Finding | |
|---|---|
| Title | Degraded Fire Door Barrier Protecting the Safeguards Switchgear Rooms |
| Description | The inspectors identified a Green noncited violation of Facility Operating License Condition 2.C(41) involving the failure to ensure that fire barriers protecting safety-related areas were functional during monthly fire barrier inspections. The inspectors identified that fire door OC211, crossover door between division 1 and 2 switchgear rooms, was missing 5 screws in the divider overlap and there was a three inch crack in the door on the bottom left side. The Fire Hazards Analysis Report, Section 9A.2.4 defines fire doors as a fire barrier, and Section 9A.5.7 and 9A.5.8, Fire Area 7 and Fire Area 8, respectively, describe the electrical switchgear rooms as having 3-hour fire rated barriers. Operations initiated an hourly fire watch for the non-functional door per the technical requirements manual. The licensee entered this issue into their corrective action program as Condition Report CR-GGN-2010-05541. The finding was more than minor since it was associated with the protection against external factors attribute of the reactor safety Mitigating Systems (MS) Cornerstone, and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Using Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process, the inspectors determined that the finding impacted the fire confinement category. The inspectors assigned a low degradation rating because the cracks did not create an actual hole through the door. The inspectors concluded that the finding was of very low safety significance (Green) because the degraded barrier was expected to maintain nearly the same level of effectiveness and reliability had the degradation not been present, and there were no fire ignition sources or combustible materials in the area that would subject the barrier to direct flame impingement. The cause of this finding has a crosscutting aspect in the area of human performance associated with resources, because plant personnel failed to adequately evaluate and provide proper maintenance for degrading fire doors. |
| Site: | Grand Gulf |
|---|---|
| Report | IR 05000416/2010004 Section 1R05 |
| Date counted | Sep 30, 2010 (2010Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | C Graves D Stearns R Smith A Barrett V Gaddy |
| CCA | H.1, Resources |
| INPO aspect | LA.1 |
| ' | |
Finding - Grand Gulf - IR 05000416/2010004 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Grand Gulf) @ 2010Q3
Self-Identified List (Grand Gulf)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||