8;

Revision U

6E-1-4661D; External Wiring Diagram 480V Auxiliary Building ESF MCC 131X1 Sect. D

1AP21E; Revision P

6E-2-4030MS02; Schematic Diagram Main Steam Isolation Valve 2B (2MS001B); Revision N

6E-2-4030CV10; Schematic Diagram Volume Control Tank Outlet Isolation Valves 2CV112B &

2CV112C; Revision K

M-37; Diagram of Auxiliary Feedwater; Revision BF

BAR0-39-A4; Alarm No: 0-39-A4; Revision 12

BOP FR-1T7; Fire Zones 11.4C-0Radwaste/Remote Shutdown Control Rooms 1D-13;

Revision 7

BOP FR-1T35; Fire Zones 5.5-1& 5.5-2 Unit 1/Unit 2 Auxiliary Electrical Equipment Rooms

1D-69/2D-69; Revision 12

BOP FR-1T39; Fire Zones 11.6-1, 11.6-2 Unit 1/Unit 2 Containment Electrical Penetration Area

1D-76, 2D-76; Revision 7

BOP FR-1T40; Fire Zones 5.2-1& 5.2-2,5.1-1 & 5.1-2 Unit 1/Unit 2 ESF Switchgear Rooms

1D-77/1D-78/2D-77/2D-78; Revision 9

OP AA-102-106; Attachment 1 Operator Response Time Validation Sheet Page 1 of 6;

Revision 4

04809703-01; Appendix R ELBP Inspection F-09(U2 Aux Bldg); 10/15/2018

04843171-01; Appendix R ELBP Inspection F-09(U2 Aux Bldg); 1/09/2019

04657020-01; B.5.

B. Pump Inspection, Maintenance, and Operation; 9/28/2017

EDMG-1; Extensive Damage Mitigation Guideline; Revision 10

EP-AA-112; Emergency Response Organization (ERO)/ Emergency Response Facility (ERF)

Activation and Operation; Revision 20

26-3084-UT-001; High Temperature Slide out Charger Assembly; Revision 0

EC-EVAL 339805; Fire Door Acceptance Criteria; Revision 0

Procedure OP-AA-201-009; Control of Transient Combustible Material; Revision 21

Work Order 01749182; Fire Protection System Fire Hydrants Flow Test; 07/14/2016

AR 04218134; NRC Identified - Enhancements to Byron B.5.b Strategy; 02/07/2019

Procedure BHP 4200-33; Installation of Appendix R Emergency Cable; Revision 10

AR 04221637; NRC Identified - Housekeeping at RADWASTE Panel; 02/19/2019

AR 04222304; NRC Identified - Emergency Lighting in Auxiliary Electrical Equipment Room

Was Found On; 02/21/2019

Procedure 0BMSR 3.10.g.7; TRM Fire Damper 18-Month Visual Inspection; Revision 21

Work Order 01881560-01; Perform Technical Specification Fire Damper Visual Inspection;

2/16/2016

Work Order 04628792-01; Perform Technical Specification Fire Damper Visual Inspection;

06/25/2018

Work Order 01791967-01; Fire Protection Pump Flow and Pressure Test; 06/10/2016

Work Order 01650449-01; Fire Protection Pump Flow and Pressure Test; 12/04/2014