05000416/FIN-2010002-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Restore Control Room Air Conditioning Subsystem B to Operable Status Within the Required Time of 30 days |
Description | The inspectors reviewed a self-revealing non-cited violation of Technical Specification 3.7.4 for failing to restore control room air conditioning subsystem B to operable status within the required time of 30 days. Specifically, between March 28, 2009 and June 25, 2009, the control room air conditioner subsystem B was inoperable due to the compressor capacity controller being set incorrectly. The deficiency initially revealed itself on May 14, 2009, when the air conditioner was unable to keep up with demand. The licensee entered this issue into the corrective action program as Condition Report CR-GGN-2009-3779. This finding is more than minor since it affects because it was associated with the equipment performance attribute of the mitigating systems cornerstone, and it adversely affected the cornerstone objective of ensuring the availability, reliability and capability of safety related equipment. Using Manual Chapter 0609, Significance Determination Process, Phase 1 Worksheet, the finding was determined to be of very low safety significance (Green) because it was not a design or qualification deficiency confirmed not to result in loss of operability or functionality, it does not represent an actual loss of a system safety function, it does not represent the actual loss of safety function of a single train for greater than its technical specification allowed outage time, it does not represent an actual loss of safety function of one or more non-technical specification of equipment designated as risk-significant per 10 CFR 50.65 for greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and it does not screen as potentially risk significant due to a seismic, flooding, or severe weather initiating event. The cause of this finding has a crosscutting aspect in the area of human performance associated with decision making in that the operators did not utilize conservative assumptions to determine system operabilit |
Site: | Grand Gulf |
---|---|
Report | IR 05000416/2010002 Section 1R07 |
Date counted | Mar 31, 2010 (2010Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.07 |
Inspectors (proximate) | G Guerra R Smith A Barrett W Sifre M Young V Gaddy B Rice |
CCA | H.14, Conservative Bias |
INPO aspect | DM.2 |
' | |
Finding - Grand Gulf - IR 05000416/2010002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Grand Gulf) @ 2010Q1
Self-Identified List (Grand Gulf)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||