ENS 48960
ENS Event | |
|---|---|
04:00 Apr 19, 2013 | |
| Title | Part 21 Report - Esi Refurbished Emergency Diesel Generator Cylinder Heads May Have Valve Keeper Seals Missing |
| Event Description | The following information is a summary of a report faxed to the Operations Center from Engine Systems, Inc. (ESI) concerning a condition reportable under 10 CFR 21:
Engine Systems Inc. (ESI) began a 10 CFR 21 evaluation on 02/19/13 following the failure analysis of a cylinder head returned by South Texas Project (STP). The cylinder head had been installed on an emergency diesel generator set at STP and, during routine prestart checks, oil was found leaking from the Kiene valve while barring over the engine. This cylinder head had been previously refurbished in 2004 under ESI's 10 CFR 50 Appendix B program. ESI's investigation revealed that the refurbished cylinder head was returned to the customer without keeper seals installed. The evaluation was concluded on 04/19/13 and it was determined that this issue is a reportable defect as defined by 10 CFR 21. Omission of the keeper seals from the cylinder head of the KSV emergency diesel generator set could allow engine lubricating oil to migrate through the cylinder head and into the combustion chamber during engine standby conditions. Presence of this oil could damage the engine to the point that it is unable to perform its safety related function. ESI began dedicating refurbished cylinder heads in 2001 but the refurbishment scope did not include valve train components. Refurbishments that included valve train components were first shipped in 2003. Procedure steps were included in 2007 to verify valve keepers were installed. Therefore, only cylinder heads refurbished between 2003 and 2007 are affected. A review of purchase orders have determined that the following plants received a total of 26 cylinder heads that may not have valve keeper seals installed: Byron Station - 3 heads South Texas Project - 21 heads Cooper Nuclear Plant - 2 heads Affected cylinder head part numbers are 10-KSV-11-3-RR, 12-KSV-11-3-RR AND 13-KSVR-11-6-RR. ESI will be notifying affected customers. |
| Where | |
|---|---|
| Engine Systems, Inc Rocky Mount, North Carolina (NRC Region 1) | |
| Organization: | Engine Systems, Inc |
| Reporting | |
| 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect | |
| Time - Person (Reporting Time:+108.53 h4.522 days <br />0.646 weeks <br />0.149 months <br />) | |
| Opened: | Tom Horner 16:32 Apr 23, 2013 |
| NRC Officer: | Howie Crouch |
| Last Updated: | Apr 23, 2013 |
| 48960 - NRC Website | |
Engine Systems, Inc with 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect | |
WEEKMONTHYEARENS 581392025-12-10T05:00:00010 December 2025 05:00:00
[Table view]10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - EMD Diesel Generator Cylinder Head Cracking ENS 579882025-08-27T04:00:00027 August 2025 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Power Driven Potentiometer with Loose Relay Sockets ENS 565382023-03-28T04:00:00028 March 2023 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Defect Identified in Emergency Diesel Generator Governor ENS 556052021-11-09T17:00:0009 November 2021 17:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 Report - Hinge Pin Retainer Plug Defective on Diesel Check Valve ENS 555312021-08-20T16:00:00020 August 2021 16:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Pressure Regulator Valve Failure ENS 553472021-05-11T16:00:00011 May 2021 16:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 Initial Report - Deviation Identified Loose Zinc Anodes Installed in Heat Exchangers for Diesel Generators ENS 544672020-01-08T05:00:0008 January 2020 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Inadequate Selenium Surge Suppressor Thread Modification ENS 543502019-09-06T04:00:0006 September 2019 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Emd Fuel Injectors Seized Plunger and Bushing ENS 542362019-08-22T04:00:00022 August 2019 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Cracked Spray Tip on Emd Fuel Injector ENS 537632018-11-30T05:00:00030 November 2018 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect En Revision Imported Date 12/24/2018 ENS 536002018-07-19T04:00:00019 July 2018 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Motor Operated Potentiometer Defect ENS 533022018-02-01T04:00:0001 February 2018 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Refurbished Pressure Regulator May Result in Emergency Diesel Generator Failure to Start ENS 527982017-06-08T04:00:0008 June 2017 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 Report - Defective Motor Operated Potentiometer ENS 524662016-12-21T05:00:00021 December 2016 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Issues Identified with the Enterprise Diesel Engine Subcover ENS 524772016-11-12T05:00:00012 November 2016 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Seizure of Fuel Injector on Emergency Diesel Generator ENS 511292015-06-05T22:12:0005 June 2015 22:12:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Incorrect Part Number Relay Shipped to Brunswick Nuclear Plant ENS 489602013-04-19T04:00:00019 April 2013 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 Report - Esi Refurbished Emergency Diesel Generator Cylinder Heads May Have Valve Keeper Seals Missing ENS 485642012-12-06T05:00:0006 December 2012 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Esi Refurbished Emergency Diesel Generator Cylinder Head with Foreign Material in Intake Port 2025-08-27T04:00:00 | |