Finding | |
|---|---|
| Title | Failure to Evaluate 480 Vac Motor Starters with Circuit Breaker Trip Settings Higher than Manufacturers Specifications |
| Description | The team identified a Green, non-cited violation of 10 CFR Part 50, Appendix B, Criterion III, Design Control, which states, in part, The design control measures shall provide for verifying or checking the adequacy of design, such as by the use of alternate or simplified calculational methods, or by the performance of a suitable testing program. Specifically, prior to September 10, 2013, the licensee failed to verify the design of 480 Vac combination motor starter instantaneous magnetic circuit breakers settings, by the use of alternate or simplified calculational methods, for those breakers whose settings are higher than their manufacturers' specifications, as documented in calculation 195B-DC, MCCB Settings for 460VAC Class 1E Motors, to provide the required level of protection and ensure that certain failures that could be caused by sustained fault currents below the circuit breaker trip setting would not occur. In response to this finding, the licensee conducted a preliminary evaluation of some of the affected equipment and concluded that sustained fault currents below the trip settings are unlikely. This finding was entered into the licensee's corrective action program as Notification 50838071. The team determined the failure to evaluate 480 Vac combination motor starters with instantaneous magnetic circuit breaker trip current settings higher than their manufacturers' specifications was a performance deficiency. The performance deficiency was more-thanminor, and therefore a finding, because it related to the design control attribute of the Mitigating Systems cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, improper motor starter breaker trip settings could result in a fire in the motor control center cubicle, damage to motor starter components, spurious tripping of the entire motor control center, or lack of protection for downstream components during fault conditions. In accordance with Inspection Manual Chapter 0609, Appendix A, The Significance Determination Process (SDP) for Findings At-Power, dated July 19, 2012, the finding screened as having very low safety significance (Green) because it was a design or qualification deficiency that did not represent a loss of operability or functionality; did not represent an actual loss of safety function of the system or train; did not result in the loss of one or more trains of non-technical specification equipment; and did not screen as potentially risk-significant due to seismic, flooding, or severe weather. This finding did not have a cross-cutting aspect because the most significant causal factor of the performance deficiency did not reflect current licensee performance. |
| Site: | Diablo Canyon |
|---|---|
| Report | IR 05000275/2016007 Section 1R21 |
| Date counted | Mar 31, 2016 (2016Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | C Steely D Loveless H Leake J Braisted J Zudans M Hayes N Okonkwo R Kopriva R Latta T Farnholtz |
| Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
| INPO aspect | |
| ' | |