05000387/FIN-2014009-03
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Correct Condition Adverse to Quality Related to Fatigue Stress in ESW Supply Lines to RHR Pump Motor Oil Cooler |
Description | The inspectors identified a Green NCV of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Actions, because PPL did not take measures to promptly correct an identified condition adverse to quality associated with the Emergency Service Water (ESW) supply lines to the 1C, 1D, 2C, and 2D Residual Heat Removal (RHR) pump motor oil coolers. PPL entered these conditions into their CAP as CR-2014-20129 and is continuing to evaluate corrective actions. Based on PPLs evaluation conducted in CR-2014-20129, that the ESW and RHR systems will perform their required safety functions and compensatory measures are in place to limit and monitor the pipe vibration, the inspectors determined that the noncompliance does not present an immediate safety concern. The finding is more than minor because it was associated with the equipment performance attribute of the Mitigating Systems cornerstone and adversely affected the cornerstone objective of ensuring the reliability of systems that respond to initiating events to prevent undesirable consequences. Additionally, it was similar to example 4.a in IMC 0612 Appendix E, Examples of Minor Issues, in that PPL had several opportunities to perform engineering evaluations on this condition and later evaluation determined that safety-related equipment was adversely affected. Specifically, no engineering evaluations were performed from 2009 through 2012, and post-2012 engineering evaluations did not fully bound the condition. Analysis performed after NRC identification resulted in additional evaluation and compensatory actions being implemented under CR 2014-20129. In accordance with IMC 0609, Significance Determination Process, Attachment 4, Initial Characterization of Findings, Table 2, Cornerstones Affected by Degraded Condition or Programmatic Weakness, inspectors determined this performance deficiency affected the Mitigating Systems Cornerstone. Using IMC 0609, Appendix A, The SDP for Findings At-Power, Exhibit 2, Mitigating Systems Screening Questions, issued June 19, 2012, the inspectors determined that this finding is of very low safety significance (Green) since question A.1 was answered Yes because the deficiency only affected the qualification of the ESW and RHR systems, but the ESW and RHR systems maintained operability. The inspectors determined that this finding had a human performance cross-cutting aspect related to Conservative Bias because PPL failed to use decision making-practices that emphasized prudent choices over those that are simply allowable. Specifically, PPL was relying on a leak-before-break assumption to support the continued operability of the safety related piping to the RHR pump motor oil coolers without sufficient priority to correct the condition adverse to quality. [H.14] |
Site: | Susquehanna |
---|---|
Report | IR 05000387/2014009 Section 4OA2 |
Date counted | Jun 30, 2014 (2014Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | A Defrancisco B Bickett F Bower T Daun |
Violation of: | 10 CFR 50 Appendix B Criterion XVI |
CCA | H.14, Conservative Bias |
INPO aspect | DM.2 |
' | |
Finding - Susquehanna - IR 05000387/2014009 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Susquehanna) @ 2014Q2
Self-Identified List (Susquehanna)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||