05000458/FIN-2008006-03
From kanterella
Revision as of 20:36, 28 October 2017 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Finding | |
---|---|
Title | Inadequate Testing Programs for 4-kV Circuit Breakers, Class 1E Molded Case Circuit Breakers, and the Emergency Diesel Generators (1R21.b.3) |
Description | The team identified a finding of very low safety significance involving a noncited violation of 10 CFR Part 50, Appendix B, Criterion XI, Test Control, with three examples. Specifically, the team identified that the licensee failed to develop and implement adequate testing programs for 4-kV circuit breakers, Class 1E molded-case circuit breakers, and the emergency diesel generators that met design or vendor requirements and recommendations. In response, the licensee entered these examples in the corrective action program as Condition Reports CR-RBS-2008-04379, CR-RBS-2008-3634, CR-RBS-2008-3676 and CR-RBS-2008-3701 and determined there was no loss of safety function for the affected components. The examples associated with this finding were more than minor because they were associated with the equipment control attribute of the Mitigating Systems Cornerstone and affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Traditional enforcement does not apply because the issue did not have any actual safety consequences or potential for impacting the NRCs regulatory function, and was not the result of any willful violation of NRC requirements. In accordance with Inspection Manual Chapter 0609, Attachment 4, Phase 1 Initial Screening and Characterization of Findings, a Phase 1 screening was performed and determined each example was of very low safety significance (Green) because it did not represent a loss of system safety function, did not represent an actual loss of safety function of a single train for greater than its Technical Specification allowed outage time, did not represent an actual loss of one or more risk-significant non-Technical Specification trains of equipment for greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, and did not screen as potentially risk-significant due to seismic, flooding, or severe weather. (Section 1R21.b.3 |
Site: | River Bend ![]() |
---|---|
Report | IR 05000458/2008006 Section 1R21 |
Date counted | Sep 30, 2008 (2008Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | B Henderson R Kopriva D Loveless S Graves P Gage R Bywater H Campbell G Nicely |