05000416/FIN-2010005-08
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Licensee-Identified Violation |
Description | With one or more fire door(s) being inoperable and with at least one side of the inoperable fire door(s) having verified continuous fire monitoring and alarm capability, Condition 2.C.41 of Grand Gulf Nuclear Power Stations Facility Operating License requires the establishment of an hourly fire watch patrol in accordance with the station fire protection program. Contrary to the above, on September 19, 2010, several inoperable fire doors were not inspected by an hourly fire watch patrol for a period of approximately 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />. This issue was documented in the licensees corrective action program in condition report CR GGN-2010-06824. This finding is of very low safety significance because at least one side of each inoperable fire door had verified continuous fire monitoring and alarm capability. |
Site: | Grand Gulf |
---|---|
Report | IR 05000416/2010005 Section 4OA7 |
Date counted | Dec 31, 2010 (2010Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Licensee-identified |
Inspection Procedure: | |
Inspectors (proximate) | P Elkman G Guerra R Smith D Jones A Barrett T Burns D Overland V Gaddy R Latta J Draper S Hedger B Hagar R Kumana P Prescott D Norwood |
INPO aspect | |
' | |