05000528/FIN-2013003-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Prevent Recurrence of a Significant Condition Adverse to Quality |
Description | A self-revealing non-cited violation of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action, occurred because the licensee failed to correct and prevent recurrence of a significant condition adverse to quality associated with the emergency diesel generator automatic voltage regulator circuitry. Specifically, from February 2011 to January 2013, the licensee failed to correct the cause of an induced voltage transient in the automatic voltage regulator circuitry, resulting in the Unit 2 train B diesel generator not reaching rated voltage during a surveillance test. The licensee entered the issue into their corrective action program as CRDR 4329997 and replaced and retested electrical components that could allow a voltage transient on the instantaneous pre-positioning circuit board. The performance deficiency associated with this finding is the failure of the licensee to correct and prevent recurrence of a significant condition adverse to quality. The performance deficiency is more than minor, and therefore a finding, because it is associated with the equipment performance attribute of the Mitigating Systems Cornerstone and affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The senior resident inspector performed the initial significance determination for the train B emergency diesel generator (EDG) failure. The inspector evaluated the significance of the issue under the SDP, as defined in Inspection Manual Chapter 0609.04, Initial Characterization of Findings, and IMC 0609, Appendix A, The Significance Determination Process (SDP) for Findings at-Power. The finding screened to a detailed risk evaluation because it involved a potential loss of one train of safety related equipment for longer than the technical specification allowed outage time. A Region IV senior reactor analyst performed the detailed risk evaluation. The exposure period was 43 days. The change to the CDF was 7.2E-7/year (Green). The finding was not significant to the large early release frequency. The dominant core damage sequences included loss of offsite power events that lead to station blackout conditions. The gas turbine generators, train A emergency diesel generator, and the DC battery life extension to six hours helped to limit the risk. The finding has a cross-cutting aspect in the area of Problem Identification and Resolution associated with the corrective action program component because the licensee failed to thoroughly evaluate problems such that the resolutions address causes and extent of condition, as necessary. |
Site: | Palo Verde |
---|---|
Report | IR 05000528/2013003 Section 4OA2 |
Date counted | Jun 30, 2013 (2013Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | M Brown B Tharakan S Graves D Allen M Baquera D Reinert P Jayroe |
Violation of: | 10 CFR 50 Appendix B Criterion XVI Technical Specification |
CCA | P.2, Evaluation |
INPO aspect | PI.2 |
' | |
Finding - Palo Verde - IR 05000528/2013003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Palo Verde) @ 2013Q2
Self-Identified List (Palo Verde)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||