Finding | |
|---|---|
| Title | Failure to Perform Periodic TOL Testing on Unit 1 |
| Description | The team identified a finding of very low safety significance (Green) and associated NCV of 10 CFR Part 50, Appendix B, Criterion XI, Test Control, for the licensees failure to assure that thermal overload protection devices (TOLs) on safety-related motor-operated valve (MOV) circuits of Unit 1 were periodically tested to ensure that trip set point drift does not affect the reliability or availability of mitigating systems when called upon to operate. The licensee entered this issue into the corrective action program as CR361181.The inspectors concluded that the finding was more than minor in that the finding involves the mitigating systems cornerstone attribute of procedure quality and affects the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the inspectors determined that the failure to assure that TOLs would not unnecessarily prevent safety related valves from performing their function. This could affect the availability and ability of MOVs to respond to initiating events. As no failures due to TOL performance were identified by the inspectors which would affect plant response, the inspectors determined this finding and violation of regulatory requirements to be of very low safety significance. The finding was reviewed for cross-cutting aspects and none were identified as this was determined to not be indicative of current licensee performance. |
| Site: | North Anna |
|---|---|
| Report | IR 05000338/2009007 Section 1R21 |
| Date counted | Dec 31, 2009 (2009Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | A Alen R Moore C Baron R Lewis J Hamman G Nicely B Desai J Eargle |
| INPO aspect | |
| ' | |
Finding - North Anna - IR 05000338/2009007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (North Anna) @ 2009Q4
Self-Identified List (North Anna)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||