05000317/LER-2018-003, Control Room Loss of Ventilation Due to Smoke Detector Failure Causing Common Supply Damper to Shut
| ML18242A074 | |
| Person / Time | |
|---|---|
| Site: | Calvert Cliffs |
| Issue date: | 08/27/2018 |
| From: | Tierney T Exelon Generation Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| LER 2018-003-00 | |
| Download: ML18242A074 (5) | |
| Event date: | |
|---|---|
| Report date: | |
| Reporting criterion: | 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(ix)(A) 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i) |
| 3172018003R00 - NRC Website | |
text
,
- - rt
~~--,* Exelon Generation August 27, 2018 U.S. Nuclear Regulatory Commission ATIN: Document Control Desk Washington, DC 20555 Calvert Cliffs Nuclear Power Plant, Units No. 1 and 2 Todd A. Tierney Plant Manager Calvert Cliffs Nuclear Power Plant 1650 Calvert Cliffs Parkway Lusby, MD 20657 410 495 5205 Office 484-459-0142 Mobile www.exeloncorp.com todd.tierney@exeloncorp.com 10 CFR 50.73 Renewed Facility Operating License Nos. DPR-53 and DPR-69 NRC Docket Nos. 50-317 and 50-318
Subject:
Licensee Event Report 2018-003, Revision 00 Control Room Loss of Ventilation due to Smoke Detector Failure Causing Common Supply Damper to Shut The attached report is being sent to you as required by 1 O CFR 50.73.
There are no regulatory commitments contained in this correspondence.
Should you have questions regarding this report, please contact Mr. Larry D. Smith at (410) 495-5219.
Respectfully,
~
a."' zj)_,,//IA~
Todd A. Tierney
-....:r- -
Plant Manager TAT/PSF/bjm
Attachment:
As stated cc:
NRC Project Manager, Calvert Cliffs NRC Regional Administrator, Region I NRC Resident Inspector, Calvert Cliffs D. A. Tancabel, DNR
NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY 0MB: NO. 3150-0104 EXPIRES: 03/31/2020 (04-2018)
Estimated burden per response to comply with this mandatory collection request: BO hours.
,,...1'REQ1,l LICENSEE EVENT REPORT (LER)
Reported lessons learned are incorporated into the licensing process and fed back to
~r,j
"'f>_
industry. Send comments regarding burden estimate to the lnfonnation Services Branch
~
~
(T-2 F43), U.S. Nuclear Regulatory Commission, Washington, DC 20555,-0001, or by e-mail to
/jJ (See Page 2 for required number of digits/characters for each block)
~
s lnfocollects.Resource@nrc.gov, and to the Desk Officer, Off~e of lnfonnation and Regulatory
~
,, lC Affairs, NEOB-10202, (3150,-0104), Office of Management and Budget, Washington, DC 20503.
~-
I (See NUREG-1022, R.3 for instruction and guidance for completing this form If a
means used to impose an infonnation collection does not
~+..,.
+o~
httg://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr1022/r3/)
cf~playacurrentlyvalid OMS control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the infonnation collection.
3.Page Calvert Cliffs Nuclear Power Plant, Unit 1 05000317 1
OF 4
- 4. Title Control Room Loss of Ventilation due to Smoke Detector Failure Causing Common Supply Damper to Shut
- 5. Event Date
- 6. LER Number
- 7. Report Date
- 8. Other Facilities Involved I
Sequential I Rev Facility Name Docket Number Month Day Year Year Number No.
Month Day Year Calvert Cliffs Nuclear Power Plant Unit 2 05000 318 Facility Name Docket Number 07 07 2018 2018 - 003 00 08 27 2018 05000
- 9. Operating Mode
- 11. This Report is Submitted Pursuant to the Requirements of 1 O CFR §: (Check all that apply)
D 20.2201(bl D 20.2203(a)(3J(il D 50.73(a)(2)(ii)(A)
D 50.73(a)(2)(viii)(A)
D 20.2201(d)
D 20.2203(a)(3)(ii)
D 50.73(a)(2)(ii)(B)
D 50.73(a)(2)(viii)(B) 1 D
D 20.2203(a)(4)
D 50.73(a)(2)(iiil D 50.73(a)(2)(ix)(A) 20.2203(a)(1)
D 20.2203(a)(2)(i)
D 50.36(c)(1)(i)(A)
D 50.73(a)(2)(iv)(A)
D 50.73(a)(2)(x)
- 10. Power Level D 20.2203(a)(2)(iil D 50.36(c)(1)(ii)(A)
D 50.73(a)(2)(v)(A)
D 73.71 (a)(4)
D 20.2203(a)(2)(iiil D 50.36(c)(2)
D 50.73(a)(2)(v)(B)
D 73.71(a)(5l D 20.2203(a)(2)(iv)
D 50.46(a)(3)(iil D 50.73(a)(2)(v)(C)
D 73.77(a)(1) 100 D 20.2203(a)(2)(v)
D 50.73(a)(2)(i)(A) 1:8:1 50.73(a)(2)(v)(D)
D 73.77(a)(2J(i)
D 20.2203(a)(2)(vi)
D 50.73(a)(2)(i)(B) 1:8:1 50.73(a)(2)(vii)
D 73.77(a)(2)(ii) i!
,*':!J*/ * (\\, ;' *,1,,.: *:*
,,,;! D 50.73(a)(2)(i)(C)
D Other (Specify in Abstract below or in The CREVS and CRETS are a two-train system that serves the common Unit 1 and Unit 2 Control Room. The CREVS is an emergency system that provides automatic airborne radiological, smoke and toxic gas protection for Control Room occupants. The CRETS is an emergency system that provides adequate cooling to maintain equipment in the Control Room operable. The CREVS and CRETS systems share the same ductwork. In the shared ductwork, the supply damper is a single damper that controls flow to both trains. Failure of that single damper renders both trains inoperable due to lack of ventilation flow.
This condition was entered into the corrective action program and the NRG was notified via Event Notification 53493 on July 7, 2018.
C.
CAUSE OF EVENT
This event is documented in the site's Corrective Action Program under IR 4153797. Field troubleshooting isolated the cause of failure to Control Room ventilation smoke detector
{OAE5347). The smoke detector functions to shut the Control Room ventilation supply damper by energizing the associated solenoid valve (O-SV-5342). The associated solenoid valve was observed in the energized state via thermography. The solenoid valve is normally de-energized to maintain the damper open.
The cause of the smoke detector failure is under investigation and will be reported in a supplement to this LER.
D.
SAFETY ANALYSIS
The actual consequence resulting from this identified event was the loss of all Control Room ventilation circulation for a ?-minute period of time. During this short loss of ventilation, the Control Room remained habitable and the temperature remained within operability limits for the equipment in the Control Room. If an event occurred during a loss of ventilation, resulting in a radioactive or toxic gas release, self-contained breathing apparatus is available in the Control Room for the operations staff to support their response to the event. Operations staff are qualified and trained on the use of the self-contained breathing apparatus during plant events. Additionally, the Units were previously analyzed for a loss of Control Room ventilation for an extended period (4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />) as part of the response to 10 CFR 50.63, Station Blackout. That analysis determined that the equipment could withstand the loss of ventilation for the extended period of time and still perform its functions.
The probabilistic risk assessment analysis determined that the estimated increase in core damage frequency was less than 1 E-07 and the estimated increase in large early release frequency was less than 1 E-08 per year for the subject condition. The PRA analysis conservatively assumed elevated temperature in the CR due to failure of the CR HVAC damper and that assumed temperature increase would not have a significant impact on plant risk. This issue would be l'GREEN" using the NRC's Significance Determination Process.
00 E.
CORRECTIVE ACTIONS
YEAR 2018 SEQUENTIAL NUMBER 003 Immediate corrective action was taken to re-open the Control Room supply damper by manually isolating air to the solenoid valve and removing air pressure to return the Control Room supply damper to an open condition.
Additional corrective actions will be determined, if any, during the on-going causal analysis. They will be reported in the supplement to this LER.
F.
PREVIOUS OCCURRENCES
No previous similar events have occurred at the site within the last 5 years.
G.
COMPONENT FAILURE DATA
Control Room ventilation smoke detector REV NO.
00 Page _4_ of _L