| Title | Licensee-Identified Violation |
| Description | Grand Gulf Nuclear Power Stations fire protection program requires control of transient combustible materials in the plant. Contrary to the above, between May 5 and May 11, 2010, plant personnel failed to maintain control of transient combustible materials in accordance with the fire protection program. Specifically, the licensee identified several improperly controlled items in combustible control zones (transient combustible exclusion areas) on the 166 foot, 139 foot, and 119 foot elevations of the auxiliary building. Items included: plastic signs on the 166 foot elevation; yellow gloves on the 139 foot elevation; a rolling work bench with combustible items on top, as well as various loose plastic and paper items in the area, a hand cart on the 119 foot elevation; and, other various transient combustibles stored outside approved combustible storage areas without transient combustible evaluation permits.
These issues were entered into the corrective action program as Condition Reports CR-GGN-2010-03232, CR-GGN-2010-03330, CR-GGN-2010-03601, CR-GGN-2010-03604, CR-GGN-2010-03147, CR-GGN-2010-03151, CR-GGN-2010-03783, and CR-GGN-2010-03822. Corrective actions for these issues included removing the materials from the combustible exclusion zones, providing additional oversight of the transient combustibles control program, and reinforcing the requirements of a transient combustible exclusion zone with the workers. This finding is of very low safety significance because although it violated the licensees program for the control of transient combustibles in an exclusion zones, it was determined to be of low degradation due to the amount of material found in the areas was negligible. |
| Site: | Grand Gulf |
|---|---|
| Report | IR 05000416/2010003 Section 4OA7 |
| Date counted | Jun 30, 2010 (2010Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Licensee-identified |
| Inspection Procedure: | |
| Inspectors (proximate) | L Ricketson P Elkmann D Stearns R Smith A Barrett V Gaddy N Hernandez B Hagar R Kumana M Williams |
| INPO aspect | |
| ' | |
Finding - Grand Gulf - IR 05000416/2010003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Grand Gulf) @ 2010Q2