SUBJECT:
LER 93-030-02:on 931028,found seven locations where electrical raceway cable tray cover deficiencies were found.
Caused by inadequate management methods. Establishing fire tour of affected areas.W/940819 ltr.
DISTRIBUTION CODE: IE22T COPIES RECEIVED:LTR 0 ENCL j SIZE: 7 TITLE: 50.73/50.9 Licensee Event Report (LER),incident Rpt, etc.,
NOTES:
RECIPIENT ID CODE/NAME PD4-2 PD INTERNAL: ACRS AEOD/SPD/RRAB NRR/DE/EMEB NRR/DRCH/HHFB NRR/DRCH/HOLB NRR/DSSA/SPLB NRR/PMAS/IRCB-E RES/DSIR/EIB EXTERNAL: EG&G BRYCE,J.H NOAC MURPHY,G.A NRC PDR COPIES LTTR ENCL 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 2
2 1
1 1
1 RECIPIENT ID CODE/NAME CLIFFORD,J AEOD/ROAB/DSP NRR/DE/EELB NRR/DORS/OEAB NRR/DRCH/HICB NRR/DRSS/PRPB NRR/J)SSR/SRXB EG FILE~
02 RGN4 FILE 01 L ST LOBBY WARD NOAC POOREFW NUDOCS FULL TXT COPIES LTTR ENCL 1
1 2
2 1
1 1
1 1
1 2
2 1
1 1
1 1
1 1
1 1
1 1
1 NOTE TO ALL"RIDS" RECIPIENTS:
PLEASE HELP US TO REDUCE iVASTEICONTACTTHE DOCUMENTCONTROL DESK, ROOM Pl-37 (EXT. 504-2083 ) TO ELIMINATEYOUR VAMEFROM DISTRIBUTIONLISTS I OR DOCUMEVTS YOU DON"I'EED!
FULL TEXT CONVERSION REQUIRED TOTAL NUMBER OF COPIES REQUIRED:
LTTR 27 ENCL 27
WASHINGTON PUBLIC POKER SUPPLY SYSTEM P.O. Box 968
~
3000 George 11'ashingion 11'ay
~ Richland, 1Vashington 99352 August 19, 1994 G02-94-199 Docket No. 50-397 Document Consol Desk U,S. Nuclear Regulatory Commission Washington, D.C.
20555
Subject:
NUCLEAR PLANT WNP-2, OPERATING LICENSE NPF-21 LICENSEE EVENT REPORT NO.93-030, REVISION 2 Transmitted herewith is Revision 2 to Licensee Event Report (LER) No.93-030 for WNP-2.
This report is s'ubmitted in response to the report requirements of 10CFR50.73 and discusses the items of reportability, corrective action taken, and action taken to preclude recurrence.
The original LER reported the discovery of missing electrical power raceway cable tray covers during walkdowns originally undertaken to identify the installation locations of noncredited Thermolag fire barriers.
Walkdowns of accessible areas were approximately 50% complete when the LER was issued.
Revision 1 to the LER described additional cable tray deficiencies identified during the walkdown of accessible areas completed on January 25, 1994.
The remaining accessible areas were walked down prior to plant shutdown for the 1994 (R-9) Refueling Outage.
Areas that were inaccessible during plant operation due to high radiation were walked down during the R-9 outage.
This revision describes the cable tray deficiencies identified throughout the electrical power raceway walkdown project and satisfies the supplemental reporting commitment of Revision 1.
No further revisions to this LER are expected.
. Parrish (Mail-Drop 1023)
Assistant Managing Director, Operations JVP/CDM Enclosure cc:
LJ Callan, NRC-RIV KE Perkins, Jr., NRC-RIV, Walnut Creek Field Office NS Reynolds, Winston & Strawn NRC Sr. Resident Inspector (Mail Drop 927N, 2 Copies)
INPO Records Center - Atlanta, GA Mr. D. L. Williams, BPA (Mail Drop 399)
AGILITY NAME (I)
LICENSEE EVEh+IEPORT (LER)
Mashin ton Nuclear Plant - Unit 2 OOCKET NUMB R
(
)
PAGE (3) 0 5
0 0
0 3
9 7
I DF ITLE (4)
MISSING CABLE TRAY COVERS DISCOVERED DURING THE ELECTRICALPOWER RACEWAYWALKDOWN EVENT DATE (5)
LER NUHBER 6
REPORT DATE (7 OTHER FACILITIES INVOLVED (8 HONTH I
0 DAY YEAR 2
6 9
3 YEAR 9
3 SEQUENTIAL NUHBER 0
3 0
EVI5 ION UMBER 0
2 HONTH 0
6 DAY 1
9 9
4 FACILITY NAMES CKE 0 5 0 050 NUHB R (5)
PERATING ODE (9)
HIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREHENTS OF 10 CFR 5:
(Check one or more of the following) (11 1
OWER LEVEL (10) 20.402(b) 20.405(a)(1)(i) 20.405(a)(1)(ii) 20.405(a)(1)(iii) 0.405(a)(1)(iv) 20.405(a)(1)(v) 20.405(C) 50.36(c)(1) 50.36(c)(2) 50.73(a)(2)(i)
X 50.73(a)(2)(ii) 50.73(a)(2)(iii) 50.73(a)(2)(iv) 50.73(a)(2)(v)
- - 50.73(a)(2)(vii) 50.73(a)(2)(viii)(A) 50.73(a)(2)(viii)(B) 50.73(a)(2)(x) 77.71(b) 73.73(c)
THER (Specify in Abstract elow and in Text, NRC orm 366A)
LICENSEE CONTACT FOR THIS LER 12)
C.
D. Mackaman, Licensing Engineer TELEPHONE NUMBER REA CODE 5
0 9
7 7
4 4
5 1
COMPLETE ONE LINE FOR EACH COMPONENT FAILURE DESCRIBED IN THIS REPORT (13)
CAUSE
SYSTEH COHPONENT MANUFACTURER EPDRTABLE 0 NPRDS
CAUSE
SYSTEH COHPONENT HANUFACTURER REPORTABLE TO NPRDS SUPPLEMENTAL REPORT EXPECTED (14)
YES (If yes, complete EXPECTED SUBMISSION DATE)
X NO EXPECTED SUBMISSION MONTH DAY YEAR ATE (15)
On October 28, 1993, with WNP-2 in Mode 1 (Power Operations) at 100% power, the Supply System found seven locations where electrical raceway cable tray covers were not installed in accordance with electrical separation design criteria.
These cable tray cover deficiencies were found during electrical power raceway walkdowns being conducted to identify noncredited Thermolag installations.
At the conclusion of the walkdowns on June 23, 1994, a total of 166 locations were found with missing cable tray covers or other deficiencies, such as gaps or holes in the cable tray covers.
Cable tray covers provide physical independence of redundant safety-related circuits, The absence of these covers violates WNP-2 electrical separation design criteria. A failure induced fire in an open power cable tray could produce faults in nearby safety-related electrical cables, resulting in a loss of a redundant safety function.
The cause of this event was inadequate management methods to identify and resolve cable tray and conduit electrical separation problems.
Corrective actions included:
establishing fire tours of afFected areas, correcting cable tray deficiencies, incorporating as-built information into the design data base, developing methods for design configuration control and feedback of as-built information into the design data base, training of plant personnel, and review and walkdown of a sample of recent plant design changes to verify that electrical separation related mistakes are not recurring.
'LICENSEE EVENT REPORT (OI)
TEXT CONTINUATION FACILITY NAME (I)
Washington Nuclear Plant
- - Unit 2 DOCKET NUMBER (2) 0 5
0 0
0 3
9 7
Year LER NUMBER (8)
Number ev.
No.
PAGE (3) 3 030 02 2
OF 6
TITLE (4)
HISSING CABLE TRAY COVERS DISCOVERED DURING THE ELECTRICAL POWER RACEWAY WALKDOWN Event Descri ti n On October 28, 1993, with WNP-2 in Mode 1 (Power Operations) at 100% power, the Supply System found seven locations where electrical raceway cable tray covers were not installed in accordance with electrical separation design criteria.
These cable tray cover deficiencies were found during walkdowns of electrical power raceways being conducted as part of the commitments made in response to the Inspection Report (IR) 93-13 potential generic concern that noncredited Thermolag installations were not included in the cable ampacity derating evaluation performed for NRC Generic Letter 92-08.
The Thermolag walkdown scope included verification of metal cable tray cover locations because the cable tray covers are used as electrical separation barriers.
At the conclusion of the walkdowns on June 23, 1994, a total of 166 locations were found with missing cable tray covers or other deficiencies, such as gaps or holes in the cable tray covers.
Cable tray covers are used to ensure physical independence of redundant safety-related circuits in accordance with WNP-2 Plant Specification 200, Section 201, Page 185.
The failure to fully implement this electrical separation design criteria could impact safety-related equipment function.
In the event of a single failure induced fire in the open power cable trays, faults could be produced in redundant safety-related electrical cables (circuits) that are routed in nearby (intruding) cable trays or conduit.
The safety-related cable faults could result in a loss of the redundant safety function, Immediate rrective Ac ions Immediate corrective actions were taken to:
1.
Establish hourly fire tours of the areas where cable tray covers were missing to enhance the ability to detect a fire and mitigate the probable effects of a fire.
2.
Correct the cable tray cover deficiencies.
All field work to correct the deficiencies has been completed.
Further Eval ti n and orrective Action F
herE 1
ion 1.
In accordance with 10CFR50.72(b)(1)(ii)(B), the first seven identified locations of electrical separation design criteria nonconformance were reported to the NRC Operations Center.
The report was made via the Emergency Notification System (ENS) on October 28, 1993, at 1130 hours0.0131 days <br />0.314 hours <br />0.00187 weeks <br />4.29965e-4 months <br /> (PDI')
as "Any event or condition during operation...
that results in the nuclear power plant being
... [i]n a condition that is outside the design basis of the plant,"
'LICENSEE EVENT REPORT (Il)
TEXT CONTINUATION ACILITY NAME (I)
Washington Nuclear Plant - Unit 2 I
DOCKET NUMBER (2) 0 5
0 0
0 3
9 7
LER NUMBER (8) ear umber ev.
No.
3 030 02 PAGE (3) 3 OF 6
ITLE (4)
MISSING CABLE TRAY COVERS DISCOVERED DURING THE ELECTRICAL POWER RACEWAY WALKDOWN 1
The initial report was updated via the ENS on November 1, 1993, at 1623 hours0.0188 days <br />0.451 hours <br />0.00268 weeks <br />6.175515e-4 months <br /> (PST) when six additional locations of nonconformance with the electrical separation design criteria were found.
2.
This event is being reported pursuant to 10CFR50.73(a)(2)(ii)(B) as "Any event or condition...
that resulted in the nuclear power plant.being... [i]n a condition that was outside the design basis of the plant..."
prior to the recently completed walkdowns, three separate cable tray separation walkdowns had been conducted since original plant construction to identify and address potential electrical conduit and
'raceway separation problems.
In 1983, a walkdown was conducted to address nonconforming cable tray to conduit configurations identified by the NRC Construction Assessment Team (CAT). The CAT item was closed by the NRC in 1984.
The full scope of the areas inspected during the walkdown cannot be determined because only deficiencies were documented.
In 1985, a walkdown of all cable trays was conducted to address potential electrical separation deficiencies identified by the Resident NRC Inspector (LER 85-023).
The last of the deficiencies identified during the walkdown was corrected in 1988.
In 1990, cable tray walkdowns were conducted to verify electrical separation barriers (including covers) for cable trays.
Although these walkdowns were intended to include the entire plant, the documentation from the walkdowns indicates that all areas were not evaluated.
4.
There was evidence that some of the conduit and cable tray separation deficiencies identified during the recent walkdowns resulted from work activities performed after construction (e,g,,
BDC 86-0306-OA).
However, in most cases, there was insufiicient information to determine ifthe deficiencies were missed by the previous walkdowns or were created by post-startup work activities.
5.
ZMning had.not been adequate to assure consistent-compliance with plant electrical separation criteria.
Although Plant 'Ibchnical engineers and field engineers were authorized to perform electrical separation evaluations, there had not been continued electrical separation training provided for them since initial plant startup.
In addition, a Quality Assurance audit conducted in response to LER 85-023 determined that Quality Control (QC) inspectors were'not adequately trained to inspect for conformance to plant electrical separation criteria.
Periodic training on the plant electrical separation criteria has been provided to design engineers.
~
'LICENSEE EVENT REPORT (lQ)
TEXT CONTINUATION FACILITY NANE (I)
Washington Nuclear Plant
- - Unit 2 DOCKET NUMBER (2) 0 5
0 0
0 3
9 7
fear LER NUNBER (B)
Number ev.
No.
3 030 02 PAGE (3) 4 OF 6
TITLE (4)
HISSING CABLE TRAY COVERS DISCOVERED DURING THE ELECTRICAL POWER RACEWAY WALKDOWN 6.
Before 1985, electrical separation criteria were not included in plant procedures related to electrical raceway and cable installation.
These procedures were revised in 1985 to include some separation criteria information in response to LER 85-023.
However, Plant Procedure Manual (PPM) maintenance procedures 10.25,54, "Cable Pulling," and 10.25.57, "Raceway Installation," were not adequately revised to assure that electrical separation was maintained.
7.
The Supply System has recently initiated significant senior management changes to improve previously identified weaknesses in management methods.
One area that was identified in the 1993 Systematic Assessment of Licensee Performance (SALP) Report was the Supply System's inadequate and ineffective corrective actions.
The new management have clearly expressed their expectation that problems are to be corrected to properly resolve the immediate concern and also to prevent recurrence.
Management has reemphasized a commitment to identify and then effectively complete all corrective actions prior to the scheduled date.
A corrective action backlog reduction plan has been implemented to track corrective actions and facilitate closure of the actions.
Management has also included specific goals for quality and timeliness of corrective actions in supervisory personnel performance plans.
These actions, which were committed to in the SALP response, should reduce the chance of recurrence of this'problem.
Unlike the previous electrical raceway walkdowns, the recently completed walkdown had trained dedicated personnel with specific inspection criteria and identified scope.
The scope addressed by these walkdowns included applicable plant areas and had been established using plant drawings and as-built tray cover information.
The as-built information had been reverified through specific spot inspections and visual walkdowns.
Senior management had been involved in oversight of the recent walkdown effort by allocating budget and manpower, and establishing project management oversight.
The Supply System believes that these changes in management methods, in conjunction with the following further corrective actions, willcorrect the long standing cable tray and conduit electrical separation problems at WNP-2.
8.
PPM maintenance procedures 10.25.54 and 10.25.57 have been changed to assure that only personnel trained on the WNP-2 electrical separation criteria perform electrical separation evaluations.
WR~uua The root cause for this event was inadequate management methods to fullyidentify and resolve cable tray and conduit electrical separation problems.
Planning and coordination of previous walkdown work activities, control of documentation, training, communication between organizations, and monitoring and assessment of corrective actions had been less than adequate.
LICENSEE EVENT REPORT ()
TEXT CONTINUATION FACILITY NAHE
~(I)
Washington Nuclear Plant
- - Unit 2 OOCKET NUHBER (2) 0 5
0 0
0 3
9 7
LER NUHBER (8)
Year Number ev.
No.
3 030 02 PAGE (3) 5 OF 6
ITLE (4)
HISSING CABLE TRAY COVERS DISCOVERED DURING THE ELECTRICAL POWER RACEWAY WALKDOWN Three contributing causes were identified:
1.
Weaknesses in as-built information in the design data base.
2.
Weaknesses in configuration control methodology and procedures to feedback complete as-built information to Design Engineering.
3.
Reliance on untrained Plant Technical engineers, field engineers, and QC inspectors for conformance to electrical separation criteria.
Fu her orrective Action 1.
The electrical power raceway walkdown project and associated activities were completed, assuring that the deficiencies were properly documented, evaluated, and corrected.
As-built information was submitted to Design Engineering on June 24, 1994.
2.
The as-built information collected during the walkdowns willbe incorporated into the design data base by December 31, 1994.
Cable ampacity calculations have been completed for as-built raceway configurations and include ampacity derating for non-credited Thermolag installations where applicable.
3.
Plant Technical coordinated with Design Engineering and other appropriate departments to develop and implement programmatic methods for electrical separation design configuration control during maintenance and modification activities and as-built information feedback to assure design data base accuracy.
4.
Appropriate plant personnel were trained on the changes to PPM maintenance procedures 10.25.54 and 10.25.57 to assure understanding that only personnel trained on the WNP-2 electrical separation criteria are to perform electrical separation evaluations.
5.
A sample of plant design changes (BDCs) from the last two refueling outages, that could introduce electrical separation deficiencies, were reviewed and walked down by engineering personnel trained on the electrical separation criteria to verify that electrical separation related mistakes reported in past LERs were not recurring, For the six BDCs reviewed, no electrical separation deficiencies were found.
SSfSi lfi Identified electrical separation deficiencies are likely to have no safety significance.
Some of the identified conduits requiring protection may only contain circuits with no safety function.
Those circuits within the identified conduits that do have safety functions are not likely to be functionally redundant to those in the redundant division open cable tray.
However, to verify this requires considerable evaluation and the Supply System had concluded that installing the missing cable tray covers was more cost effective.
'iCENSEE EVENT REPORT (+I)
TEXT CONTINUATION FACILITY NAME (I)
Washington Nuclear Plant - Unit 2 OOCKET NUMBER (2) 0 5
0 0
0 3
9 7
LER NUMBER (8)
Year Nuiiiber ev.'o.
3 030 02 PAGE (3)
'6 OF 6
ITLE (4)
HISSING CABLE TRAY COVERS DISCOVERED DURING THE ELECTRICAL POWER RACEWAY WALKDOWN The purpose of the electrical separation criteria is to ensure that a single failure induced, localized cable raceway or enclosure fire does not result in the loss of redundant safety functions.
A localized raceway fire resulting from a single failure is extremely unlikely.
However, assuming one did occur, the identified separation deficiencies may affect safety-related functions and may result in a degradation of the ability to mitigate the effects of a Design Basis Accident (DBA).
The Supply System believes that there was minimal safety significance associated with the individual electrical separation deficiencies based on the low probability of occurrence.
However, the Supply System also believes that there was potentially collective safety significance in view of the large number of deficiencies identified and the extended period of time the deficiencies may have existed.
Simil r Event II
.LER 85-023, "10CFR50 Appendix 'R'able Fire Protection and Electrical Separation," reported, in part, inadequate electrical separation between raceways carrying "prime" circuits (nonsafety-related circuits connected to a safety-related power supply) due to missing or improperly installed cable tray covers.
LERs91-010, 92-021, and 92-031 reported deficiencies associated with electrical separation but the deficiencies did not involve cable trays or conduit.
Allof the above similar events involved electrical separation design and installation problems that occurred during original plant construction.
However, except for originating during construction, the circumstances surrounding these past events appear unrelated.
As a result, these events were previously believed. to be random instances of electrical separation criteria nonconformance and not amenable to general corrective action.
Of the four events, only LER 85-023 could be viewed as a possible precursor to this event.
The LER identified a similar condition where cable tray covers were missing between redundant Class 1E conduits and open Non-Class 1E cable trays which traverse across them.
The review of plant design changes from the last two refueling outages for "Further Corrective Action" No. 5, above, found no electrical separation related mistakes.
II Inf rm ti n T~RR
$ggem Q~m~nen Cable Raceway System Cable Cable 'I?ay Conduit FA CBL TY CND
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000397/LER-1993-001, :on 930213,determined That Both Trains of SPC of RHR System Were Inoperable Due to LOP Coincident W/Lpci Safety Function.Reviews & Safety Evaluations Has Been Enhanced |
- on 930213,determined That Both Trains of SPC of RHR System Were Inoperable Due to LOP Coincident W/Lpci Safety Function.Reviews & Safety Evaluations Has Been Enhanced
| 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-001-01, :on 930310,determined That Previously Performed Surveillance Testing Had Not Been Fully Adequate to Demonstrate Operability of Hoists.Caused by Error by Nonlicensed Util Personnel.Calibration Revised |
- on 930310,determined That Previously Performed Surveillance Testing Had Not Been Fully Adequate to Demonstrate Operability of Hoists.Caused by Error by Nonlicensed Util Personnel.Calibration Revised
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-002, :on 930121,low RPV Level Reactor Scram Initiated by RPS in Response to Low Water Level Condition. Caused by Inadvertent Actuation of Deluge Sys.Plant Procedure PPM 8.3.120 Will Be Revised |
- on 930121,low RPV Level Reactor Scram Initiated by RPS in Response to Low Water Level Condition. Caused by Inadvertent Actuation of Deluge Sys.Plant Procedure PPM 8.3.120 Will Be Revised
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-003, :on 930121,determined That Under Certain Ac Electrical Distribution Sys Alignments,Fault Could Result in Unavailability of Both Offsite Power Sources.Caused by Inadequate Sys Analysis.Delay Times Revised |
- on 930121,determined That Under Certain Ac Electrical Distribution Sys Alignments,Fault Could Result in Unavailability of Both Offsite Power Sources.Caused by Inadequate Sys Analysis.Delay Times Revised
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-004, :on 930127,determined That Two Inadequately Installed Fuses Could Have Caused Loss of RHR Capability During Seismic Event.Caused by Improper Installation of Fuses.Fuse Deficiencies Will Be Evaluated |
- on 930127,determined That Two Inadequately Installed Fuses Could Have Caused Loss of RHR Capability During Seismic Event.Caused by Improper Installation of Fuses.Fuse Deficiencies Will Be Evaluated
| 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-005, :on 930202,inadequate Documentation & Review of Operability Status Results in Unavailability of Wetwell Purge Exhaust Valve.Caused by Technical Inadequacies.Wetwell Valves Adjusted & Returned to Operable Status |
- on 930202,inadequate Documentation & Review of Operability Status Results in Unavailability of Wetwell Purge Exhaust Valve.Caused by Technical Inadequacies.Wetwell Valves Adjusted & Returned to Operable Status
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-006, :on 930206,manual Reactor Scram Initiated Due to Reactor Recirculation Pump Trip While Operating in Area of Increased Awareness.Caused by Component Design Not within Parameter Limits.Procedures Changed |
- on 930206,manual Reactor Scram Initiated Due to Reactor Recirculation Pump Trip While Operating in Area of Increased Awareness.Caused by Component Design Not within Parameter Limits.Procedures Changed
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-007, :on 930210,low RPV Level Reactor Scram Initiated by RPS in Response to Actual Low Water Level Condition.Caused by Connector Pin Corrosion.Suppression Pool Level Lowered |
- on 930210,low RPV Level Reactor Scram Initiated by RPS in Response to Actual Low Water Level Condition.Caused by Connector Pin Corrosion.Suppression Pool Level Lowered
| 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(1) | | 05000397/LER-1993-008, :on 930211,determined That Logic Sys Functional Test Requirements for Emergency Bus Undervoltage Logic Not Fully Implemented.Caused by Inadequate Procedures.New Procedures Developed |
- on 930211,determined That Logic Sys Functional Test Requirements for Emergency Bus Undervoltage Logic Not Fully Implemented.Caused by Inadequate Procedures.New Procedures Developed
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition | | 05000397/LER-1993-009, :on 930217,existence of Noncondensible Gases in Reference Leg of RPV Instrumentation Due to Design Deficiency.Procedures Developed & Revised & Evaluation Performed |
- on 930217,existence of Noncondensible Gases in Reference Leg of RPV Instrumentation Due to Design Deficiency.Procedures Developed & Revised & Evaluation Performed
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-010, :on 940304,24 Reportable Problems Identified by Failure of Procedures to Fully Implement.Cause Was Less than Adequate Barrier & Controls for Program Changes.Corrective Actions Include Procedure & TS Changes |
- on 940304,24 Reportable Problems Identified by Failure of Procedures to Fully Implement.Cause Was Less than Adequate Barrier & Controls for Program Changes.Corrective Actions Include Procedure & TS Changes
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(iii) | | 05000397/LER-1993-010-07, Forwards LER 93-010-07 Re Two Addl Reportable Findings of TS Surveillance Improvement Project.Rept Provides Updated Status of Corrective Actions | Forwards LER 93-010-07 Re Two Addl Reportable Findings of TS Surveillance Improvement Project.Rept Provides Updated Status of Corrective Actions | | | 05000397/LER-1993-010-01, Forwards LER 93-010-01,discussing Items of Reportability, Corrective Action Taken & Action Taken to Preclude Recurrence | Forwards LER 93-010-01,discussing Items of Reportability, Corrective Action Taken & Action Taken to Preclude Recurrence | | | 05000397/LER-1993-011, :on 930310 & 0409,determined That Previously Performed Surveillance Testing Did Not Demonstrate Operability of Hoists Associated W/Refueling Platform.Caused by Personnel Error.Listed Procedures Changed |
- on 930310 & 0409,determined That Previously Performed Surveillance Testing Did Not Demonstrate Operability of Hoists Associated W/Refueling Platform.Caused by Personnel Error.Listed Procedures Changed
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-011-01, Forwards LER 93-011-01,discussing Items of Reportability, Corrective Action Taken & Action to Preclude Recurrence | Forwards LER 93-011-01,discussing Items of Reportability, Corrective Action Taken & Action to Preclude Recurrence | | | 05000397/LER-1993-012, :on 930311,Sys Engineer Learned That Fast Open Function of Main Turbine BPV Was Not Operable.Caused by Less than Adequate Surveillance Procedures.No Immediate Corrective Actions Were Required |
- on 930311,Sys Engineer Learned That Fast Open Function of Main Turbine BPV Was Not Operable.Caused by Less than Adequate Surveillance Procedures.No Immediate Corrective Actions Were Required
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-013-01, Forwards LER 93-013-01,discussing Items of Reportability, Corrective Action Taken & Action Taken to Preclude Recurrence | Forwards LER 93-013-01,discussing Items of Reportability, Corrective Action Taken & Action Taken to Preclude Recurrence | | | 05000397/LER-1993-013, :on 930318 & 0412,design Errors Noted in Component Safety Classification & Design Requirements Document Programs for RCIC Primary Containment Release path.RCIC-V-31 Closed & motor-operator Deenergized |
- on 930318 & 0412,design Errors Noted in Component Safety Classification & Design Requirements Document Programs for RCIC Primary Containment Release path.RCIC-V-31 Closed & motor-operator Deenergized
| 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-014, :on 930803,discovered Inadequate Backup Overcurrent Protection for Containment Penetrations Due to Inadequate Design Analysis Using Inaccurate & Incomplete Documentation.Changed Plant Procedure |
- on 930803,discovered Inadequate Backup Overcurrent Protection for Containment Penetrations Due to Inadequate Design Analysis Using Inaccurate & Incomplete Documentation.Changed Plant Procedure
| 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-015, :on 930331,unusual Event Declared as Result of Inoperability of HPCS Sys from Low Svc Water Flow Through HPCS Pump Room Cooler,Coincident w/930318 Inoperability of Rcic.Caused by Component Defect.Flow Revised |
- on 930331,unusual Event Declared as Result of Inoperability of HPCS Sys from Low Svc Water Flow Through HPCS Pump Room Cooler,Coincident w/930318 Inoperability of Rcic.Caused by Component Defect.Flow Revised
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-016, :on 930331,containment Atmosphere Control Sys Primary Containment Isolation Valves Discovered Open, Resulting in Exceeding Leakage Limits.Caused by Less than Adequate Procedures.Valves Closed by Removing Jumper |
- on 930331,containment Atmosphere Control Sys Primary Containment Isolation Valves Discovered Open, Resulting in Exceeding Leakage Limits.Caused by Less than Adequate Procedures.Valves Closed by Removing Jumper
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) | | 05000397/LER-1993-017, :on 930426,discovered That Fire Damper Seismic Qualification Concerns Identified in 1985 Through 1987,but Not Reported.Caused by Failure to Include Fire Dampers on safety-related Mechanical List.No C/A Required |
- on 930426,discovered That Fire Damper Seismic Qualification Concerns Identified in 1985 Through 1987,but Not Reported.Caused by Failure to Include Fire Dampers on safety-related Mechanical List.No C/A Required
| 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-018, :on 930428,discovered Design Condition That Could Have Impacted Plants Ability to Mitigate Accident Conditions.Caused by Less than Adequate Change Mgt.Abnormal Operating Procedures Will Be Revised |
- on 930428,discovered Design Condition That Could Have Impacted Plants Ability to Mitigate Accident Conditions.Caused by Less than Adequate Change Mgt.Abnormal Operating Procedures Will Be Revised
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(8) | | 05000397/LER-1993-019, :on 930510,ESF Isolations & Actuations Occurred Due to 500 Kv Load Break Disconnect Failure. RHR Loop a Shutdown Cooling Restored & Plant Sys Returned to Normal Lineup Status |
- on 930510,ESF Isolations & Actuations Occurred Due to 500 Kv Load Break Disconnect Failure. RHR Loop a Shutdown Cooling Restored & Plant Sys Returned to Normal Lineup Status
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-020, :on 930511,MSRV Position Indicators Not Tested Per TS Requirements Due to Poor Procedures,Inconsistency of Three Specs Re MSRVs & TS 3/4.3.7.5 for MSRV Acoustic Monitors Not Met at Required Times |
- on 930511,MSRV Position Indicators Not Tested Per TS Requirements Due to Poor Procedures,Inconsistency of Three Specs Re MSRVs & TS 3/4.3.7.5 for MSRV Acoustic Monitors Not Met at Required Times
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-021, :on 930514,discovered Potential for Water Accumulation in CAC Sys.Due to Inadequate Original Analysis of Sys Design.Drains Installed in Lowest Elevations of CAC Sys Piping |
- on 930514,discovered Potential for Water Accumulation in CAC Sys.Due to Inadequate Original Analysis of Sys Design.Drains Installed in Lowest Elevations of CAC Sys Piping
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-022, :on 930524,two Control Rod Withdrawal Events Were Identified as Having Violated Ts.Caused by Control Rod Maintenance & Testing Not Sufficient.Sys to Improve HCU & Control Rod Implemented |
- on 930524,two Control Rod Withdrawal Events Were Identified as Having Violated Ts.Caused by Control Rod Maintenance & Testing Not Sufficient.Sys to Improve HCU & Control Rod Implemented
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-023, :on 930605,concluded That Flexible Conduit Associated W/Pressure Switches Not Seismically Supported. Caused by Improper Construction Instructions.Walkdown of Quality Class I Racks Performed |
- on 930605,concluded That Flexible Conduit Associated W/Pressure Switches Not Seismically Supported. Caused by Improper Construction Instructions.Walkdown of Quality Class I Racks Performed
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-024, :on 930615,ESG Actuation of Containment Instrument Air Backup Nitrogen Bottle Programmer Occurred. Caused by Personnel Error & Procedure Deficiency.Test Procedures to Be Strengthened |
- on 930615,ESG Actuation of Containment Instrument Air Backup Nitrogen Bottle Programmer Occurred. Caused by Personnel Error & Procedure Deficiency.Test Procedures to Be Strengthened
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-025, :on 930615,Group 1 Nuclear Steam Supply Shutoff Sys Isolation Occurred During Performance of TS Surveillance Test on Turbine Throttle Valves.Caused by Procedure Deficiency.Procedure Changed |
- on 930615,Group 1 Nuclear Steam Supply Shutoff Sys Isolation Occurred During Performance of TS Surveillance Test on Turbine Throttle Valves.Caused by Procedure Deficiency.Procedure Changed
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-026, :on 930619,failed to Complete Weekly Battery Surveillance Requirements within Allowed TS Interval Due to Scheduling Oversight.Initiated & Completed PPM 7.4.8.2.1.20 |
- on 930619,failed to Complete Weekly Battery Surveillance Requirements within Allowed TS Interval Due to Scheduling Oversight.Initiated & Completed PPM 7.4.8.2.1.20
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-027, Primary Coolant Steam Leak Discovered During Scram Recovery.Event Also Described in LER 93-027. Encl LER 93-029 Provides Separate Report,Per 10CFR50.73 | Primary Coolant Steam Leak Discovered During Scram Recovery.Event Also Described in LER 93-027. Encl LER 93-029 Provides Separate Report,Per 10CFR50.73 | | | 05000397/LER-1993-028, Application for Amend to License NPF-21 for Exclusion of Single RWCU Helb,In Ref to LER 93-028-00,submitted Via | Application for Amend to License NPF-21 for Exclusion of Single RWCU Helb,In Ref to LER 93-028-00,submitted Via | | | 05000397/LER-1993-029, :on 930805,discovered Primary Coolant Steam Leak.Caused by Weld Defect.Weld Crack Repaired on 930806. Weld Record for Applicable Weld Also Reviewed & No Discrepancies Identified |
- on 930805,discovered Primary Coolant Steam Leak.Caused by Weld Defect.Weld Crack Repaired on 930806. Weld Record for Applicable Weld Also Reviewed & No Discrepancies Identified
| 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2) | | 05000397/LER-1993-030, :on 931028,cable Tray Cover Deficiencies Discovered Due to Inadequate Mgt Methods to Identify & Resolve Cable Tray & Conduit Electrical Separation Problems. Established Fire Tours of Affected Areas |
- on 931028,cable Tray Cover Deficiencies Discovered Due to Inadequate Mgt Methods to Identify & Resolve Cable Tray & Conduit Electrical Separation Problems. Established Fire Tours of Affected Areas
| 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000397/LER-1993-031, :on 931109,engineering Evaluation Determined That MCR HVAC Sys Will Not Maintain CR Temp.Caused by Inadequate Design Margin in Original Design.Per Written to Document Potential Analysis Concerns |
- on 931109,engineering Evaluation Determined That MCR HVAC Sys Will Not Maintain CR Temp.Caused by Inadequate Design Margin in Original Design.Per Written to Document Potential Analysis Concerns
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2) | | 05000397/LER-1993-031-01, Provides Info Re WNP-2,Operating License NPF-21, LER 93-031-01,corrective Actions That Were Completed | Provides Info Re WNP-2,Operating License NPF-21, LER 93-031-01,corrective Actions That Were Completed | |
|