Finding | |
---|---|
Title | Failure to Evaluate the Extent of Condition for a Degraded Condition on a Nonsafety-Related 4160 Vac Breaker |
Description | The team identified a Green, non-cited violation of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, which states, in part, Activities affecting quality shall be prescribed by documented instructions, procedures, or drawings, of a type appropriate to the circumstances and shall be accomplished in accordance with these instructions, procedures, or drawings. Specifically, in October of 2015, the licensee failed to evaluate the extent of condition of a cracked holding pawl on a nonsafety-related 4160 Vac SF6 breaker, which was procured as safety-related, in accordance with Procedure OM7.ID1, Problem Identification and Resolution, when the failure of the component could adversely impact safety-related breakers of the same make and model. In response to this finding, the licensee is performing a procedure review to include steps to perform an extent of condition analysis for unplanned nonsafety-related equipment issues that may also affect similar safety-related equipment. This finding was entered into the licensee's corrective action program as Notifications 50836859 and 50836689. The team determined the failure to evaluate the impact of a cracked holding pawl identified on a nonsafety-related 4160 Vac SF6 breaker on additional safety-related 4160 Vac SF6 breakers was a performance deficiency. The performance deficiency was more-thanminor, and therefore a finding, because it related to the equipment performance attribute of the Mitigating Systems cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the 4160 Vac breaker with the cracked holding pawl was procured as safetyrelated; therefore, the condition extends to safety-related 4160 Vac breakers of the same make and model and potentially adversely affects the ability to perform their safety function. In accordance with Inspection Manual Chapter 0609, Appendix A, The Significance Determination Process (SDP) for Findings At-Power, dated July 19, 2012, the finding screened as having very low safety significance (Green) because it was a design or qualification deficiency that did not represent a loss of operability or functionality; did not represent an actual loss of safety function of the system or train; did not result in the loss of one or more trains of non-technical specification equipment; and did not screen as potentially risk-significant due to seismic, flooding, or severe weather. This finding had a cross-cutting aspect in the area of human performance associated with conservative bias because the licensee failed to ensure that individuals used decision-making practices that emphasized prudent choices [H.14]. |
Site: | Diablo Canyon |
---|---|
Report | IR 05000275/2016007 Section 1R21 |
Date counted | Mar 31, 2016 (2016Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | C Steely D Loveless H Leake J Braisted J Zudans M Hayes N Okonkwo R Kopriva R Latta T Farnholtz |
Violation of: | 10 CFR 50 Appendix B Criterion V |
CCA | H.6, Design Margins |
INPO aspect | WP.2 |
' | |