Semantic search

Jump to navigation Jump to search
Condition
Printout selection
Options
Parameters [
limit:

The maximum number of results to return
offset:

The offset of the first result
link:

Show values as links
headers:

Display the headers/property names
mainlabel:

The label to give to the main page name
intro:

The text to display before the query results, if there are any
outro:

The text to display after the query results, if there are any
searchlabel:

Text for continuing the search
default:

The text to display if there are no query results
class:

An additional CSS class to set for the table
transpose:

Display table headers vertically and results horizontally
sep:

The separator between results
prefix:

Control display of namespace in printouts
Sort options
Delete
Add sorting condition
 Issue dateTitleTopic
05000000/LER-1950-237, Updated LER 50-237/01L:on 760406,unacceptable Ultrasonic Indication Found on Isolation Condenser safe-end.Caused by Cracks in safe-ends.Cracked safe-end Removed & Sent to Bmcl for Metallographic Analysis13 July 1976Updated LER 50-237/01L:on 760406,unacceptable Ultrasonic Indication Found on Isolation Condenser safe-end.Caused by Cracks in safe-ends.Cracked safe-end Removed & Sent to Bmcl for Metallographic Analysis
05000000/LER-1977-005, Updated LER 77-005/1T:on 770114,failure of High Pressure Svc Water/Emergency Svc Water & Emergency Cooling Water Pumps to Meet FSAR Seismic Requirements Noted.Caused by Change in Calculation Techniques28 January 1977Updated LER 77-005/1T:on 770114,failure of High Pressure Svc Water/Emergency Svc Water & Emergency Cooling Water Pumps to Meet FSAR Seismic Requirements Noted.Caused by Change in Calculation Techniques
05000000/LER-1986-001, Partially Deleted LER 86-001-00:on 860105,loss of Dynamic Reporting of Vital Door Activity Occurred.Cause & Corrective Action Completely Deleted10 January 1986Partially Deleted LER 86-001-00:on 860105,loss of Dynamic Reporting of Vital Door Activity Occurred.Cause & Corrective Action Completely Deleted
05000000/LER-1986-002, Partially Deleted LER 86-002-00:on 860117,loss of Alarm Surveillance on Doors Occurred.Caused by Erroneously Listing Officer as Being Posted on Door 398.Processing of Rev to Physical Security Plan Initiated23 January 1986Partially Deleted LER 86-002-00:on 860117,loss of Alarm Surveillance on Doors Occurred.Caused by Erroneously Listing Officer as Being Posted on Door 398.Processing of Rev to Physical Security Plan Initiated
05000000/LER-1986-003, Partially Deleted LER 86-003-00:on 860125,loss of Dynamic Reporting of Vital Area Door Activity Occurred.Caused by Equipment Malfunction.Corrective Action Withheld29 January 1986Partially Deleted LER 86-003-00:on 860125,loss of Dynamic Reporting of Vital Area Door Activity Occurred.Caused by Equipment Malfunction.Corrective Action Withheld
05000000/LER-1986-004, Partially Deleted LER 86-004-01:on 860204,loss of Dynamic Reporting of Alarm Surveillance Occurred.Cause Withheld. Computer Svcs Personnel Will Continue to Monitor Sys for Indicators of Cause11 June 1986Partially Deleted LER 86-004-01:on 860204,loss of Dynamic Reporting of Alarm Surveillance Occurred.Cause Withheld. Computer Svcs Personnel Will Continue to Monitor Sys for Indicators of Cause
05000000/LER-1986-007, Partially Deleted LER 86-007-01:on 860218,loss of Alarm Surveillance Occurred.Caused by Water Leaking Into Cable Due to Heavy Rain.Cable Dried,Leak Repaired & Design Corrected6 October 1986Partially Deleted LER 86-007-01:on 860218,loss of Alarm Surveillance Occurred.Caused by Water Leaking Into Cable Due to Heavy Rain.Cable Dried,Leak Repaired & Design Corrected
05000000/LER-1986-009, Ro:On 860312,discovered That LER 2-86-04 & LER 86-009 Not Submitted to Nrc.Caused by Misplaced Repts.Repts Telecopied to Nrc.Procedure for Distribution of Repts Revised14 April 1986Ro:On 860312,discovered That LER 2-86-04 & LER 86-009 Not Submitted to Nrc.Caused by Misplaced Repts.Repts Telecopied to Nrc.Procedure for Distribution of Repts Revised
05000000/LER-1986-011, Partially Deleted LER 86-011-00:on 860410,vital Area Intrusion Alarm Failure Occurred.Cause of Event Deleted. Alarm & Door Tested Satisfactorily15 April 1986Partially Deleted LER 86-011-00:on 860410,vital Area Intrusion Alarm Failure Occurred.Cause of Event Deleted. Alarm & Door Tested Satisfactorily
05000000/LER-1986-012, Partially Deleted LER 86-012-00:on 860412,breach Discovered in Protected Area Barrier.Caused by Personnel Error. Personnel Counseled17 April 1986Partially Deleted LER 86-012-00:on 860412,breach Discovered in Protected Area Barrier.Caused by Personnel Error. Personnel Counseled
05000000/LER-1986-013, Partially Deleted LER 86-013-00:on 860414,vital Area Door W/O Alarm Capability Discovered.Caused by Personnel Error. Personnel Removed from Shift & Vital Area Checked for Unauthorized Personnel W/None Being Found18 April 1986Partially Deleted LER 86-013-00:on 860414,vital Area Door W/O Alarm Capability Discovered.Caused by Personnel Error. Personnel Removed from Shift & Vital Area Checked for Unauthorized Personnel W/None Being Found
05000000/LER-1986-014, Partially Deleted LER 86-014-00:on 860421,bomb Threat Received by Security Officer in Security Assembly Room. Cause Not Applicable.Actions Taken to Minimize Station Threat & Investigation Underway25 April 1986Partially Deleted LER 86-014-00:on 860421,bomb Threat Received by Security Officer in Security Assembly Room. Cause Not Applicable.Actions Taken to Minimize Station Threat & Investigation Underway
05000000/LER-1986-015, Partially Deleted LER 86-015-00:on 860428,stationary Side of Door Failed to Alarm When Tested.Cause Withheld.Alarm Repaired2 May 1986Partially Deleted LER 86-015-00:on 860428,stationary Side of Door Failed to Alarm When Tested.Cause Withheld.Alarm Repaired
05000000/LER-1986-016, Partially Deleted LER 86-016-00:on 860501,vital Area Door Discovered W/O Alarm Capabilities.Caused by Access Control Security Officer Asleep at Post.Determination to Suspend or Discontinue Employment Being Made6 May 1986Partially Deleted LER 86-016-00:on 860501,vital Area Door Discovered W/O Alarm Capabilities.Caused by Access Control Security Officer Asleep at Post.Determination to Suspend or Discontinue Employment Being Made
05000000/LER-1986-020, Partially Deleted LER 86-020-00:on 860812,security Sys Experienced Loss of Power.Caused Withheld.Numerous Failures Experienced Until Machine a Designated as Prime.Procedures to Reboot Computers Revised15 August 1986Partially Deleted LER 86-020-00:on 860812,security Sys Experienced Loss of Power.Caused Withheld.Numerous Failures Experienced Until Machine a Designated as Prime.Procedures to Reboot Computers Revised
05000000/LER-1986-021, Partially Deleted LER 86-021-00:on 860911,vital Area Doors Failed to Alarm When Tested During Surveillance.Caused by Failure to Report Door Transactions to Host Computer.Central Procesing Unit Board Replaced15 September 1986Partially Deleted LER 86-021-00:on 860911,vital Area Doors Failed to Alarm When Tested During Surveillance.Caused by Failure to Report Door Transactions to Host Computer.Central Procesing Unit Board Replaced
05000000/LER-1986-022, Partially Deleted LER 86-022-02:on 861018,potential Undetected Access Into Vital Area Discovered.Caused by Use of Incorrect Procedure.Card Reader Replaced & Tested to Ensure Proper Operation20 February 1987Partially Deleted LER 86-022-02:on 861018,potential Undetected Access Into Vital Area Discovered.Caused by Use of Incorrect Procedure.Card Reader Replaced & Tested to Ensure Proper Operation
05000000/LER-1986-023, Partially Deleted LER 86-023-01:on 861023,unauthorized Access Into Vital Area Door Discovered.Caused by Card Reader Malfunction.Malfunctioning Card Reader Replaced.Cause Still Under Investigation21 November 1986Partially Deleted LER 86-023-01:on 861023,unauthorized Access Into Vital Area Door Discovered.Caused by Card Reader Malfunction.Malfunctioning Card Reader Replaced.Cause Still Under Investigation
05000000/LER-1986-024, Partially Deleted LER 86-024-00:on 861113,attempted Introduction of Unauthorized Weapon Into Protected Area Discovered.Caused by Personnel Attempt to Enter Plant W/ Concealed Gun.Personnel Denied Facility Access18 November 1986Partially Deleted LER 86-024-00:on 861113,attempted Introduction of Unauthorized Weapon Into Protected Area Discovered.Caused by Personnel Attempt to Enter Plant W/ Concealed Gun.Personnel Denied Facility Access
05000000/LER-1986-026, Partially Deleted LER 86-026-00:on 861124,vital Area Door Discovered W/O Alarm Capability.Caused by Personnel Error. Secutiry Officer in Question Terminated & Function of Administrative Sergeant Reviewed1 December 1986Partially Deleted LER 86-026-00:on 861124,vital Area Door Discovered W/O Alarm Capability.Caused by Personnel Error. Secutiry Officer in Question Terminated & Function of Administrative Sergeant Reviewed
05000000/LER-1986-030, Partially Deleted LER 86-030-00:on 861211,unauthorized Opening Into Protected Area Discovered.Caused by Area Not Properly Identified as Area for Security Concern.Signs Posted16 December 1986Partially Deleted LER 86-030-00:on 861211,unauthorized Opening Into Protected Area Discovered.Caused by Area Not Properly Identified as Area for Security Concern.Signs Posted
05000000/LER-1986-052, Partially Withheld LER 86-052-01:on 860926,security Data Mgt Sys Computer Terminals Became Inoperable (Ref 10CFR73.21). Caused by Overload of Alarms & Sys Instability.Sys Restored by Placing Sys Multiplexers Online13 November 1986Partially Withheld LER 86-052-01:on 860926,security Data Mgt Sys Computer Terminals Became Inoperable (Ref 10CFR73.21). Caused by Overload of Alarms & Sys Instability.Sys Restored by Placing Sys Multiplexers Online
05000259/LER-1980-031, Updated LER 80-031/03X-1:on 820415,during 4 Kv Shutdown Bus 2 Transfer,Fault on Normal Feeder Bus from TS1B to 480-volt SD Bd 1B Caused Loss of Power to Board.Caused by Fault Condition at Busway Joint Above Board1 June 1982Updated LER 80-031/03X-1:on 820415,during 4 Kv Shutdown Bus 2 Transfer,Fault on Normal Feeder Bus from TS1B to 480-volt SD Bd 1B Caused Loss of Power to Board.Caused by Fault Condition at Busway Joint Above Board
05000259/LER-1982-018, Updated LER 82-018/03X-1:on 820317,inspector Observed Bolts Missing from Reactor Core Isolation Cooling Turbine Exhuast Rupture Diaphragm Assembly.Outer Rupture Diaphragm Missing. Caused by Failure to Install Outer Rupture Disc1 June 1982Updated LER 82-018/03X-1:on 820317,inspector Observed Bolts Missing from Reactor Core Isolation Cooling Turbine Exhuast Rupture Diaphragm Assembly.Outer Rupture Diaphragm Missing. Caused by Failure to Install Outer Rupture Disc
05000259/LER-1982-023, Followup LER 82-023/03X-2:on 820327,recirculation Pump 1A Tripped Due to Spurious Generator Starter Relay Operation. Caused by Hi-temp Relay Trip.Relay Reset in 20 Minutes & Pump Returned to Svc.No Recurrence Control Planned13 October 1982Followup LER 82-023/03X-2:on 820327,recirculation Pump 1A Tripped Due to Spurious Generator Starter Relay Operation. Caused by Hi-temp Relay Trip.Relay Reset in 20 Minutes & Pump Returned to Svc.No Recurrence Control Planned
05000259/LER-1982-039, Reissued LER 82-039/03L-0:on 820609,fuse Blew Resulting in Inboard Primary Containment Isolation.Caused by Shorted Coil for Relay 16A-K66B,GE Type CR120A.Fuse & Relay Coil Replaced & Hydrogen Analyzers Returned to Normal6 July 1982Reissued LER 82-039/03L-0:on 820609,fuse Blew Resulting in Inboard Primary Containment Isolation.Caused by Shorted Coil for Relay 16A-K66B,GE Type CR120A.Fuse & Relay Coil Replaced & Hydrogen Analyzers Returned to Normal
05000259/LER-1982-064, Updated LER 82-064/03X-1:on 820823 & Jan 1984,Station II Cable Tray Fixed Spray Sys Did Not Meet Tech Spec Requirements.Caused by Restriction in Supply Line Strainer Due to Buildup of Silt & Clam Shells20 April 1984Updated LER 82-064/03X-1:on 820823 & Jan 1984,Station II Cable Tray Fixed Spray Sys Did Not Meet Tech Spec Requirements.Caused by Restriction in Supply Line Strainer Due to Buildup of Silt & Clam ShellsFire Watch
05000259/LER-1982-089, Updated LER 82-089/03T-1:on 821103,primary Containment Purge Sys Failed to Achieve Required Flow Rate.Caused by Sand Dust Clogging HEPA Filters.New Filters Installed8 April 1983Updated LER 82-089/03T-1:on 821103,primary Containment Purge Sys Failed to Achieve Required Flow Rate.Caused by Sand Dust Clogging HEPA Filters.New Filters Installed
05000259/LER-1983-018, Updated LER 83-018/031-2:on 830325,while Performing SI 4.2.A-13,standby Gas Train B Found Inoperable.Caused by Erratic Mcdonnel & Miller Flow Switch.Switch Replaced & SI 4.7.B-1 & SI 4.7.A-13 Completed27 July 1984Updated LER 83-018/031-2:on 830325,while Performing SI 4.2.A-13,standby Gas Train B Found Inoperable.Caused by Erratic Mcdonnel & Miller Flow Switch.Switch Replaced & SI 4.7.B-1 & SI 4.7.A-13 Completed
05000259/LER-1983-029, Updated LER 83-029/03L-1:on 830604,during Standby Gas Treatment Sys Operability Test,Train B Discovered Inoperable.Caused by Erratic Mcdonnel & Miller Model AF-1 Flow Switches.Damper Adjusted.W/Undated Ltr27 February 1984Updated LER 83-029/03L-1:on 830604,during Standby Gas Treatment Sys Operability Test,Train B Discovered Inoperable.Caused by Erratic Mcdonnel & Miller Model AF-1 Flow Switches.Damper Adjusted.W/Undated Ltr
05000259/LER-1983-066, Updated LER 83-066/03X-1:on 831112,interlock That Prevents Bridge Travel Over Core W/One Rod Withdrawn & Fuel Grapple Extended Failed to Operate,Resulting in Loss of Rod Block Function.Caused by Improper adjustment.W/840309 Ltr9 March 1984Updated LER 83-066/03X-1:on 831112,interlock That Prevents Bridge Travel Over Core W/One Rod Withdrawn & Fuel Grapple Extended Failed to Operate,Resulting in Loss of Rod Block Function.Caused by Improper adjustment.W/840309 Ltr
05000259/LER-1984-004, Updated LER 84-004-01:on 840106,reactor Mode Switch Moved from Run to Startup,Causing Half Scram.Caused by Personnel Error.Unit Manually Scrammed.Operator & Nuclear Engineer Counseled Re Use of Rod Notch Override11 April 1984Updated LER 84-004-01:on 840106,reactor Mode Switch Moved from Run to Startup,Causing Half Scram.Caused by Personnel Error.Unit Manually Scrammed.Operator & Nuclear Engineer Counseled Re Use of Rod Notch OverrideHalf scram
05000259/LER-1984-007, Followup LER 84-007-01:on 840127,operator Observed Decreasing Pressure on Control Atmospheric Dilution Tanks. Caused by Two Isolation Valves Being in Closed Position. Operating Instructions Revised2 March 1984Followup LER 84-007-01:on 840127,operator Observed Decreasing Pressure on Control Atmospheric Dilution Tanks. Caused by Two Isolation Valves Being in Closed Position. Operating Instructions Revised
05000259/LER-1984-014, Updated LER 84-014-01:on 840222,reactor Scrammed When Turbine High Pressure First Stage Pressure Exceeded 142 Psig W/Turbine Stop Valves Closed.Caused by Procedural Error. Operating Instruction Revised13 March 1984Updated LER 84-014-01:on 840222,reactor Scrammed When Turbine High Pressure First Stage Pressure Exceeded 142 Psig W/Turbine Stop Valves Closed.Caused by Procedural Error. Operating Instruction Revised
05000259/LER-1984-022, Updated LER 84-022-01:on 840212,investigation Determined That Single Failure or LOCA & Loss of Offsite Power Could Cause Equipment Necessary for Electrical Board Room Cooling to Be Lost.Caused by Design Oversight20 July 1984Updated LER 84-022-01:on 840212,investigation Determined That Single Failure or LOCA & Loss of Offsite Power Could Cause Equipment Necessary for Electrical Board Room Cooling to Be Lost.Caused by Design Oversight
05000259/LER-1985-049, Corrected Page 1 to LER 85-049-00:on 850623,during Performance of Work on Diesel Generator Battery Racks, Several Rack Support Studs Found Broken.Caused by Use of Stud Matl Not Suitable for Welding25 October 1985Corrected Page 1 to LER 85-049-00:on 850623,during Performance of Work on Diesel Generator Battery Racks, Several Rack Support Studs Found Broken.Caused by Use of Stud Matl Not Suitable for Welding
05000259/LER-1985-054, Advises That LER 85-054-00 Cancelled10 February 1986Advises That LER 85-054-00 Cancelled
05000260/LER-1981-052, Updated LER 81-052/03X-1:on 811007,containment Atmosphere Hydrogen Analyzer B Sample Return Pump Discovered Cycling. Probably Caused by Randon Failure.Gas Calibr Performed & Analyzer Returned to Svc12 April 1982Updated LER 81-052/03X-1:on 811007,containment Atmosphere Hydrogen Analyzer B Sample Return Pump Discovered Cycling. Probably Caused by Randon Failure.Gas Calibr Performed & Analyzer Returned to Svc
05000260/LER-1982-010, Corrected LER 82-010/03L-0 on 811021,during Full Power,Avg Power Range Monitor Output Signal Calibr Was Not Performed within Required Frequency During 811014-28.Caused by Personnel Error.Personnel Instructed to Be More Careful4 March 1982Corrected LER 82-010/03L-0 on 811021,during Full Power,Avg Power Range Monitor Output Signal Calibr Was Not Performed within Required Frequency During 811014-28.Caused by Personnel Error.Personnel Instructed to Be More Careful
05000260/LER-1982-013, Updated LER 82-013/03X-1:on 820412,pressure Switch 2-PS-68-96 Found to Operate Above Tech Spec Limits.Caused by Drifted Calibr.Barton Model 288 Pressure Switch Recalibr, Functionally Tested & Returned to Svc1 June 1982Updated LER 82-013/03X-1:on 820412,pressure Switch 2-PS-68-96 Found to Operate Above Tech Spec Limits.Caused by Drifted Calibr.Barton Model 288 Pressure Switch Recalibr, Functionally Tested & Returned to Svc
05000260/LER-1982-028, Followup LER 82-028/03X-3:on 810921,turbine Reactor Bldg Doors 237 & 238 Opened Simultaneously,Breaching Secondary Containment.Caused by Failed Folger Adams Interlock Sys Due to Loose Door Latch Screws.Procedures Revised9 March 1984Followup LER 82-028/03X-3:on 810921,turbine Reactor Bldg Doors 237 & 238 Opened Simultaneously,Breaching Secondary Containment.Caused by Failed Folger Adams Interlock Sys Due to Loose Door Latch Screws.Procedures Revised
05000260/LER-1983-074, Updated LER 83-074/03X-1:on 831105 & 10,turbine Exhaust Inner Rupture Diaphragms Failed During HPCI Initiation. Investigation Underway to Determine Cause of Failures. Diaphragms Replaced & HPCI Returned to Svc5 December 1983Updated LER 83-074/03X-1:on 831105 & 10,turbine Exhaust Inner Rupture Diaphragms Failed During HPCI Initiation. Investigation Underway to Determine Cause of Failures. Diaphragms Replaced & HPCI Returned to Svc
05000260/LER-1986-003, Corrected Page 2 to LER 86-003-00:on 860226,energized Isolation Logic Tripped.Caused by Personnel Error.Temporary Cover for Protection Against Accidental Bumping of Bus Transfer Switch Provided10 April 1986Corrected Page 2 to LER 86-003-00:on 860226,energized Isolation Logic Tripped.Caused by Personnel Error.Temporary Cover for Protection Against Accidental Bumping of Bus Transfer Switch Provided
05000296/LER-1979-005, Updated LER 79-005/01T-2:on 790506,RHR Svc Water Supply to RHR HX 2B Isolated Standby Coolant Supply.Caused by Lack of Administrative Control Over Sys Cross Connect Valves. Controls Improved27 April 1984Updated LER 79-005/01T-2:on 790506,RHR Svc Water Supply to RHR HX 2B Isolated Standby Coolant Supply.Caused by Lack of Administrative Control Over Sys Cross Connect Valves. Controls Improved
05000296/LER-1983-026, Supplemental LER 83-026/03X-4:on 830411,while Attempting to Establish EECW Flow Rate to Emergency Diesel Generator 3 Coolers,Head on HX Found Cracked.Caused by Mfg Defect.Cast Iron Head Replaced25 November 1983Supplemental LER 83-026/03X-4:on 830411,while Attempting to Establish EECW Flow Rate to Emergency Diesel Generator 3 Coolers,Head on HX Found Cracked.Caused by Mfg Defect.Cast Iron Head ReplacedHydrostatic
05000296/LER-1984-004, Followup LER 84-004-01:on 840228,RHR Outboard Loop II Isolation Valve CFV-74-67 Stem Found Broken Upon Disassembly.Caused by Overloading.Valve Stem Replaced W/Stronger & More Durable Matl15 June 1984Followup LER 84-004-01:on 840228,RHR Outboard Loop II Isolation Valve CFV-74-67 Stem Found Broken Upon Disassembly.Caused by Overloading.Valve Stem Replaced W/Stronger & More Durable Matl
05000327/LER-1982-0701 July 1982LER 82-070/01T-0:on 820618,discovered Possible Inoperability of Containment Sump Level Instrument Loops in Event of Loca.Possibly Caused by Increased Temps Rupturing Sensor Bellows.Procedures Revised
05000327/LER-1982-126, Revised LER 82-126/01T-1:on 821105,check Valve Downstream of MSIV Failed.Caused by Valve Disc Separating from Stem & Lodging Downstream in Steam Dump Header.Disc Retrieved & Replaced30 March 1983Revised LER 82-126/01T-1:on 821105,check Valve Downstream of MSIV Failed.Caused by Valve Disc Separating from Stem & Lodging Downstream in Steam Dump Header.Disc Retrieved & Replaced
05000327/LER-1983-122, Updated LER 83-122/03X-1:on 830927 & 28,diesel Generator 2A-A Declared Inoperable Due to Failure to Maintain Load of 4,400 Kw During Surveillance Testing.Caused by Faulty Exciter1 November 1983Updated LER 83-122/03X-1:on 830927 & 28,diesel Generator 2A-A Declared Inoperable Due to Failure to Maintain Load of 4,400 Kw During Surveillance Testing.Caused by Faulty Exciter
05000327/LER-1993-01911 August 1993LER 93-019-00:on 930713,containment Isolation Occurred Due to Inaccurate Drawing Used to Develop Clearance Boundary. Returned Valves to Normal Positions & Restored Sys Air pressure.W/930811 LtrSafe Shutdown