Init EXAM-4-2000-Draft JPM Swcsp - Shift Stator Water Cooling Pumps
ML003716762
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 04/24/2000
From:
NRC Region 4
To:
References
-RFPFR
Download: ML003716762 (6)


Text

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-SWCSP REV. 00 PAGE 1 of 6 SYSTEM/DUTY AREA:

Stator Water Cooling System

TASK: Shift Stator Water Cooling Pumps

JTA #: None

KA VALUE RO: 3.9 SRO: 3.4 KA

REFERENCE:

045 2.1.30

APPROVED FOR ADMINISTRATION TO:

NLO: X RO: X SRO: X TASK LOCATION:

INSIDE CR:

OUTSIDE CR:

X BOTH:

SUGGESTED TESTING ENVIRONMENT AND METHOD (PERFORM OR SIMULATE):

PLANT SITE:

Simulate SIMULATOR:

LAB:

POSITION EVALUATED:

NLO:

RO:

SRO:

ACTUAL TESTING ENVIRONMENT:

SIMULATOR:

PLANT SITE:

X LAB:

TESTING METHOD:

SIMULATE: X PERFORM:

APPROXIMATE COMPLETION TIME IN MINUTES:

5 minutes

REFERENCE(S):

OP 2106.004 Rev.012-01-0 EXAMINEE'S NAME:

SSN:

-

-

EVALUATOR'S NAME:

DATE:

THE EXAMINEE'S PERFORMANCE WAS EVALUATED AGAINST THE STANDARDS CONTAINED IN THIS JPM AND IS DETERMINED TO BE:

SATISFACTORY:

UNSATISFACTORY:

PERFORMANCE CHECKLIST COMMENTS:

__________

Start Time

__________

Stop Time__________

Total Time Signature indicates this JPM has been compared to its applicable procedure by a qualified individual (not the examinee) and is current with that revision.

SIGNED:

DATE:

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-SWCSP REV. 00 PAGE 2 of 6 THE EXAMINER SHALL REVIEW THE FOLLOWING WITH THE EXAMINEE:

The examiner shall review the "Briefing Checklist - System Walkthrough" portion of OP 1064.023 Attachment 6 with the examinee.JPM INITIAL TASK CONDITIONS:

Predictive maintenance would like to take vibration readings on "B" stator water cooling pump (2P-25B). 2P-25A is running.

TASK STANDARD:

2P-25A has been started and 2P

-25B has been secured.

TASK PERFORMANCE AIDS:

OP 2106.004, Section 7.2

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-SWCSP REV. 00 PAGE 3 of 6 INITIATING CUE:

The SS/CRS directs, "Shift Stator Water Cooling Pumps from 2P-25A to 2P-25B using OP 2106.004 Section 7.2."

CRITICAL ELEMENTS (C):

1, 2

START TIME:

PERFORMANCE CHECKLIST STANDARDS (Circle One)(C)1.Place 2P-25A/B select switch (2HS-9784) to B-RUN A-RES.

POSITIVE CUE

For 2P-25B, red light on; green light off.

NEGATIVE CUE:

For 2P-25B, green light on; red light off.

On panel 2C140, rotated 2HS

-9784 CCW to "B-RUN A-RES".

Observed 2P

-25B pump indication red light on; green light off.

N/A SAT UNSAT (C)2.Push the Reserve Coolant Pump Cutout pushbutton.

POSITIVE CUE

For 2P-25A, green light on; red light off.

NEGATIVE CUE:

For 2P-25A, red light on; green light off.

At panel 2C140, pushed the Reserve Coolant Pump Cutout pushbutton.

Observed the 2P

-25A pump running status lights.

N/A SAT UNSAT 3.Verify the following readings are normal: - Pump discharge pressure (2PI-9799) - Stator Inlet Flow (2FIS-9722) - Stator Inlet Pressure (2PI-9798)

POSITIVE CUE:

2PI-9799 shows 120 psig.

2FIS-9722 shows between 510 and 525 gpm.2PI-9798 shows 60 psig.

Verified pressures and flow to be normal. N/A SAT UNSAT JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-SWCSP REV. 00 PAGE 4 of 6 PERFORMANCE CHECKLIST STANDARDS (Circle One) 4.Notify control room of pump shift and pump status.

Using the plant telephone, notified the control room that 2P

-25B is running. N/A SAT UNSAT END STOP TIME:

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-SWCSP REV. 00 PAGE 5 of 6 Question: Answer:

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-SWCSP REV. 00 PAGE 6 of 6 EXAMINEE'S COPY JPM INITIAL TASK CONDITIONS:

Predictive maintenance would like to take vibration readings on "B" stator water cooling pump (2P-25B). 2P-25A is running.

INITIATING CUE:

The SS/CRS directs, "Shift Stator Water Cooling Pumps from 2P-25A to 2P-25B using OP 2106.004 Section 7.2."