Finding | |
---|---|
Title | Cables for Fire Safe Shutdown Not Protected In Accordance With 10 CFR 50 Appendix R Section III.G.2 |
Description | The NRC identified a Green non-cited violation (NCV) of 10 CFR Part 50, Appendix R, Section III.G.2, for the licensees failure to protect one of the redundant trains of cables, located in the same fire area (FA), needed to achieve post-fire safe shutdown (SSD) from fire damage for multiple fire areas for Unit 1. Upon discovery, the licensee entered this item into their corrective action program as Condition Report (CR) 100755. As corrective actions, the licensee had implemented modifications to eliminate the need for local operator manual actions (OMAs) to achieve SSD. However, the inspectors discovered that, for FZ 0014K, the modifications did not adequately eliminate reliance on local OMAs to achieve SSD. The licensee entered this condition into the corrective action program as CR 364483. At the time of the exit meeting, the licensee planned to reroute affected cables out of the affected FA. The licensees failure to protect one train of cables and equipment necessary to achieve post-fire SSD from fire damage for fire areas designated in the fire protection program as meeting 10 CFR 50 Appendix R, Section III.G.2, is a performance deficiency. This finding is more than minor because it is associated with the reactor safety mitigating system cornerstone attribute of protection against external events (i.e., fire). Failure to protect safe shutdown cables and equipment from fire damage affects the reactor safety mitigating systems cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The inspectors used NRC Inspection Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process, and determined the finding was of very low safety significance (Green). Inspectors determined that no cross cutting aspect was applicable to this performance deficiency because this finding was not indicative of current licensee performance. |
Site: | Hatch |
---|---|
Report | IR 05000321/2011005 Section 4OA5 |
Date counted | Dec 31, 2011 (2011Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | |
Inspectors (proximate) | L Dymek M Bates R Carrion D Hardage E Morris J Hickey J Montgomery |
INPO aspect | |
' | |
Finding - Hatch - IR 05000321/2011005 | ||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Hatch) @ 2011Q4
Self-Identified List (Hatch)
| ||||||||||||||||||||||||||||||||||||||||||||||||||