Init EXAM-4-2000-Draft JPM CCP01 - Shift Lead Charging Pump
ML003716744
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 04/24/2000
From:
NRC Region 4
To:
References
-RFPFR
Download: ML003716744 (5)


Text

JPM- ANO-2-JPM-NRC-CCP01 PAGE 1 OF 5 JOB PERFORMANCE MEASURE UNIT: 2 REV #: 6 DATE:

SYSTEM/DUTY AREA:

Pressurizer Level Control System TASK: Shifting Lead Charging Pump JTA#: 20045510401 KA VALUE RO:

3.5 SRO:

3.7 KA

REFERENCE:

011 A2.04 APPROVED FOR ADMINISTRATION TO: RO:

X SRO:

X TASK LOCATION: INSIDE CR:

X OUTSIDE CR:

BOTH:

SUGGESTED TESTING ENVIRONMENT AND METHOD (PERFORM OR SIMULATE):

PLANT SITE:

SIMULATOR:

Perform LAB:

POSITION EVALUATED: RO:

SRO:

ACTUAL TESTING ENVIRONMENT: SIMULATOR:

X PLANT SITE:

LAB:

TESTING METHOD: SIMULATE:

PERFORM:

X APPROXIMATE COMPLETION TIME IN MINUTES:

5 Minutes REFERENCE(S):

OP 2104.002 Rev 038-01-0 EXAMINEE'S NAME:

SSN: - -

EVALUATOR'S NAME:

THE EXAMINEE'S PERFORMANCE WAS EVALUATED AGAINST THE STANDARDS CONTAINED IN THIS JPM AND IS DETERMINED TO BE:

SATISFACTORY:

UNSATISFACTORY:

PERFORMANCE CHECKLIST COMMENTS:

Start Time

Stop Time

Total Time SIGNED__________________________________

DATE: _____________________

SIGNATURE INDICATES THIS JPM HAS BEEN COMPARED TO ITS APPLICABLE PROCEDURE BY A QUALIFIED INDIVIDUAL (NOT THE EXAMINEE) AND IS CURRENT WITH THAT REVISION.

THE EXAMINER SHALL REVIEW THE FOLLOWING WITH THE EXAMINEE:

JPM- ANO-2-JPM-NRC-CCP01 PAGE 2 OF 5 JOB PERFORMANCE MEASURE The examiner shall review the "Briefing Checklist - System Walkthrough" portion of OP 1064.023 Attachment 6 with the examinee.JPM INITIAL TASK CONDITIONS:

WCO has requested Charging Pump 2P36B be stopped to perform oil level check. THIS IS AN ALTERNATE SUCCESS PATH JPM.

TASK STANDARD:

Shift lead charging pump.

TASK PERFORMANCE AIDS:

OP 2104.002

SIMULATOR SETUP:

Select "B" as lead charging pump and trigger 2P36C Plunger Break CVC2P36CBRK. 2P36C aligned to green bus.

JPM- ANO-2-JPM-NRC-CCP01 PAGE 3 OF 5 JOB PERFORMANCE MEASURE INITIATING CUE:

The SS/CRS directs, "Shift lead charging pump to 2P36C using OP 2104.002 Section 8.1. Seal water pump has been running for 15 minutes." CRITICAL ELEMENTS (C):

2 PERFORMANCE CHECKLIST STANDARDS (Circle One) 1.Place selected pump handswitch to START.On 2C09, placed 2HS-4853-2 to START. Observed red light ON

and green light OFF.

N/A SAT UNSAT (C)2.Check Charging Flow goes up ~44 gpm.On 2C09, checked Charging Flow (2FIS-4863) and reports flow

indicates 60 gpm.

N/A SAT UNSAT 3.Did not get expected response, therefore secure 2P36C.

Placed 2HS-4853-2 to AUTO or STOP. Observed red light OFF and

green light ON.

N/A SAT UNSAT EXAMINEERS CUE:

Act as CRS and direct examinee to select 2P36A as lead charging pump.

4.Place selected pump handswitch to START.On 2C09, placed 2HS-4832-1 to START. Observed red light ON and

green light OFF.

N/A SAT UNSAT 5.Check Charging Flow goes up ~44 gpm.On 2C09, checks Charging Flow (2FIS-4863) flow indicates ~88 gpm.

N/A SAT UNSAT 6.Place Charging Pump Select Switch (2HS-4868) to selected lead

pump.On 2C09, placed Charging Pump Select handswitch (2HS-4868) to

PMP B&C position.

N/A SAT UNSAT 7.Verify previous lead pump stops.

Checked 2P36B stopped. Observed red light OFF and green light ON.

N/A SAT UNSAT 8.Check Charging Flow lowers

~44 gpm.On 2C09, checks Charging Flow (2FIS-4863) flow indicates ~44 gpm.

N/A SAT UNSAT 9.Place selected pump handswitch to AUTO.On 2C09, placed 2HS-4832-1 to AUTO. N/A SAT UNSAT END JPM- ANO-2-JPM-NRC-CCP01 PAGE 4 OF 5 JOB PERFORMANCE MEASURE QUESTION ANSWER JPM- ANO-2-JPM-NRC-CCP01 PAGE 5 OF 5 JOB PERFORMANCE MEASURE EXAMINEE'S COPY JPM INITIAL TASK CONDITIONS:

WCO has requested Charging Pump 2P36B be stopped to perform oil level checks.

INITIATING CUE:

The SS/CRS directs, "Shift lead charging pump to 2P36C using OP 2104.002 Section 8.1. Seal water pump has been running for 15 minutes."