05000272/FIN-2014002-02
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Inadequate Online Risk Assessment for an Adverse Change in Grid Conditions |
| Description | The inspectors identified a Green NCV of Title 10 of the Code of Federal Regulations (10 CFR) 50.65(a)(4) when PSEG inadequately assessed risk during a period of adverse grid conditions. On January 7, 2014, the regional transmission organization declared a Maximum Emergency Generation Action, a condition that PSEG was procedurally required to consider a high risk evolution (HRE) for a loss of offsite power (LOOP). Specifically, PSEG was to elevate online risk to a Yellow condition; however, PSEG did not assess risk as Yellow. PSEG subsequently elevated their risk condition, protected equipment, took other risk management actions (RMAs), and entered the issue in their CAP. The issue was more than minor since it was associated with the Protection Against External Factors attribute of the Initiating Events cornerstone and adversely affected its objective to limit the likelihood of events that upset plant stability and challenge critical safety functions during shutdown as well as power operations. Specifically, the extreme cold weather conditions indirectly were affecting grid stability and required risk assessment and management. Additionally, it was similar to IMC 0612, Appendix E, example 7.e, in that an inadequate risk assessment is not minor if the overall plant risk would put the plant into a higher licensee-established risk category. In this case, plant risk was reclassified from Green to Yellow when properly assessed. Specifically, the extreme cold weather conditions indirectly were affecting grid stability. The inspectors evaluated the finding using IMC 0612, Appendix K, Maintenance Risk Assessment and Risk Management Significance Determination Process. Since the incremental core damage probability deficit was less than 1 E-6 and the incremental large early release probability deficit was less than 1 E-7, this finding was determined to be of very low safety significance (Green). The finding was determined to have a cross-cutting aspect in the area of Human Performance, Teamwork, in that individuals and work groups communicate and coordinate their activities within and across organizational boundaries to ensure nuclear safety is maintained. Specifically, PSEG staff in the Electric System Operations Center (ESOC), Salem control room, and Hope Creek control room did not appropriately communicate across organizational boundaries to ensure that risk was appropriately assessed. |
| Site: | Salem |
|---|---|
| Report | IR 05000272/2014002 Section 1R13 |
| Date counted | Mar 31, 2014 (2014Q1) |
| Type: | NCV: Green |
| cornerstone | Initiating Events |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.13 |
| Inspectors (proximate) | A Ziedonis E Burket G Dentel J Schoppy P Finney R Barkley R Nimitz |
| Violation of: | 10 CFR 50.65(a)(4) 10 CFR 50.65 |
| INPO aspect | |
| ' | |
Finding - Salem - IR 05000272/2014002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Salem) @ 2014Q1
Self-Identified List (Salem)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||