Finding | |
---|---|
Title | Failure to Ensure the Adequacy of Control Voltage to the 4160 and 480 VAC Equipment |
Description | The team identified a finding of very low safety significance and associated NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the failure to ensure the adequacy of control voltage to the 4160 and 480 VAC equipment in support of mitigating system loads; specifically, a lack of voltage drop analysis for 125 VDC control power to breaker open/close coil, spring charging motors, and other miscellaneous DC loads. The licensee entered this issue into the corrective action program as CR361181.The inspectors concluded that the finding is more than minor in that it involves the mitigating systems cornerstone attribute of design control and affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The inspectors determined the failure to assure and verify that adequate control voltage was available to close and open the 4160 VAC and 480 VAC breakers could have affected the capability of safety-related equipment to respond to initiating events. The finding is of very low safety significance as it did not result in an actual loss of safety function. The team also evaluated the finding for cross-cutting aspects and none were identified as this was determined to not be indicative of current licensee performance. |
Site: | North Anna ![]() |
---|---|
Report | IR 05000338/2009007 Section 1R21 |
Date counted | Dec 31, 2009 (2009Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | A Alen R Moore C Baron R Lewis J Hamman G Nicely B Desai J Eargle |
INPO aspect | |
' | |
Finding - North Anna - IR 05000338/2009007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (North Anna) @ 2009Q4
Self-Identified List (North Anna)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||