IR 05000003/1978002

From kanterella
Jump to navigation Jump to search
IE Insp Repts 50-003/78-02 & 50-247/78-02 on 780126-27.No Noncompliance Noted.Major Areas Inspected:Radiation Protection During Refueling & Observation of Radiological Safety & Work Practices
ML20042A079
Person / Time
Site: Indian Point  
Issue date: 02/10/1978
From: Knapp P, Thonus L
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20042A077 List:
References
50-003-78-02, 50-247-78-02, 50-247-78-2, 50-3-78-2, NUDOCS 8203230065
Download: ML20042A079 (3)


Text

-

.

U.S. NUCLEAR REGULATORY COMMI_. ION

-

.

0FFICE OF INSPECTION AND ENFORCEMENT

-

Region I g

/15 FEBpato PW nav 50-03/78-02

.

Report No. gn_747/7A_o';

,, *

50-03 8 8gnes188 cE**'

Docket No. 80_p47 g8 License No DPR-5 Priority Category nr noo_7g Licensee:

rnogn14aona ra4 nn r-n, ny n r yo,,, vork, Inc.

d Trvinn placo

  • low Ynrk-Now Ynck 1000~4 Facility Name: inaian pnint Hncloar Gonoratinn Units 1 and 2 Inspection at: Indian Point Station, Buchanan, New York Inspection conducted: January 26-27, 1977 k ff M,

2[o/ryy

[! 117 Th'bn'up, Rapiation Specialist Inspectors:

L dete/ s'igned date signed

.

.

date signed O

Approved by: x(x W Y' 'N M

2/fg/7p P. hKnapp, Chief, Radiahjon Support datelsigned

,

Section, FF&MS Branch

'

Inspection Summary:

Inspection on January 26-27,1978 (Report Nos. 50-03/78-02; 50-247/78-02)

Areas Inspected:

Routine, announced inspection of Unit 2 radiation protection during refueling including facility tour, procedures and advance planning and preparation.

Upon arrival the inspector toured the facility including portions of the combined Unit 1 and Unit 2 controlled area to observe radiological safety and work practices.

The inspection involved 10 inspection hours onsite by one NRC inspector.

Resul ts:

Of the three areas inspected no items of noncompliance were found.

Region I Form 12 (Rev. April 77)

8203230065 780214 PDR ADOCK 05000003 G

PDR

_

_ _ _ _ _ _ _ _ _.

._ -

'

.

,

(

-

.

DETAILS 1.

Persons Contacted

  • M. Byster, QA Engineer J. Cullen, General Health Physics Supervisor

-

  • T. Law, Plant Manager
  • J. Makepeace, Technical Engineering Director W. Monti, Outage Coordinator J. O'Connell, Foreman, Van Nest Shops F. Smith, Superintendent, Van Nest Shops
  • S. Wisla, Chemistry and Radiation Safety Director M. Hensch, Field Supervisor (NUMANC0)
  • J. Bayne, Resident Manager IP 3 (PASNY)
  • J. Kelly, Radiological and Environmental Services Superintendent (PASNY)
  • J. Kilduff, Asst. to Resident Manager (PASNY)

The inspector also interviewed 8 other licensee employees during the course of the inspection.

They included members of the security force engineering staff, health physics staff and maintenance personnel.

  • denotes those present at the exit interview.

2.

Facility Tour The inspector toured the facility on January 26 to verify licensee compliance with 10 CFR 20, Technical Specifications (TS) and procedure requi rements.

Posting and labeling and radiation area control were examined in the combined Unit 1 and 2 controlled area for compliance with 10 CFR 20.203 and procedures developed pursuant to Unit 2 T.S.

6.11 and Unit 1 T.S.

3.2.6.

Independent measurements were made to verify licensee posting.

Personnel working under Radiation Work Permit (RWP) numbers 1020 and 1049 were. observed to verify that they were ccmplying with the conditions of the RWP's.

Contamination control points (step-off pads) were maintained and contamination monitoring devices (portal monitors, hand and foot counters and friskers) were operational, calibrated and the alarms functional.

No items of noncompliance were identified.

I t

l i

_ -.

_ _ _ _ _ _

'

'

.

,

,

.

3.

Procedures The inspector reviewed two refueling maintenance procedures, one for the repair of Crosby valve 855 (part of the safety injection system) and one for steam generator eddy current testing and tube plugging for compliance with the criteria in Regulatory Guide 1.33 and ANSI standard N 18.7-1972.

The steam generator maintenance procedure referenced a temporary Health Physics procedure titled

" Steam Generator Primary Channel Head Work", which was also reviewed.

No items of noncompliance were identified.

4.

Advance Planning and Preparation The inspector reviewed the licensee's contractor entry control point and a modified gate' to control traffic behind the security desk at the current control point.. The contractor control point is capable of controlling traffic flow and preventing the spread of contamination outside the controlled area.

The inspector also reviewed the licensee's supplies and equipment to determine if they were adequate for the increased usage during the outage.

A tour was made of the licensee's Van Nest Shops where the steam generator mockup and other outage related items were located.

The inspector examined the full-scale (including interferences) steam generator mockup for eddy corrent testing and the full scale mockup for the placement of hand-holes and removal of tubes.

The use of these mockups should increase worker skill, greatly reduce exposure and facilitate resolution of difficulties encountered during the the task.

e 5.

Exit Interview The inspector met with licensee representatives (denoted in Paragraph 1) at the conclusion of the inspection on January 26, 1978.

The inspector summarized the scope and findings of the inspection.

.