Finding | |
|---|---|
| Title | Failure to Include Flood Protection Features in the Maintenance Rule Program |
| Description | An NRC-identified Green non-cited violation (NCV) of 10 CFR 50.65(b)(2)(ii) was identified for the failure of the licensee to scope flood protection features in the maintenance rule (MR) program. Specifically, from July 10, 1996, to May 8, 2014, the licensee failed to include floor drain flood protection features in the MR program that are nonsafety-related but whose failure could prevent safety-related structures, systems, and components (SSCs) from fulfilling their safety-related function. The licensees corrective actions included scoping the floor drains into the MR program. The licensee entered this issue into the corrective action program (CAP) as nuclear condition report (NCR) 677850. The inspectors determined that the failure of the licensee to monitor flood protection features in the MR program, as required by 10 CFR 50.65(b)(2)(ii), was a performance deficiency. The finding is more than minor because it is associated with the protection against external factors (i.e. flood hazard) attribute of the Mitigating Systems Cornerstone and adversely affects the cornerstone objective of ensuring the availability, reliability, and capability of the safety related systems to respond to initiating events to prevent undesirable consequences. Specifically, the finding is more than minor because failing to monitor flood protection features resulted in degradation of various flood protection features which could have impacted safety-related equipment. Using IMC 0609, Appendix A, issued June 9, 2012, The SDP for Findings At-Power, Exhibit 2, the inspectors determined the finding is of very low safety significance (Green) because it did not represent an actual loss of function of one or more non-TS trains of equipment designated as high safety-significant in accordance with the licensees maintenance rule program for greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The finding has a cross-cutting aspect in the area of problem identification and resolution associated with the resolution attribute because the organization failed to take effective corrective actions to address issues in a timely manner commensurate with their safety significance. Specifically, the licensee failed to scope the credited flood protection floor drains into the MR program. [P.3] |
| Site: | Brunswick |
|---|---|
| Report | IR 05000324/2014003 Section 1R12 |
| Date counted | Jun 30, 2014 (2014Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.12 |
| Inspectors (proximate) | D Jackson G Hopper J Dodson M Catts M Schwieg |
| Violation of: | 10 CFR 50.65(b) 10 CFR 50.65 |
| CCA | P.3, Resolution |
| INPO aspect | PI.3 |
| ' | |
Finding - Brunswick - IR 05000324/2014003 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Brunswick) @ 2014Q2
Self-Identified List (Brunswick)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||