~~ CONTAINMENT SYSTEMS . | |||
. \-) | |||
3/4.6.2 DEPRESSURIZATION AND COOLING SYSTDiS CONTAINMENT ~ QUENCH SPRAY SYSTDi | |||
' | |||
LIMITING CONDITIONS FOR OPERATION 3.6.2.1 Two-separate and-independent containment quench .= pray subsystems shall be OPERABLE. | |||
APPLICABILITY: MODES 1, 2, 3 and 4. | |||
rACTION: | |||
'With one containment quench spray subsystem inoperable, restore the inoperable subsystem to OPERABLE 6tatus within 72 hours or be in at least HOT STANDBY within the next 6 hours and in COLD SHUTDOWN within the following 30 hours. | |||
SURVEILLANCE REQUIRDiENTS 4.6.2.1 Each containment quench spray subsystem shall be demonstrated OPERABLE: | |||
: a. At least once per 31 days by: | |||
: 1. Starting each spray pump. | |||
*2. Verifying, that on recirculation flow, when tested in accordance with the requirements of proposed Section 4.0.5, each quench spray pump develops a discharge pressure of 2; psig at a flow of > gpm and 3; psig at a flow of 2; gpm in the throttled mode. | |||
: 3. Verifying that each spray pump operates for at least 15 minutes. | |||
: 4. Cycling each testable power operated or automatic valve in | |||
' | |||
the flow path through at least one complete cycle of full travel. | |||
* Values to be determined l | |||
BEAVER VALLEY - UNIT 1- 3/4 6-11 8'00 708 00BY . . . . - - . | |||
BV-1 s..- | |||
ATTACHMENT B | |||
. | |||
CONTAINMENT SYSTDfS 3/4.6.2 DEPRESSURIZATION AND COOLING SYSTEMS . | |||
CONTAINMENT QUENCH SPRAY SYSTDi | |||
. | |||
LIMITING CONDITION FOR OPERATION 3.6.2.1 Two separate and independent containment quench spray subsystems shall be OPERA 3LE. | |||
APPLICABILITY: MODES 1, 2, 3.an'd .4. | |||
ACTION: | |||
With one containment quench spray rubsystem inoperable, restore the inoperable subsystem to OPERABLE status within 72 hours or be in at least HOT STANDBY within-the next 6 hours and in COLD SHUTDOWN within the following 30 hours. | |||
~ | |||
SURVEILLANCE REOUIREMENTS 4.6.2.1 Each containment quench spray subsystem shall be demotistrated OPERABLE: | |||
: a. At least once per 31 days by: | |||
: 1. Starting each spray pump. | |||
: 2. Verifying, that or recirculation flow, when tested in accordance with the requirements of proposed Section 4.0.5, each quench spray pump develops a discharge pressure of > 153 psig at a flow of > 1550 gpm. | |||
: 3. Verifying that each spray pump operates for at least 15 minutes. | |||
' | |||
: 4. Cycling each testable power operated or automatic valve in the flow path through at least one complete cycle of full travel. | |||
. | |||
s BEAVER VALLEY - UNIT 1 3/4.6-11' | |||
- | |||
. | |||
o | |||
; | |||
. | |||
. | |||
, | |||
. | |||
. | |||
- | |||
. | |||
. | |||
. . | |||
- QUENCH SPRAY RING, A A a - | |||
CHE MICAL | |||
--~- al'!e' ,".) | |||
V V v LOOP SEAL j WOV REFUEllNG WATER | |||
, RECIRCULATING PIPING ADDITION (EXISTlNG) STORACE TANK , | |||
' | |||
> SPR AY RING L (RWST) --CH3-- - q | |||
( ' | |||
C [- - ---~ 7 l ,_ _ _.i i_ _ _ = > | |||
i . | |||
, , | |||
l 1. / FLOW I | |||
; | |||
--- TRANSMITTER I c ) r- - % t" ~l l ORIFICE (ggg) | |||
J. | |||
V, RECIRCULATING SPRAY RlHG c y / | |||
(EXISTING) ] w- | |||
* I 4l I | |||
l o a_ i e | |||
: | |||
,___I_ > . | |||
- > ,, ,,,,,, . l | |||
, | |||
X 7i f (RiriCEU_ | |||
O NEW) -- | |||
< | |||
s i | |||
> ; | |||
- | |||
, | |||
- | |||
r" - - | |||
f ~ | |||
u i | |||
! | |||
l | |||
' ' ' CHEMICAL | |||
* l l l l '~''] X TEST LINE | |||
"*S' l INJECTION 8 (j | |||
' | |||
l l | |||
' | |||
lo ol %E0i lo o l i | |||
' | |||
l---rs-__----> J | |||
~ | |||
i i N/ 1 W v . Og,r. | |||
----- W '* .h .MOV | |||
, z r ,,, | |||
_4lp ., ' | |||
. | |||
REACTOR I - | |||
ggy CONTAINMENT l l MOV i (EXISTING) I Q l I | |||
(EXISTING) | |||
' | |||
' b MOV | |||
* | |||
*b (NEW) | |||
* OUTSIDE INSIDE . QUENCH ' | |||
! R.S. PUM P R.S. PUMP SPRAY PUMP | |||
' | |||
(EXISTING) (EXISTING) (NEW IMPELLER) | |||
- | |||
, | |||
' | |||
. | |||
FIGURE 2 i Revisions. LEGEND RS & QS SYSTEM MODIFICATIONS | |||
: 11/17/ 7 7 - REVISION O --- NEw BEAVER VALLEY-UNIT 1 | |||
) 9 /4/79 - REVISION 1 - | |||
, | |||
DUQUESNE LIGHT CO. | |||
' | |||
I / 2/80 - REVISION 2 6/11/80 - REVISION 3 l | |||
: | |||
; | |||
_ - _ _ _ _ - _ _ - - - - - - _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ - _ _ _ -}} |
Revision as of 02:12, 18 December 2019
ML19320A870 | |
Person / Time | |
---|---|
Site: | Beaver Valley |
Issue date: | 07/03/1980 |
From: | DUQUESNE LIGHT CO. |
To: | |
Shared Package | |
ML19320A869 | List: |
References | |
TAC-7170, NUDOCS 8007080084 | |
Download: ML19320A870 (3) | |
Text
_ _ _ _ _ _ - - _ _ _ _ _
.-..*
'
.
~~ CONTAINMENT SYSTEMS .
. \-)
3/4.6.2 DEPRESSURIZATION AND COOLING SYSTDiS CONTAINMENT ~ QUENCH SPRAY SYSTDi
'
LIMITING CONDITIONS FOR OPERATION 3.6.2.1 Two-separate and-independent containment quench .= pray subsystems shall be OPERABLE.
APPLICABILITY: MODES 1, 2, 3 and 4.
rACTION:
'With one containment quench spray subsystem inoperable, restore the inoperable subsystem to OPERABLE 6tatus within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
SURVEILLANCE REQUIRDiENTS 4.6.2.1 Each containment quench spray subsystem shall be demonstrated OPERABLE:
- a. At least once per 31 days by:
- 1. Starting each spray pump.
- 2. Verifying, that on recirculation flow, when tested in accordance with the requirements of proposed Section 4.0.5, each quench spray pump develops a discharge pressure of 2; psig at a flow of > gpm and 3; psig at a flow of 2; gpm in the throttled mode.
- 3. Verifying that each spray pump operates for at least 15 minutes.
- 4. Cycling each testable power operated or automatic valve in
'
the flow path through at least one complete cycle of full travel.
- Values to be determined l
BEAVER VALLEY - UNIT 1- 3/4 6-11 8'00 708 00BY . . . . - - .
BV-1 s..-
ATTACHMENT B
.
CONTAINMENT SYSTDfS 3/4.6.2 DEPRESSURIZATION AND COOLING SYSTEMS .
CONTAINMENT QUENCH SPRAY SYSTDi
.
LIMITING CONDITION FOR OPERATION 3.6.2.1 Two separate and independent containment quench spray subsystems shall be OPERA 3LE.
APPLICABILITY: MODES 1, 2, 3.an'd .4.
ACTION:
With one containment quench spray rubsystem inoperable, restore the inoperable subsystem to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within-the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
~
SURVEILLANCE REOUIREMENTS 4.6.2.1 Each containment quench spray subsystem shall be demotistrated OPERABLE:
- a. At least once per 31 days by:
- 1. Starting each spray pump.
- 2. Verifying, that or recirculation flow, when tested in accordance with the requirements of proposed Section 4.0.5, each quench spray pump develops a discharge pressure of > 153 psig at a flow of > 1550 gpm.
- 3. Verifying that each spray pump operates for at least 15 minutes.
'
- 4. Cycling each testable power operated or automatic valve in the flow path through at least one complete cycle of full travel.
.
s BEAVER VALLEY - UNIT 1 3/4.6-11'
-
.
o
.
.
,
.
.
-
.
.
. .
- QUENCH SPRAY RING, A A a -
CHE MICAL
--~- al'!e' ,".)
V V v LOOP SEAL j WOV REFUEllNG WATER
, RECIRCULATING PIPING ADDITION (EXISTlNG) STORACE TANK ,
'
> SPR AY RING L (RWST) --CH3-- - q
( '
C [- - ---~ 7 l ,_ _ _.i i_ _ _ = >
i .
, ,
l 1. / FLOW I
--- TRANSMITTER I c ) r- - % t" ~l l ORIFICE (ggg)
J.
V, RECIRCULATING SPRAY RlHG c y /
(EXISTING) ] w-
- I 4l I
l o a_ i e
,___I_ > .
- > ,, ,,,,,, . l
,
X 7i f (RiriCEU_
O NEW) --
<
s i
> ;
-
,
-
r" - -
f ~
u i
!
l
' ' ' CHEMICAL
- l l l l '~] X TEST LINE
"*S' l INJECTION 8 (j
'
l l
'
lo ol %E0i lo o l i
'
l---rs-__----> J
~
i i N/ 1 W v . Og,r.
W '* .h .MOV
, z r ,,,
_4lp ., '
.
REACTOR I -
ggy CONTAINMENT l l MOV i (EXISTING) I Q l I
(EXISTING)
'
' b MOV
- b (NEW)
- OUTSIDE INSIDE . QUENCH '
! R.S. PUM P R.S. PUMP SPRAY PUMP
'
(EXISTING) (EXISTING) (NEW IMPELLER)
-
,
'
.
FIGURE 2 i Revisions. LEGEND RS & QS SYSTEM MODIFICATIONS
- 11/17/ 7 7 - REVISION O --- NEw BEAVER VALLEY-UNIT 1
) 9 /4/79 - REVISION 1 -
,
DUQUESNE LIGHT CO.
'
I / 2/80 - REVISION 2 6/11/80 - REVISION 3 l
_ - _ _ _ _ - _ _ - - - - - - _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ - _ _ _ -