0 UNITED STATES NUCLEAR REGULATORY COMMISSION o
/REGION II 101 MARIETTA ST., ATLANTA, GEORGIA 30323 OCT 0 7 198 Report Nos.:
50-269/88-27, 50-270/88-27, and 50-287/88-27 Licensee:
Duke Power Company 422 South Church Street Charlotte, NC 28242 Docket Nos.: 50-269, 50-270, License Nos.: DPR-38, DPR-47, and and 50-287 DPR-55 Facility Name:
Oconee 1, 2, and 3 Inspection Conducted* August 22-26, 1988 Inspectors:
/6Z4 o
z4e Wri Date Signed W. B. G oersen Datd Signed Approved by:
10sL..
C. M. Hosey, Section Chlef Date Signed
Division of Radiation S fety and Safeguards SUMMARY Scope: This routine, unannounced inspection of the radiation protection program included a review of occupational exposures during extended outages and licensee action on previous inspection finding Results: The licensee's radiation protection program during extended outages appears to be generally effective in protecting the health and safety of occupational radiation worker No violations or deviations were identifie eI 0)2504-20 CSA Ic00 7 pDR
~DIK050C02&9
REPORT DETAILS 1. Persons Contacted Licensee Employees
- C. Boyd, Design Engineer, Site Office R. Brock, Instrument Electrical Engineer
- R. Brackett, Quality Assurance Supervisor
- T. Carroll, Health Physics Supervisor J. Davis, Associate Nuclear Instructor, Production Support Department
- T. Mathews, Compliance Engineer V. Owens, Health Physics Specialist R. Slocum, Relief Vendor Supervisor T. Smith, Health Physics Supervisor
- M. Tuckman, Station Manager
- C. Yongue, Station Health Physicist Other licensee employees contacted during this inspection included engineers, operators, mechanics, technicians, and office personne Nuclear Regulatory Commission
- P. Skinner, Senior Resident Inspector
- Attended exit interview 2. Occupational Exposure During Extended Outages (83729)
a. Unit 3 Refueling Outage The licensee took the unit three reactor off line August 10, 1988, for a 47 day routine refueling outage. Significant work planned for the end of cycle 10 included once through steam generator (OTSG)
ultrasound testing (UT)
of welds, tube sleeving, eddy current testing, and the replacement of main feedwater nozzles; seal replacement on rector coolant pumps; inspection of the unit's turbine and main stop valves; condenser UT and repairs; valve rebuild for approximately 400 valves and the refurbishing of approximately 80 valve actuators; and refueling activitie b. Organization and Management Controls The inspector reviewed the licensee's organization, staffing level and lines of authority as they related to the outage radiation protection program The inspector verified that the licensee had not made organizational changes which would adversely affect the
ability to control radiation exposure The inspector determined that the licensee had assigned and scheduled specific health physics contracts for job coverage on each shift for outage work in the auxiliary building, turbine building, containment and steam generator Four contract technicians were included in these assignments along with Oconee staff personne In each of the four cases a permanent staff member was assigned with the contract technicia Overall responsibility for outage work coverage was assigned to the Unit 3 Health Physics Supervisor and the Unit 3 Health Physics General Supervisor of Station Sciences who reports directly to the station Radiation Protection Manager (RPM).
Ninety-seven contract health physics personnel were -on site to support the normal plant health physics staff of 96 personne The inspector attended a morning daily outage planning meeting to review the licensee's scheduled work for the day and outage progres The inspector noted that personnel exposure problems or As Low As Reasonably Achievable (ALARA)
person-rem totals or goals were not addressed during the meetin No violations or deviations were identifie c. Training and Qualifications
-
The licensee was required by Technical Specification 6.1.1.4 to use in responsible positions radiation protection technicians who met the requirements of ANSI/ANS-3.1-197 The licensee utilizes three vendors to provide contract health physics suppor The inspector reviewed the licensee's method for selection and qualification of contract health physics technicians utilized during outage The licensee has a health physics supervisor who typically reviews the resumes for various candidates approximately six weeks prior to the start of the outag The licensee primarily utilizes health physics technicians having at least three years of experience and tries to obtain technicians that have demonstrated good working performance at the facility in the pas Licensee representatives reported that they were able to accomplish these goals ninety percent of the time. Technicians that have not worked at a Duke Power Company (DPC)
nuclear power plant in the past are typically brought on site for training two weeks prior to the outage. Technicians who have prior facility work experience are brought in approximately one week before the outage to process through security and general employee training requirement The inspector reviewed the licensee's Health Physics Vendor Entry Test which is administered to all contract technicians reporting to a DPC facility for the first tim The written test includes one hundred questions which address basic knowledge and skills in the areas of algebra, radiation units, radiation physics, ALARA concepts, instrumentation limitation and use, system related nuclear power
plant radiological problems, radiological biological effects, nuclear regulatory exposure limits and requirements, internal and external exposure controls, decontamination techniques, radioactive waste reduction management, contamination control, and survey technique The licensee also administers a site specific health physics training program for vendor employees entering the site for the first tim The training objectives are specified in Oconee Nuclear Station Lesson Plan OCHP-008 dated August 1, 198 The site specific training prerequisites require that the technician meet the requirements of ANSI 3.1-1978 and make a test score greater than 70%
on the Health Physics Entrance Tes The site specific training addresses health physics related duties prescribed in Station Directives, Health Physics Procedures, System Health Physics Manual, Health Physics Section Manual and other applicable plant procedure The training which takes three days to complete also includes a review of specific outage plans and major work projects to be carried out during the outag The lesson plan for the licensee's Unit 3 outage specified thirty-six specific topics to be covered during the training, and included an outline on the training presentation During the training, licensee employee's having expertise in various subjects are utilized as guest speakers under the supervision of the training coordinato Upon completion of the program, students are required to complete a Health Physics Site Specific Test which included over ninety questions on site policies and procedure Students must score greater than 70% to work at the facilit The inspector discussed retraining requirements for contract health physics technicians that may have received their initial site retraining more than one or two years ago and determined that the licensee did not have a formal plan for vendor health physics retrainin Licensee representatives agreed to establish a retraining policy for vendor health physics technician The inspector stated that a review of licensee retraining policy and retraining objectives would be reviewed in a subsequent inspection and would be tracked by the NRC as Inspector Followup Item (IFI)
50-269/88-27-0 The inspector reviewed general employee training records for selected individuals entering Unit 3 containment on various radiation work permits and verified that each person selected for review had successfully completed required trainin No violations or deviations were identifie d. External Exposure Control 10 CFR 20.203 specifies the posting labeling and control requirements for radiation areas, high radiation areas, airborne radioactivity areas and radioactive materia During tours of the plant's turbine, auxiliary, and Unit 3 containment building the inspector reviewed the licensee's posting and control of radiation areas, high radiation areas, airborne radioactivity material areas and the labeling of radioactive materia The inspector selectively reviewed active RWPs for appropriateness of the radiation protection requirements based on work scope, location, and condition During tours in the auxiliary building and in the licensee's Unit 3 containment the inspector observed compliance with RWP requirements and discussed RWP requirements with plant workers at the job site. The RWP requirements appeared appropriate for assigned work activitie The inspector discussed planned work inside unit three containment with a maintenance foreman. The inspector reviewed Nuclear Station Work Request 51547G, Unit 3. The work requested the refurbishment of a limitorque operator on reactor coolant pump 3B1 low pressure service water oil cooler inlet valv The inspector observed the mechanical maintenance personnel's preparation for the tas The inspector also reviewed the licensee's procedure MP/O/A/1210/07 Operator Limitorque SMB/SB Series Removal and Replacement and MP/O/A/1210/8 Disassembly and Reassembly of SMBOOO to be utilized by the mechanical maintenance personnel for performing -the task. The inspector attended a discussion between the maintenance personnel and health physics concerning the radiation protection requirements for the tas The maintenance workers were assigned to RWP 3080, Limitorque Operator Refurbishmen The mechanical maintenance personnel were instructed to locate the health physics technician assigned in the area for a survey of the work area and any additional requirement The inspector and mechanical maintenance personnel donned required protective clothing and checked in with the health physics containment access personnel who verified that all persons entering containment were qualified to enter on the assigned work permi The workers and inspectors entered containment and located the health physics technicia The mechanical maintenance personnel located the valve operator for the health physics technicia The health physics technician asked the workers to move to a known low dose rate for ALARA purposes and made contamination and radiation surveys in the limitorque work are The health physics technician surveyed the area and the limitorque operator and reported the general area dose rates to be up to 10 mrem per hour and the limitorque operator only slightly contaminated. The inspector made radiation survey measurements of the work area and found that they agreed with the licensee's health physics technician's results. The inspector observed the workers following removal procedure and the work progressed quickl The limitorque operator, which weighed approximately 120 pounds, was lifted and placed in a clear plastic bag and moved to the equipment hatch where health physics personnel placed the valve operator in another bag, then taped and tagged the limitorque operator for transfer to the contaminated material
refurbish sho A refurbish shop had been established in a mechanical maintenance work area. The inspector determined that the observed work had been adequately controlled and efficiently performe No measurable exposure was registered on any of the worker's self-reading dosimeters (SRD) as the removal only took a few minutes to perfor The inspector determined that about 80-such limitorque operators would be checked during the units outage..Upon exiting the containment self-reading dosimeter results were reported to health physics technicians for updating the SRD exposure record Upon exiting the area health physics personnel required all workers to monitor hands and feet on a hand and foot monitor located at the containment entrance and exit point. The workers then proceeded to the clean change room for a whole body survey using a whole body frisker prior to donning street clothes. The inspector also verified the general employee training qualifications for each of the mechanical maintenance personne The inspector toured all elevations of the containment building and observed work in progress on the steam generators, containment sump, and reactor vessel hea The inspector made independent radiation surveys with licensee survey instruments and found all radiation and high radiation areas inside containment properly poste While reviewing a licensee Unusual Dosimetry Incident Investigation report, made during a previous outage, the inspector identified a problem with the use of an off scale self reading dosimeter (SRD).
The report documented that an individual, prior to entry into the reactor building reported to a reactor building health physics technician that his SRD was off-scal The reactor building health physics technician re-zeroed the individual's SRD and allowed the worker to enter the reactor building. The individual worked in the reactor building for about two hour Upon exiting the reactor building the individual's dosimeter was again off scal Health physics personnel zeroed the SRD again and observed the SRD drift upscale to 300 mR in about 30 minute The SRD was removed from service at this point and the licensee performed a readout on the licensee's thermoluminescent dosimeter (TLD)
to determine the individual's dos The measured dose from the TLD was comparable with co-workers dose and below any administrative exposure limit The inspector pointed out potential problems with off scale dosimeters being reissued without a documented drift test and response check to verify operability and accurac Licensee representatives agreed to revise dosimetry procedures to remove off scale dosimeters from service until an adequate SRD drift and response check was performed if the cause for the dosimeter being off-scale was not known for sur SRDs that are off-scale because they were bumped or dropped will not normally be tested prior to rezeroing and reissuing the dosimeters. The inspector stated that a review of the licensee's procedures and requirements for determining the operability of off scale SRDs would be reviewed in subsequent inspections and will be tracked by the NRC as an IFI 50-269/88-27-0 No violations or deviations were identifie e. Internal Exposure Control (1) Measurement of Airborne Radioactivity 10 CFR 20.103(a) establishes the-1-imits for exposure of individuals to concentrations of radioactive materials in air in restricted area This section also-requires that suitable measurements of concentrations of radioactive materials in air be performed to detect and evaluate the airborne radioactivity in restricted area The inspector reviewed selected routine air sample results made in the Unit 3 containment and the results of special air samples taken to support containment work authorized by various radiation work permits. The inspector determined that the air sample results were traceable to calibrated air sampler No violations or deviations were identifie (2) 10 CFR 20.103(b) requires the licensee to use process or other engineering controls, to the extent practicable, to limit concentrations of radioactive material in air to levels below that specified in Part 20, Appendix B, Table I, Column 1 or limit concentrations when averaged over the number of hours in any week during which individuals are in the area, to less than 25 percent of the specified concentration The inspector observed the use of engineering controls such as high efficiency particulate air filters on steam generators in containment and "tent containments" on the turbine deck used to control airborne radioactive material from sandblasting contaminated turbine part No violations or deviations were identifie (3) Respiratory Protection Previous inspections identified respiratory protection program weaknesses including poor and outdated procedures and problems with the plant breathing air system. The inspector reviewed the licensee's respiratory protection procedures which had been recently revised, the procedures contained sufficient information for implementing the current respiratory protection program and were found to be a significant improvement from previous procedure The problems previously identified in the plant's breathing air system included problems associated with routine calibration checks of system pressure gauges in containment, operator actions upon system carbon monoxide, monitor failure, and as built versus plant drawings for air
manifolds and pressure gauges. The inspector determined that an engineering design request had been submitted and approved to upgrade the plant's breathing air system by increasing the systems capacity and air quality monitorin Drawing problems are expected to be corrected with-the system modifications. The inspector determined that the response-.check for pressure gauges in containment had been placed on.-a -refueling cycle and had been checked during the Unit 3 refueling-outag The inspector determined that Operations Procedure OP/O/B/1106/32 Oconee Nuclear Station Breathing Air System dated October 20, 1987, had been changed to require operations staff to red tag (take out of service) the breathing air system-when the carbon monoxide monitor. is out of servic The inspector also reviewed procedure 1SA-18/C-3, Breathing Air Carbon Monoxide High dated November 5, 1987. The procedure required operations to announce over the plant public address (PA)
system to discontinue use of the breathing air when the carbon monoxide monitor was out of servic The inspector stated that a direct communication to the health physics shift-supervisor would be an additional safety factor since the health physics shift supervisor could determine if and where plant breathing air was in us Operations representatives agreed to revise the procedure to add the direct communication to health physics shift supervisor to improve safety consideration CFR 20, Appendix A Footnote h states in part that when air supplied hoods are used and a protection factor credit is taken during the use, calibrated gauges or flow measuring devices shall be used to ensure that proper air flow rates are maintaine The licensee had obtained the services of a vendor to supply grade D breathing air where supplied air hoods were utilize The inspector reviewed the procedures utilized for the vendor supplied air and the results of test to determine that breathing air quality met the requirements for grade D ai The licensee was utilizing air supplied hoods in the steam generator and on the turbine deck in the sand blasting ten The inspector determined that the pressure of the vendor supplied air to the air hood respirators was sufficient to meet the Mine Safety and Health Administration (MSHA)
and National Institute for Occupational Safety and Health (NIOSH) flow requirements for the length of hose used as specified in the hoods certificatio No violations or deviations were identifie (4) Assessments of Internal Radiation Exposures 10 CFR 20.103(a)(3) requires in part, that the licensee use suitable measurements of concentrations of radioactivity in air
in restricted areas and in addition, as appropriate, shall use measurements of radioactivity in the body or excreted from the body, or any combination of such measurements as may be necessary for timely detection and assessment of individual intakes of radioactivit The inspector determined that the licensee had made 13 assessments of exposures exceeding 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> at MPC levels in 1 day and one assessment of exposure exceeding 40 hours4.62963e-4 days <br />0.0111 hours <br />6.613757e-5 weeks <br />1.522e-5 months <br /> at MPC levels in a 7 day period in 198 The licensee had also made one assessment for an individual that had received an exposure greater than an administrative limit of 35 hours4.050926e-4 days <br />0.00972 hours <br />5.787037e-5 weeks <br />1.33175e-5 months <br /> at MPC levels in any 7 day perio The inspector reviewed the licensee's assessments of exposures to concentration of radioactive material in air greater than 2 MPC per day or 40 MPC per any 7 day perio The highest exposure for the year requiring assessment was 41.78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> at MPC levels in one da The licensee calculated the exposure from measurements made in the body utilizing the facilities whole body counter which detected measurable quantities of mixed fission and corrosion product The individual had become contaminated installing an oil enclosure on a reactor coolant pump motor during the previous Unit 2 outage when a section of the cover brushed against the employee's fac The licensee added the exposure to previous exposures in the first calendar quarter of 1988 for a total of 43.21 hours2.430556e-4 days <br />0.00583 hours <br />3.472222e-5 weeks <br />7.9905e-6 months <br /> at MPC level Surveys made in the area reported contamination levels on the oil enclosures up to 14,000 disintergrations per minute per 100 square centimeters (14,000dpm/cm2). A coworker working with the individual during the entire job was not contaminated. The worker was counselled on health physics work practices and restricted from entering the radiological control area for seven consecutive day The radiation work permit requirements were not change No violations or deviations were identifie f. Surveys, Monitoring and Control of Radioactive Material 10 CFR 20.201(b) requires each licensee to make or cause to be made such surveys as (1) may be necessary for the licensee to comply with the regulations and (2) are reasonable under the circumstances to evaluate the extent of radiation hazards that may be presen The inspector reviewed selected records of radiation and contamination surveys performed during the Unit 3 outage and discussed the survey results with licensee representative The licensee began moving fuel August 24 at about 2200. The inspector verified that the licensee made radiation surveys inside containment
and in the containment penetration rooms near the fuel transfer canal during fuel movement on the 24 and 25 of August 198 During tours of the facility the inspector observed health physics technicians performing contamination surveys of equipment leaving contaminated areas in.the auxiliary building and Unit 3 equipment and personnel containment exit The inspector observed routine air sampling equipment set up in various locations in containment to monitor for changes in airborne concentration The licensee has defined areas within the auxiliary building as
"controllable" or "noncontrollable" for decontamination purpose "Controllable" areas are those that are frequently entered and have reasonably low general area radiation dose rate "Non-controllable" areas were those areas that are rarely entered and/or have a high general area radiation level Examples of "non-controllable" areas include the spent resin storage tank rooms, high pressure injection pump rooms, and letdown filter room The "controllable areas" includes potentially contaminated areas and contaminated areas in the auxiliary building and has a total square footage of 107,750 square feet (ft?).
In January of 1988, the licensee established monthly goals for decontamination of the controllable areas. The August goal was to have 89,025 ft2 or 82% of the defined area of 107,750 ft 2 decontaminate During the inspection the licensee had 87% of the controllable area in the auxiliary building decontaminate Management support for the decontamination effort is demonstrated in a intrastation letter from the Station Manager to the Station Superintendents dated August 2, 1988, encouraging the supervisors to assist in obtaining a 1988 goal of having 90% of the controllable area decontaminated by the end of the yea It appeared that the plant was on schedule in meeting the decontamination goa No violations or deviations were identifie g. Maintaining Occupational Exposures ALARA 10 CFR 20.1c states that persons engaged in activities under licenses issued by the NRC should make every reasonable effort to maintain radiation exposures as low as reasonably achievable. The recommended elements of an ALARA program are contained in Regulatory Guide 8.8, Information Relevant to Ensuring That Occupational Radiation Exposure at Nuclear Power Stations will be ALARA, and Regulatory Guide 8.10, Operating Philosophy for Maintaining Occupational Radiation Exposures ALAR The inspector reviewed the status of the licensee's ALARA program activities and goals for 1988. The licensee's annual person-rem goal was established by the corporate office utilizing industry and utility averages of person rem per task planne The corporate staffs goal was set at 1100 person-rem for the three unit facility having refueling outages during 1988 for Unit 2 and 3. The facility
Station Manager established a more aggressive goal of 1000 person-rem for 1988. The inspector determined that the total person-rem through July was 52 The ALARA person-rem goal for the Unit 3 outage which began August 10, 1988, was set at 306 person-rem. As of August 23, 1988 (day 13 of the 47 day outage), the actual exposure based on self reading pocket dosimeter information was at 92 person-rem or about 30% of the outage goal. Significant jobs which were generating most of the outage dose included work on reactor coolant pump and motor, reactor vessel head, various valves, in service inspection (ISI),
decontamination efforts, and steam generator wor An estimated 113 person-rem was allotted for eddy current testing, feed water nozzle replacement, tube sleeving, and other steam generator activitie The inspector determined that the supervisors from each section at the station (approximately 20) provide the Station Manager with an estimated person-rem for their group annuall The ALARA group reviews the section estimates and makes proposed alterations, if necessary. The ALARA group works with the various sections by providing the supervisor with previous exposure data for various tasks. The Integrated Scheduling group also provides the supervisors information on outage plans and upcoming work for the next yea The inspector reviewed a graph of the licensee's (person-rem)
collective radiations dose by month The actual exposure was tracking below but with the planned estimates. The Unit 2 outage which began on February 3, 1988 and ran through April 10th was completed on schedule and the actual person-rem total was 98% of the estimated 433.7 person re The inspector reviewed selected Health Physics ALARA Pre Planning Work Sheets and noted that the use of shielding, prejob meetings, mock-up training, flushing or slucing, decontamination, pre-job fabrication of equipment, and the use of video equipment (for remote monitoring) were included on various tasks to reduce the plant's collective radiation dos No violations or deviations were identifie h. Solid Radioactive Waste and Transportation of Radioactive Material 10 CFR 71.5 requires that licensees who transport licensed material outside the confines of the plant or other place of use, or who deliver licensed material to a carrier for transport, shall comply with the applicable requirements of the regulations appropriate to the mode of transport of the Department of Transportation (DOT) in 49 Parts 170 through 18 CFR 173.441(b)(4) requires that radiation levels external to a package of radioactive material not exceed 2 millirems per hour in any normally occupied position of the transport vehicle, unless it is a private transport vehicle and certain other conditions are satisfie CFR 173.425(b) specifies the transportation requirements for shipping low specific activity (LSA)
radioactive materials in exclusive-use vehicle In addition to the limits for external radiation levels and removable contamination 49 CFR 173.425(b)(4) requires that the shipment must be loaded by the cosignor (e.g., the licensee shipper) and unloaded by the cosigne Section 49 CFR 173.425(b)(6)
requires that the shipment be braced to prevent shifting under normal transportation condition On March 7, 1988, an exclusive-use vehicle (which was not a private transport vehicle) containing a shipment of low specific activity radioactive material (SPRING REPLACEMENT TOOLING) left the Oconee facility and upon receipt of the shipment at Babcock & Wilcox Naval Nuclear Fuel Division Research Laboratory (B&W NNFDRL) on March 8, 1988, the radiation levels in the cab of the exclusive use vehicle were reported to be 2.3 millirems per hou Babcock & Wilcox Naval Nuclear Fuel Division Research Laboratory notified the NRC of the dose rates in the cab in a letter to the Director of Region II dated April 8, 198 The B&W NNFDRL staff unloaded the radioactive material shipment on the 8th of Marc The inspector determined through interviews with Oconee personnel that they received notification by phone one week after B&W performed the survey. During the Oconee inspection, the inspector reviewed the licensee's shipment surveys and associated paper work for Oconee radioactive material shipment number 88-05 The licensee's survey information for the transportation vehicle showed the following: highest contact reading on the truck was 25 millirad per hour, highest results for a survey 2 meters from the truck surfaces was 1.5 millirad per hour and the highest reading in the transport cab was 0.7 millirad per hou The shipment included five packages, three drums and two boxes. With the exception of one box all of the packages were reported to have radiation levels less than 30 millirad per hour at 0.5 inches and less than 3.0 millirad per hour at one meter. However, one of the boxes containing long rods utilized in the fuel storage pool at the licensee's facility had a contact reading of 750 millirad per hour at 0.5 inches and 5 millirad.per hour at one mete The inspector determined through discussions with licensee representatives that the box was positioned on a diagonal on the bed of the transport vehicle and had to be removed and turned around 180 degree According to the licensee, the box was repositioned to reduce the exposure dose rates in the cab of the vehicle to the 0.7 millirad per hour rate.The inspector reviewed the qualifications of the individual who had made the surveys and determined that the individual was qualified to make radiation surveys. The inspector also reviewed calibration checks on the survey instrument (geiger - muller) utilized to make the survey and found it was capable of measuring radiation within acceptable limit The licensee's survey record did not include a drawing of the vehicle indicating the position of the packages. The inspector determined through interviews with licensee representatives, that the
shipment had been properly secured for transport and that shifting of the long tools in the long.box having the highest dose rates would be minimal (due to their length and the length of the box).
The inspector informed the licensee that failure to ensure that the dose rates in the cab of an exclusive sole use vehicle would normally be considered an apparent violation of NRC and Department of Transportation requirements. However, the inspector made the item an unresolved item at the exit meeting held August 26, 198 Upon returning to the Region II office the inspector requested the Babcock & Wilcox Naval Nuclear Fuel Division Research Laboratory provide copies of their receipt survey of the shipment, and the calibration records of the instrument used to document the radiation survey and determined that the (B&W NNFDRL)
survey was made by a qualified individual utilizing a geiger-muller survey instrument capable of measuring the radiation levels documented in their surveys and was calibrated within acceptable limit Region II Management reviewed the information provided from B&W NNFDRL and Oconee and determined that there was not basis for accepting one of the surveys over the othe Therefore a Notice of Violation will not be issue The bracing of loads may involve blocking, shoring, tie-downs (chairs and/or straps), or other restraint As noted in NRC Information Notice 87-31 Blocking, Bracing, and Securing of Radioactive Materials Packages in Transport, dated July 10, 1987, Section 49 CFR 173.403(c), states that "all initial, intermediate, and final loading and unloading are to be carried out in accordance with the directions of the cosignor or consignee."
Blocking, bracing, and tie-downs, therefore, are considered to be part of the loading process and the responsibility of the cosignor-shipper-licensee for exclusive use shipment An IFI was identified in a routine inspection of transportation activities in Inspection Report No. 87-42 during October 198 The IFI concerned the training and qualifications of personnel assigned load securing responsibilitie Inspection Report No. 87-42 noted some confusion by the licensee's staff on the proper method for securing the load of three packages of dewatered resin on a flat bed truc On August 23, 1988, the inspector observed the loading of three liners of dewatered resin waste (radioactive material LSA)
on a flatbed trailer for transport to a disposal facility. The loading for shipment 88-177 was completed and properly secured in an orderly manne Security of the load was verified by a maintenance superviso The inspector verified that all personnel involved in the lifting, loading, and securing of packages were properly trained in rigging and weight handling procedures by reviewing licensee training records for each person assigned to the job that day. The inspector determined that the standing work permit utilized by the maintenance staff during the loading and securing of radioactive material shipments requires assigned personnel to have completed the
training for task number MM-1119 Rigging and Weight Handlin The training includes classroom and on the job trainin CFR 20.311 requires a licensee who transfers radioactive waste to a land disposal facility to prepare all waste so that the waste is classified in accordance with 10 CFR 61.55 and meets the waste characteristic requirements of 10 CFR 61.5 The inspector made independent surveys of radioactive waste shipment 88-177, verified that the shipment was properly placarded, and reviewed the shipping paper The inspector -determined that the waste was properly classified in accordance with the requirements of 10 CFR Part 6 No violations or deviations were identifie. Action On Previous Inspection Findings (92701)
a. (Closed) IFI 50-269/87-42-01, 50-270/87-42-01, and 50-287/87-42-0 Review licensee's method for correlating air sample results with air sampling equipmen The inspector reviewed licensee procedure HP/0/B/1002/21, Operating Procedure for Portable Air Samplers Equipped with 2 Inch Filter Head,
)
dated November 23, 1987, and verified that the licensee had revised the procedure to require the air sampler instrument number to be documented with the air sample result The inspector reviewed selected air sample results and verified that the air sample results were traceable to a specific air sample b. (Closed) IFI 50-269/87-42-02, 50-270/87-42-02, and 50-287/87-42-0 Review licensee's evaluation of its respiratory protection procedure The inspector reviewed the licensee's respiratory protection procedures and determined that they had been revised to reflect current respiratory protection activitie c. (Closed) IFI 50-269/87-42-03, 50-270/87-42-03, and 50-287/87-42-0 Review the licensee's controls for the breathing air system when the system carbon monoxide monitor was out of servic The inspector reviewed licensee operation procedures for carbon monoxide monitor failure and verified that the breathing air system would be removed from service, tagged out and that an announcement, that the breathing air system, was out of service would be made over the plant's public address syste d. (Open)
IFI 50-269/87-42-04, 50-270/87-42-04, and 50-287/87-42-0 Review licensee's evaluation of Breathing Air System drawings verses
as-built configuration and the establishment of a refuel cycle calibration for system air pressure gauges located inside containment The inspector determined that an Engineering Request to upgrade the plant's breathing air system had been approved to increase the system's capacity and safety monitorin The breathing air system drawings would be modified as necessary to show system additions and as-built configuration The inspector did determine that the instrumentation staff had set the containment pressure gauge checks on a refueling cycle and were being calibrate e. (Closed) IFI 50-269/87-42-05, 50-270/87-42-05, and 50-287/87-42-0 Review the training and qualifications of persons assigned load securing responsibilities for radioactive material shipment The inspector determined that the licensee has a standing maintenance work request that requires personnel assigned the responsibility to lift, load, and secure radioactive packages. The inspector reviewed a radioactive material shipment loading and determined that all personnel involved were properly qualified and had received the required trainin.
Exit Interview The inspection scope and finding were summarized on August 26, 1988, with those persons indicated in Paragraph 1 abov The inspectors described the areas inspected and discussed in detail the inspection findings listed below. The licensee did not identify as proprietary any of the material provided to or reviewed by the inspector during this inspectio During the exit meeting the inspector discussed an unresolved item concerning the exposure in the cab of a transport vehicle in excess of 2 millirem requirements as specified in 10 CFR 71.47(d) or 49 CFR 173.441(b)(4) (See Paragraph 2.h).
The licensee took exception to the unresolved item and stated that the licensee did not agree that a violation had occurred and would probably deny the violation if issue Following the inspection exit meeting, Region II contacted the receiving licensee regarding the unresolved item and requested information on qualifications of their personnel making the survey, the instrumentation type, and its associated calibratio Region II evaluated the qualifications and monitoring programs for both the shipping and receiving licensee's and found them both to be acceptabl Since there was no independent third party survey made and there was insufficient information to question either licensee's survey the Region II decided not to issue a violation based upon inconclusive evidenc Item Number Description and Reference 50-269/88-27-01 IFI - Review the licensee's criteria for and contents of a vendor retraining program for contract health physics technicians (See Paragraph 2.c).
50-269/88-27-02 IFI - Review the licensee's procedures and requirements for determining the operability of off-scale self reading pocket dosimeters (See Paragraph 2.d).