05000263/FIN-2015001-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Identify High Pressure Coolant Injection (HPCI) Seismic Support Nonconformance |
| Description | The inspectors identified a finding of very low safety significance and an NCV of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action, for the licensees failure to promptly identify conditions adverse to quality, such as deficiencies, deviations, and nonconformances. Specifically, on February 11, 2015, the inspectors identified a safety related seismic support for high pressure coolant injection (HPCI) turbine trip instrumentation that was not rigidly attached, supported, and restrained in accordance with plant construction code and installation specifications, a nonconformance which the licensee had failed to identify since initial plant construction. Corrective actions for this issue included repairs to the seismic support to rigidly connect the instrument line restraint and installation of a standalone support for the instrument tray. This issue was entered into the licensees corrective action program (CAP 1465906). The inspectors determined that the failure to promptly identify an HPCI instrument line support nonconformance was a performance deficiency requiring evaluation. The inspectors determined that the issue was more than minor because it adversely impacted the Mitigating Systems Cornerstone attribute of Protection Against External Factors, and affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage). The inspectors assessed the significance of this finding in accordance with IMC 0609 and determined that it was of very low safety significance. The inspectors determined that the contributing cause that provided the most insight into the performance deficiency was associated with the cross-cutting area of Problem Identification and Resolution, and the aspect of Identification because the licensee failed to implement a CAP with a low threshold for identifying issues [P.1]. |
| Site: | Monticello |
|---|---|
| Report | IR 05000263/2015001 Section 1R04 |
| Date counted | Mar 31, 2015 (2015Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.04 |
| Inspectors (proximate) | I Hafeez J Beavers J Neurauter K Riemer M Davis M Learn M Mitchell M Ziolkowski P Voss P Zurawski S Bell T Bilik |
| Violation of: | 10 CFR 50 Appendix B Criterion XVI |
| CCA | P.1, Identification |
| INPO aspect | PI.1 |
| ' | |
Finding - Monticello - IR 05000263/2015001 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Monticello) @ 2015Q1
Self-Identified List (Monticello)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||