Finding | |
---|---|
Title | Failure to Identify Conditions Adverse to Fire Protection |
Description | The inspectors identified a noncited violation of License Condition 2.C(41) for the failure to identify conditions adverse to the fire protection program. Specifically, during required inspections of the material condition of the sprinkler system, the licensee failed to identify several instances of bent or misaligned sprinkler head deflector plates and a painted sprinkler head. Corrective action included correcting bent or misaligned plates and replacing the painted sprinkler head. This issue was entered into the licensees corrective action program as Condition Report CR-GGN-2011-03132. The finding is more than minor because it is associated with the protection against external factors attribute of the Mitigating System Cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the safety concern is that the number of bent or misaligned sprinkler heat canopies and painted sprinkler heads would not provide an adequate area-wide coverage of suppression. The inspectors evaluated the significance of this finding using Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process. The deficiency involved the Fixed Fire Protection Systems category. Using Appendix F, Attachment 2, Degradation Rating Guidance Specific to Various Fire Protection Program Elements, the inspectors determined that the deficiency had low degradation since less than 10 percent of the heads in the affected fire area were nonfunctional, a functional head remained within 10 feet of the combustibles of concern, and the system remained nominally code compliant. This finding screened as having very low safety significance (Green) in Phase 1of Manual Chapter 0609, Appendix F. This finding has a cross-cutting aspect in the area of human performance associated with resources because the procedure used to inspect the condition of these sprinklers did not contain specific criteria for identifying unacceptable sprinkler conditions. |
Site: | Grand Gulf |
---|---|
Report | IR 05000416/2011003 Section 1R05 |
Date counted | Jun 30, 2011 (2011Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | J Drake M Baquera R Kumana R Smith V Gaddy A Fairbanks B Rice E Uribe J Braisted |
CCA | H.7, Documentation |
INPO aspect | WP.3 |
' | |