Proposed TS Table 3.3.7.12-1, Explosive Gas Monitoring Instrumentation.
ML17289A862
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 09/17/1992
From:
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To:
Shared Package
ML17289A861 List:
References
NUDOCS 9209230019
Download: ML17289A862 (2)


Text

TABLE 3.3.7.12-1 C 4 EXPLOSIVE GAS HONITORING INSTRUHENTATION INSTRUHENT HINIHUH CHANNELS OPERABLE APPLICABILITY ACTION 1 Hain Condenser Offgas Treatment System Explosive Gas Honitoring System a.Hydrogen Honitor"During main condenser offgas treatment system operation.

ACTION 111'-With the number of channels OPERABLE less than required by the Hinimum Channels OPERABLE requirement, operation of main condenser offgas treatment system may continue for up to 30 days provided that grab samples are collected at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and analyzed within the following 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.If the recombiner temperature remains constant and THERMAL POWER has not changed, the grab sample collection frequency may be changed to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.A G C7 A 0 t$!Q XO IQ WM UO OO QV OQ cntu OO 04 QOP au%