Finding | |
|---|---|
| Title | Failure to Have Adequate Documentation for Verification of ASME Code Compliance. |
| Description | The inspectors identified a Green noncited violation of 10 CFR Part 50, Appendix B, Criterion VII Control of Purchased Material, Equipment, And Services for the failure of licensee personnel to maintain radiographs onsite for the verification of ASME Code,Section III compliance. Specifically, radiographs for welds associated with the reactor head vent line were neither received nor reviewed as required. When the radiographs were obtained, reviews identified that welds for Units 1 and 2 did not meet the standards of Section III of the ASME Boiler and Pressure Vessel Code. The licensee corrected the non-conforming weld in Unit 2 during refueling outage 2R16 and Unit 1 welds will be restored to Section III standards during the next refueling outage beginning October 1, 2011. The licensee entered the issue into the corrective action program as Condition Report / Disposition Requests 3540575. Inspectors determined that the failure to maintain radiographs onsite for review was a performance deficiency. The performance deficiency was more than minor because it adversely affected the RCS equipment and barrier performance attribute of the Barrier Integrity Cornerstones objective to provide reasonable assurance that physical design barriers protect the public from radionuclide releases caused by accidents or events. Using Inspection Manual Chapter 0609, Attachment 4, Initial Screening and Characterization of Findings, the inspectors concluded that the finding is of very low safety significance (Green) because the reactor coolant system barrier remained intact, was not associated with the fuel barrier, and did not constitute a spent fuel pool issue. This finding had a cross-cutting aspect in the area of human performance associated with the work practices component because the licensee failed to communicate expectations regarding procedural compliance and personnel follow procedures. |
| Site: | Palo Verde |
|---|---|
| Report | IR 05000528/2011003 Section 4OA2 |
| Date counted | Jun 30, 2011 (2011Q2) |
| Type: | NCV: Green |
| cornerstone | Barrier Integrity |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | G Guerra R Lantz M Brown P Elkmann G George J Adams J Bashore M Baquera S Hedger |
| CCA | H.8, Procedure Adherence |
| INPO aspect | WP.4 |
| ' | |
Finding - Palo Verde - IR 05000528/2011003 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Palo Verde) @ 2011Q2
Self-Identified List (Palo Verde)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||