U. S. NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT
REGION IV
IE Inspection Report No. 50-267/80-21 Docket No. 50-267 License No. OPR-34 Licensee:
Public Service Company of Colorado P. O. Box 840 Denver, Colorado 80201 Facility Name:
Fort St. Vrain Nuclear Generation Station Inspection at:
Fort St. Vrain Site, Platteville, Colorado Inspection Conducted:
October 1-31, 1980 h1 N
/ /S[8C Inspector,:
/
M. W. Dickerson, Senior Resident Reactor Inspector Date '
s
>
S h! ~]
ukW
/0// ~1/ 80 R. E. Collins, Resident Reactor Inspector Date '
,
Approved b -
/ X.,)
u N u' $ 0"~
l0 3/ $0
'
t,T. F. Westerman, Chief, Reactor Projects Section No.1 Cate '
Insoection) Summary Insoection conducted on October 1-31, 1980 (Report No. 50-267/80-21)
Areas Inspected:
Routine, announced inspection of review of plant operations; followup on previous items of noncompliance; surveillance; maintenance; opera-tional safety verification; review of periodic and special reports; and review of licensee event reports.
The inspection involved 197 inspector-hours on site by two (2) NRC inspectors.
Results:
With the seven (7) areas inspected, one item of noncompliance was identified (failure to comply with procedural requirements, Paragraph 3).
N O307n h &
__
_
_ _
-
. - - =.
-
,
.
DETAILS 1.
Persons Contacted L. Brey, QA Manager
<
W. Franklin, Shift Sepervisor
C. Fuller, Reactor Engineer J. Gamm, Supervisor Technical Services E. Hill, Superintendent or Operation W. Hillyard, Administrative Services Manager R. Lamb, Electrical Supervisor J. Liebelt, Maintenance Supervisor F. Mathie, Operations Manager
T. Orlin, Superintendent Operations QA
G. Riegel, Shift Supervisor
'
R. Wadas, Training Supervisor D. Wars tourg, Manager Nuclear Production V. Wetzbarger, Scheduling & QC Supervisor The inspectors also contacted other plant personnel including reactor operators, maintenance men, electricians, technicians and administrative personnel.
2.
Licensee Action on Previous Insoection Findings (Closed) Item of Noncompliance (50-257/8015-01):
Failure to adhere to requirements of RWP #2365.
The corrective action specified in the licensee's response P-80320, dated July 16, 1980, has been reviewed by the inspector.
(Closed) Item of Noncompliance (50-267/8018-01):
Recorder ZR-1233-1
not working and no PRT written.
A PTR was issued and the recorder
repaired.
A memo was 1;so issued to all involved personnel stating that furtner occurre*:es of this type would result in disciplinary action 3.
Goerational Safety Verification The inspector reviewed licensee activities to ascertain the facility is being operated safely and in conformance with regulatory requirements, and the licensee's management control system is effectively discharging its responsibilities for continued safe operation.
The review was conducted by direct observation of activities, tours of the facilities, interviews and discussions with licensee personnel, independent verifi-cation of safety system status and limiting concitions for operations, and review of facility records.
-
_-
,.
.
._
- -. _ _ -.
-
. _.
-
.
.
. _ _
- _..
_.
.
.
Included in the inspection were observation of control room activities i
review of operational logs, records, and tours of accessible areas.
Logs and records reviewed included:
~
Shift Supervisor Logs
.
Reactor Operator Logs
.
Equipment Operator Logs
.
Auxiliary Operator Logs
.
..
Technical Specification Compliance Logs
.
Operations Order Book
.
System Status Log
.
Form 1 Log (Jumper Log)
.
Plant Trouble Reports
.
During tours of accessible areas, particular attention was directed to the following:
Monitoring Instrumentation
.
Radiation Controls
,
.
J l
Housekeeping
.
Fluid Leaks
.
Piping Vibrations
.
Hanger / Seismic Restraints
.
Clearance Tags
.
Fire Hazards
.
Control Room Manning
.
.
The operability of selected systems or portions of systems were verified by walkdown of the accessible portions.
Observed was the Emergency Feedwater and Condensate System.
Procedures were also reviewed and implementation observed for Liquid Waste Release #410.
The release was made in a satisfactory manner.
,
-.,.,
..
y.,,
,,..,--..,m.e.
,,,,,. -,,
,
,_,o--.,,.-,_
r
,,,,.,m-,
,,
,...y
. + _,
,,-.,.
. w.,
,v.-
_.
. _
_
__-
.__
.
!
During a plant tour on October 27, 1980 at 10:46 a.m., seals were found missing from valves V-2212 and V-2213, Steam Water Dump Isolation Valves for Loop 1, although the valves were in the open position as required
!
by Overall Plant Operating Procedure I (OPOP I).
This procedure con-tains the sealed valve checklist in Section B.31 which requires certain valves to be sealed in position prior to plant startup.
This checklist had last been completed on September 24, 1980 and no reason for a change is known to have occurred.
The plant power level at the time the missing seals were discovered was approximately 4%.
The licensee replaced the seals upon notification.
Technical Specification AC 7.4.a requires in part that " Written procedures shall be established, implemented and maintained.
" and OPOP I,
..,
section B, requires that certain valves be locked in position prior to plant startup.
Section B.21.b contains the sealed valve list for System 22 (Secondary Coolant System).
Contrary to these requirements the valves noted were found not sealed.
The failure to fulfill these requirements were discussed with the licensee at which time it was pointed out that this was an apparent item of noncompliance (8012-1).
The inspector had no additional questions in this area.
4.
Maintenance (Monthly)
The inspector reviewed records and observed work in progress to asce/tain that the following maintenance activities were being conducted in ac;ordance with approved procedures, Technical Specifications and Appropriate Codes and Standards.
PTR 10-392 Auxiliary Boiler Room Fire Alarm PTR 10-417
)
PTR 10-418
)
PTR 10-419
)
PTR 10-420
) Replace 4-Bolt Flange 0-Rings on System 91, Hydraulic PTR 10-421
) System PTR 10-422
)
PTR 10-423
)
PTR 8-128 Repair Bypass Valve HV-3113-3 No items of noncompliance or deviations were identified.
5.
Surveillance (Monthly)
The inspector reviewed all aspects of surveillance testing invol.ing safety-related systems.
The review included observation and review relative to Technical Specification requirements.
The surveillance tests reviewed and observed were:
-
--
.
. - - -
.
- -.
. -
- - -
~
.-
_-_
_ ____-_ ___
=_ _ _ _. _ _ _.
..
..
_.
,
.
.
,
SR 5.4.1.2.7 c-M Superheat Header Temperature Test i
SR 5.4.1.3.6 b-M, Circulator Seal Malfunction Test SR 5.4.1.3.2 c-M, Feedwater Flow Test SR 5.4.1.2.4 a-M, Circulator iC and iD Tripped Test SR 5.4.1.2.3 a-M, Circulator iA and iB Tripped Test No items on noncompliance or deviations were identified.
6.
Reoort Reviews
,
i The inspector revi-awed the September 1980, Monthly Operating Information Report.
'
No items of noncompliance or deviations were identified.
7.
Review of Plant Onerations The inspector attended training lectures provided to the Physical
Security personnel and verified that the lesson plan objectives and schedule were being met.
No items of noncompliance or deviations were identified.
8.
Review of Licensee Event Reoorts The inspector reviewed licensee event reporting activities to verify
'
that they were in accordance with Technical Specification, Section 7, including identification details, corrective action, review and evalua-tion of aspects relative to operations and accuracy of reporting.
l The following reports were reviewed by the inspector:
78-30 80-42
'
80-03 80-43 j
80-36 80-44
'
80-39 80-48 No items of noncompliance or deviations were identified.
9.
Exit Interviews Exit interviews were conducted at the end of various segments of this
,
inspection with Mr. D. Warembourg (Manager, Nuclear Production) and/or other members of the Public Service Comoany staff.
At the interviews, the inspector discussed the findings indicated in the previous paragraphs.
The licensee acknowledged these findings.
]