05000285/FIN-2015012-03
From kanterella
(Redirected from 5000285/FIN-2015012-03)
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Set Action Levels to Ensure that the Assumptions in the Engineering Analysis Remain Valid |
Description | The inspectors identified a non-cited violation of License Condition 3.D, Fire Protection Program, for the failure to establish an appropriate monitoring program in accordance with National Fire Protection Association Standard 805, Section 2.6. Specifically, the licensee failed to set the action level for the availability of the raw water system pumps to ensure that the assumptions in the engineering analysis remained valid. There was no immediate safety concern since the raw water pumps availability remained above the value assumed in the analysis and the licensee entered this violation into the corrective action program as Condition Report 2015-12612. The failure to set the action level for the availability of the raw water system pumps to ensure that the assumptions in the engineering analysis remained valid was a performance deficiency. The performance deficiency was more than minor because it was associated with the protection against external events (fire) attribute of the Mitigating Systems cornerstone and it adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The inspectors evaluated this finding using Inspection Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process, and determined that the issue was of very low safety significance (Green). This finding had a cross-cutting aspect associated with change management within the human performance area since the leaders failed to use a systematic process for evaluating and implementing change so that nuclear safety remains the overriding priority. Specifically, the inspectors determined that the licensee did not use the process that was in place to ensure that the appropriate fire risk assessment monitoring action levels were incorporated into the maintenance rule program and monitored (H.3). |
Site: | Fort Calhoun |
---|---|
Report | IR 05000285/2015012 Section 1R05 |
Date counted | Dec 31, 2015 (2015Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | D Loveless E Uribe G Werner H Barrett J Mateychick N Okonkwo S Alferink S Galbreath |
Violation of: | License Condition - Fire Protection License Condition |
CCA | H.3, Change Management |
INPO aspect | LA.5 |
' | |