Init EXAM-4-2000-Draft Admin JPM A-1-2
ML003716657
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 04/24/2000
From:
NRC Region 4
To:
References
-RFPFR
Download: ML003716657 (6)


Text

JPM- ANO-2-JPM-NRC-PMS001 PAGE 1 OF 6 ADMIN JOB PERFORMANCE MEASURE UNIT: 2 REV #: 000 DATE:

SYSTEM/DUTY AREA: Plant Monitoring System (PMS)

TASK: Setup programmable alarm on PMS.

JTA#:

KA VALUE RO: 3.0 SRO: 3.0 KA

REFERENCE:

2.1.19 APPROVED FOR ADMINISTRATION TO: RO: X SRO: X TASK LOCATION: INSIDE CR: X OUTSIDE CR: BOTH:

SUGGESTED TESTING ENVIRONMENT AND METHOD (PERFORM OR SIMULATE):

PLANT SITE: Simulate SIMULATOR: Perform LAB:

POSITION EVALUATED: RO: SRO:

ACTUAL TESTING ENVIRONMENT: SIMULATOR: PLANT SITE: LAB:

TESTING METHOD: SIMULATE: PERFORM:

APPROXIMATE COMPLETION TIME IN MINUTES: 10 Minutes REFERENCE(S): 2106.008 Rev 025-00-0 and skill of craft EXAMINEE'S NAME: SSN:

EVALUATOR'S NAME:

THE EXAMINEE'S PERFORMANCE WAS EVALUATED AGAINST THE STANDARDS CONTAINED IN THIS JPM AND IS DETERMINED TO BE:

SATISFACTORY: UNSATISFACTORY:

PERFORMANCE CHECKLIST COMMENTS:

Start Time Stop Time Total Time SIGNED: DATE:

SIGNATURE INDICATES THIS JPM HAS BEEN COMPARED TO ITS APPLICABLE PROCEDURE BY A QUALIFIED INDIVIDUAL (NOT THE EXAMINEE) AND IS CURRENT WITH THAT REVISION.

JPM- ANO-2-JPM-NRC-PMS001 PAGE 2 OF 6 ADMIN JOB PERFORMANCE MEASURE THE EXAMINER SHALL REVIEW THE FOLLOWING WITH THE EXAMINEE:

The examiner shall review the "Briefing Checklist - System Walkthrough" portion of OP 1064.023 Attachment 6 with the examinee.

JPM INITIAL TASK CONDITIONS:

Mode 1 Full Power. Performing initial conditions of 2106.008, Steam Generator Operations section 8.2.

TASK STANDARD:

Programmable alarm setup on PMS for blowdown activity (R4425).

TASK PERFORMANCE AIDS:

PMS operating EXAMINER'S NOTE:

Check no PMS programmable alarms are set.

JPM- ANO-2-JPM-NRC-PMS001 PAGE 3 OF 6 ADMIN JOB PERFORMANCE MEASURE INITIATING CUE:

The SS/CRS directs, "Place a programmable alarm on 2K01-J9 for blowdown activity (R4425) high of 1.0E3. Use work item number 101010."

CRITICAL ELEMENTS (C): 3,4,5,6,7,9,10,and 11 PERFORMANCE CHECKLIST STANDARDS (Circle One)

NOTE:

Steps 3 through 7 may be performed prior to steps 1 and 2.

1. Select Programmable At PMS keyboard, typed J9 and N/A SAT UNSAT Annunciator Assignment Screen depressed ENTER key.

for 2K01-J9 on PMS.

Verified Programmable Annunciator Assignment Screen for 2K01-J9 appears on touch screen.

2. Add R4425point on At PMS keyboard, selected a point N/A SAT UNSAT Programmable Annunciator location on Programmable Assignment Screen. Annunciator Assignment Screen.

Typed R4425 and depressed ENTER key.

(C) 3. Select Database Management At Programmable Annunciator N/A SAT UNSAT from Programmable Annunciator Assignment Screen, touched Assignment Screen. DBM touch button on lower portion of touch screen.

Verified Analog Input Point Template Screen appears.

(C) 4. Select R4425 on Analog Input At PMS keyboard, typed R4425 N/A SAT UNSAT Point Template Screen. and depressed ENTER key.

Verified that point R4425 is selected.

(C) 5. Select Power Operations alarm At PMS keyboard, depressed right N/A SAT UNSAT setpoint for update. or left arrow key to place cursor on either Power Operations High Alarm position.

(C) 6. Change High alarm setpoint to At PMS keyboard, typed 1.0E3 N/A SAT UNSAT 1.0E3. and depressed ENTER key.

(C) 7. Save changes to alarm setpoint. At PMS keyboard, depressed F-3 N/A SAT UNSAT key to save.

JPM- ANO-2-JPM-NRC-PMS001 PAGE 4 OF 6 ADMIN JOB PERFORMANCE MEASURE PERFORMANCE CHECKLIST STANDARDS (Circle One)

Examiners Note:

Have examinee type 101010 as work item number and press ENTER to allow saving on the Simulator PMS.

8. Select Programmable At PMS keyboard, typed J9 and N/A SAT UNSAT Annunciator Assignment Screen depressed ENTER key.

for 2K01-J9 on PMS.

Verified Programmable Annunciator Assignment Screen for 2K01-J9 appears on touch screen.

(C) 9. Add R4425point on At PMS keyboard, selected a point N/A SAT UNSAT Programmable Annunciator location on Programmable Assignment Screen. Annunciator Assignment Screen.

Typed R4425 and depressed ENTER key.

(C) 10. Type S in process code and At PMS keyboard, typed S in N/A SAT UNSAT depress ENTER. process code and depressed ENTER key.

(C) 11. Save changes to alarm setpoint. At PMS keyboard, depressed F3 N/A SAT UNSAT key to save.

END

JPM- ANO-2-JPM-NRC-PMS001 PAGE 5 OF 6 ADMIN JOB PERFORMANCE MEASURE QUESTION:

ANSWER:

JPM- ANO-2-JPM-NRC-PMS001 PAGE 6 OF 6 ADMIN JOB PERFORMANCE MEASURE INITIAL CONDITIONS:

Mode 1 Full Power. Performing initial conditions of 2106.008, Steam Generator Operations section 8.2.

INITIATING CUE:

The SS/CRS directs, "Place a programmable alarm on 2K01-J9 for blowdown activity (R4425) high of 1.0E3. Use work item number 101010."