{{#Wiki_filter:APF 05-013-01, REV. 04 E-1F9905 FIRE HAZARD ANALYSIS ENGINEERING REVIEW:
{{#Wiki_filter:}}
DigsigOrg 2.8 0.45 DigsigCert 3.5 1.75 DRAFTER:
DigsigOrg 2.8 0.45 CHECKER:
DigsigVer 2.8 0.45 ENGINEER:
DigsigApp 2.8 0.45 SUPERVISOR:
ELECTRONIC APPROVAL
: 1. APPROVED-MFG. MAY PROCEED
: 2. NOT APPROVED--RESUBMIT FINAL DOCUMENT/DRAWING-MFG. MAY PROCEED                          YES  NO
: 3. APPROVED INFORMATION NOT CONTROLLED UNDER DESIGN PROCESS
: 4. ACCEPTABLE-MAINTAIN AS RECORD (INFO. ONLY)
: 5. RESTRICTED FOR WOLF CREEK PLANNING ONLY-MFG. MAY PROCEED                      YES          NO APPROVAL OF THIS DOCUMENT/DRAWING DOES NOT RELIEVE SUPPLIER/CONTRACTOR FROM FULL COMPLIANCE WITH CONTRACT, SPECIFICATIONS AND/OR PURCHASE ORDER REQUIREMENTS.
COMMENTS:
P.O.#:                          VENDOR MANUAL:
PAGE:
CHANGE PACKAGE #:              INCORPORATED CHANGE DOCUMENT(S):
012513                          WIP-E-1F9905-010-A-1 REV. #                                                                                              DC RELEASED:
DigsigDSR 3 0.50 DC7 07/29/2021 11 COMPONENT NUMBER(S)
COMPONENT NUMBERS ARE FOR INITIAL (REV, W01) DATA LINKING ONLY. ADDITIONAL COMPONENT LINKS ARE MADE IN DATABASE ONLY.
Page 1 of 281
 
Wolf Creek Nuclear Operating Corporation            Page 2 of 281 Fire Hazard Analysis TABLE OF CONTENTS 1.0    PURPOSE                                                3 2.0    SCOPE                                                  3
 
==3.0    REFERENCES==
3 4.0    FHA PROCESS                                            5 ATTACHMENT A PLANT FIRE AREAS PROVIDED WITH A FHA            16 ATTACHMENT B FIRE HAZARD ANALYSIS                            30 ATTACHMENT C NON-SAFETY RELATED SITE STRUCTURES              280
 
Wolf Creek Nuclear Operating Corporation                                                  Page 3 of 281 Fire Hazard Analysis 1.0      PURPOSE 1.1      The purpose of the Fire Hazard Analysis (FHA) is to provide an evaluation of the effects of postulated fires within Wolf Creek Generating Station (WCGS). The overall intent of the FHA is to demonstrate that any single plant fire will not negatively affect post fire safe shutdown (PFSSD) capability, or result in a radiation release that exceeds 10 CFR Part 20 limits. The analysis was performed to demonstrate that WCGS comparison requirements to 10 CFR 50 Appendix R are satisfied.
1.2      This document supersedes the WCGS FHA that was historically maintained within Appendix 9.5B (Sections 9.5B.7 and 9.5B.8) of the USAR.
2.0      SCOPE 2.1      FHA for each plant Fire Area identified in Attachment A. This includes all plant areas containing PFSSD equipment/circuits and non-safety plant areas that present a potential exposure hazard to areas containing PFSSD equipment/circuits due to proximity.
 
==3.0      REFERENCES==
 
3.1      BTP APCSB 9.5-1 Appendix A, Guidelines for Fire Protection for Nuclear Power Plants Docketed Prior to July 1, 1976 (USAR Appendix 9.5A) 3.2      10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior to January 1, 1979 (USAR Appendix 9.5E) 3.3      NRC Letter dated September 30, 1976 - Fire Protection Evaluation Wolf Creek Generating Station, Unit No. 1 3.4      NRC Letter dated October 21, 1981 - Appendix R of 10 CFR 50 Fire Protection Rule 3.5      NUREG-0881, Safety Evaluation Report Related to the Operation of Wolf Creek Generating Station Unit No. 1 3.6      NUREG/CR-4527, An Experimental Investigation of Internally Ignited Fires in Nuclear Power Plant Control Cabinets: Part 1: Cabinet Effects Tests 3.7      NUREG/CR-4527, An Experimental Investigation of Internally Ignited Fires in Nuclear Power Plant Control Cabinets: Part 2: Room Effects Tests 3.8      NUREG/CR-4596, Screening Tests of Representative Nuclear Power Plant Components Exposed to Secondary Environments Created by Fires, June 1986 3.9      NUREG/CR-6476, Circuit Bridging of Components By Smoke, October 1996 3.10    Regulatory Guide 1.29, Seismic Design Classification 3.11    Regulatory Guide 1.75, Physical Independence of Electric Systems 3.12    SLNRC 82-046, Fire Protection Review, dated November 15, 1982 [SNUPPS Control Room Fire Hazards Analysis]
3.13    SLNRC 84-109, Fire Protection Review, dated 8/23/1984 [Alternate Shutdown Response Plan]
 
Wolf Creek Nuclear Operating Corporation                                              Page 4 of 281 Fire Hazard Analysis 3.14    ASTM D 3286-1973, Standard Test Method for Gross Calorific Value of Coal and Coke by the Isoperibol Bomb Calorimeter 3.15    ASTM E 84-1976, Standard Test Method for Surface Burning Characteristics of Building Materials 3.16    ASTM E-119, Standard Test Methods for Fire Tests of Building Construction and Materials 3.17    ASTM E-152, Standard Methods of Fire Tests of Door Assemblies 3.18    UL-10B, Standard for Safety Fire Tests of Door Assemblies 3.19    UL-555, Standard for Fire Dampers 3.20    IEEE-383, Standard for Qualifying Class 1E Electric Cables and Field Splices for Nuclear Power Generating Stations 3.21    IEEE-634, Standard for Cable Penetration Fire Stop Qualification Test 3.22    DE88003808 (SAND87-2484C), Investigation of Smoke Corrosivity in Nuclear Power Plant Equipment 3.23    M-663-00017A, Fire Protection Evaluations for Unique or Unbounded Fire Barrier Configurations 3.24    AI 26A-003, Regulatory Evaluations (Other than 10 CFR 50.59) 3.25    AP 10-106, Fire Preplans 3.26    AP 15C-004, Preparation, Review, and Approval of Procedures, Instructions and Forms 3.27    E-15000, Electrical Cable and Raceway List 3.28    E-1F9900, Post Fire Safe Shutdown Manual Actions 3.29    E-1F9910, Post Fire Safe Shutdown Fire Area Analysis 3.30    XX-E-013, Post Fire Safe Shutdown Analysis 3.31    XX-X-004, Combustible Loading Information Program 3.32    Drawing Series A-1800, Fire Delineation 3.33    Drawing Series M-12LF, P&IDs for Hot Machine Shop, Auxiliary, Radwaste, Fuel, Control, and Reactor Buildings Floor and Equipment Drain System 3.34    Drawing Series M-12LE, P&IDs for Auxiliary Boiler Room, Turbine Building, Control Building, Diesel Generator Building, Tendon Access Gallery, and Auxiliary Feedwater Pump Rooms Oily Waste Drain System 3.35    Drawing E-11013, Installation, Inspection and Testing Details for Electrical Equipment and Cable 3.36    EPRI Technical Report TR-100370, Fire-Induced Vulnerability Evaluation (FIVE)
 
Wolf Creek Nuclear Operating Corporation                                                Page 5 of 281 Fire Hazard Analysis 3.37    PIR 2002-2246, Removal of Fire Protection Description from the USAR.
3.38    KC-M-006, Water-Based Fire Protection System and Standpipe System Hydraulic Calculations 4.0      FHA PROCESS 4.1      General 4.1.1    Attachment A identifies the following:
All plant Fire Areas that are provided with a FHA.
Rooms within each Fire Area.
Rooms provided with automatic detection.
Rooms provided with automatic suppression.
Rooms that are within the Radiological Controlled Area (RCA) during normal operations.
Rooms containing PFSSD circuits.
4.1.2      Attachment B documents the FHA for each Fire Area identified in Attachment A.
4.1.3      Attachment C identifies the Non-Safety Related Site Structures and their distance to the nearest structure containing PFSSD equipment and/or circuits.
These structures are remotely located from structures containing PFSSD equipment/circuits, and as such, a postulated fire within these structures does not pose a hazard to equipment and/or circuits required for PFSSD.
 
===4.2      Background===
4.2.1      The NRC originally requested that WCGS perform a fire hazard analysis for the facility in a {{letter dated|date=September 30, 1976|text=letter dated September 30, 1976}}. This letter also requested that a comparison to APCSB 9.5-1 Appendix A be provided. NRC {{letter dated|date=October 21, 1981|text=letter dated October 21, 1981}} requested that WCGS provide a comparison to 10 CFR 50 Appendix R. These requests were addressed via information provided within the following appendices of the SNUPPS Final Safety Analysis Report (FSAR) and WCGS Site Addendum:
Appendix 9.5A - Comparison to APCSB 9.5-1 Appendix A.
Appendix 9.5B - Fire Hazards Analysis.
Appendix 9.5E - Comparison to 10 CFR 50 Appendix R.
Additionally, a detailed report entitled SNUPPS Control Room Fire Hazard Analysis was submitted to the NRC by letter SLNRC 82-046. This report addressed transient fires originating between various panels in the Control Room.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 6 of 281 Fire Hazard Analysis Subsequent to the above Control Room FHA report, the criteria for a Control Room fire was modified by the NRC. In response to these changes, a new detailed report entitled SNUPPS Response Plan for Immediate Evacuation of the Control Room Due to Fire was submitted to the NRC via SLNRC 84-0109.
NRC questions from the 1977-79 time frame concerning fire protection information within the FSAR and WCGS Site Addendum (including the SNUPPS/Wolf Creek responses to the questions) were documented within FSAR Appendices 9.5C and 9.5D. A future revision to the FHA will provide a reference to the current document addressing the issue of concern. This revision will occur in parallel with the release of the Fire Protection Program Manual, which is being developed in response to PIR 2002-2246.
Ultimately the FHA and other supporting fire protection within the SNUPPS FSAR and WCGS Site Addendum received NRC approval, as documented in Operating License Condition 2.C.(5)(a).
Wolf Creek has historically maintained facility fire protection information within what is now termed the Updated Safety Analysis Report (USAR), which is a consolidation of the SNUPPS FSAR and WCGS Site Addendum. Revisions have been incorporated as necessary to address plant changes, including enhancements to the original response plan provided in SLNRC 84-0109 for Control Room evacuation.In effort to eliminate repetitive information and provide a more efficient and consistent means to update and control fire protection program documents, the majority of USAR Appendix 9.5B is superseded by this document. The extent of USAR Appendix 9.5A, 9.5B, and 9.5E incorporation within this document is as follows:
Appendix 9.5A - Comparison to APCSB 9.5-1 Appendix A Applicable elements of the comparison have been incorporated within this document. Specific paragraphs within this document that address an APCSB 9.5-1 Appendix A comparison issue are provided with a parenthetical reference to APCSB 9.5-1 Appendix A, including the respective paragraph number addressed. The current comparison provided in Appendix 9.5A of the USAR will remain active until release of the Fire Protection Program Manual, which is being developed in response to PIR 2002-2246.
Appendix 9.5B - Fire Hazards Analysis The entire appendix was incorporated into this document with the exception of the following:
                                      -    With limited exception, PFSSD analysis is documented in E-1F9910 with PFSSD supporting information provided by XX-E-013 and E-1F9900. PFSSD capability is specifically addressed within this document for Fire Areas KDB, RW, T-4, T-10, YARD-ESF, and YARD-SU, as these areas were not originally included in the USAR FHA.
                                      -    The evaluation of unique or unbounded fire barrier features, which is documented in M-663-00017A.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 7 of 281 Fire Hazard Analysis FHA revision was provided where necessary to eliminate redundancy, provide clarification, or to strengthen the existing analysis.
Appendix 9.5E - Comparison to 10 CFR 50 Appendix R Applicable elements of the comparison have been incorporated within this document. Specific paragraphs within this document that address an Appendix R comparison issue are provided with a parenthetical reference to Appendix R, including the respective paragraph number addressed. The current comparison provided in Appendix 9.5E of the USAR will remain active until release of the Fire Protection Program Manual, which is being developed in response to PIR 2002-2246.
4.3      Methodology 4.3.1      For each Fire Area analyzed in Attachment B, the topics identified in Sections 4.3.2 through 4.3.8 below, are addressed.
4.3.2      Fire Area Description
: 1. The Rooms within the Fire Area are identified.
4.3.3      Major Equipment
: 1. Major equipment within the Fire Area is identified.
4.3.4      Design Features
: 1. Fire boundary separation from other Fire Areas is discussed.
: a. Fire barrier features separating Fire Areas are 3-hour rated, unless otherwise indicated. Unique or unbounded fire barrier configurations are addressed in M-663-00017A.
: 2. Passive barrier features within the Fire Area are discussed, where applicable.
4.3.5      Combustible Loading
: 1. Significant fire hazards within the Fire Area are discussed, where applicable.
: 2. The cumulative fire hazard classification (Low, Moderate, or High) for the Fire Area is identified. This classification is based on the Room and Fire Area combustible loading tabulation maintained in calculation XX-X-004.
Unless indicated otherwise, the specific location of combustible material within a room is not a significant factor in the combustible loading analysis.
 
Wolf Creek Nuclear Operating Corporation                                                Page 8 of 281 Fire Hazard Analysis The three combustible loading classifications are defined as follows:
LOW:                < 100,000 Btu/ft2 MODERATE:          > 100,000 Btu/ft2 and < 200,000 Btu/ft2 HIGH:              > 200,000 Btu/ft2 Typical combustibles include Class A and Class B hazards. Class A hazards are ordinary combustible materials such as wood, paper, fabric, nylon, plastic, rubber, and cable insulation. Class B hazards are flammable and combustible liquids and gases such as cleaning solvent, diesel fuel oil, lube oil, oxygen, and acetylene.
A significant amount of fixed combustibles in the plant is electric cable insulation. The specific calorific value of each type and size of cable was used in calculating the maximum heat leading for each Fire Area.
Class A combustibles in closed metal containers located in general corridor areas of the plant may not be considered to contribute to the fuel load in that area. Their contribution is considered based on the adjacent combustible loads and the probability of a long duration fire.
Although fire hazard effects on exposed conduits have been evaluated for safe shutdown, electric cable inside metal conduit has not been considered as contributing to the fire loading in the hazard areas.
: 3. Combustible Control Zones that are administratively maintained to control transient combustibles in the separation area between redundant PFSSD components/circuits are discussed, where applicable.
: 4. In some instances cable chase fire loading is Moderate or High with an equivalent fire severity either near or exceeding three hours. This is the case due to the small floor area in relation to the combustibles presented by cable and postulated transient combustibles. Under normal situations, no ignition sources are present within cable chases, and introduction of a transient ignition source is administratively controlled. As previously identified, cable is IEEE-383 rated. Electric Power Research Institute (EPRI) technical report TR-100370, Fire-Induced Vulnerability Evaluation (FIVE), identifies that such cable is not typically considered a fire source initiator due to a low ignition frequency considering past nuclear power plant experience and fire tests. Based on this and the defense in depth fire protection features discussed in the applicable Fire Area analysis section, the development of a cable chase fire severity that would challenge fire barrier integrity is not considered credible.
: 5. Administrative controls are in place to limit the use and location of transient combustibles. Based on these limits, the maximum increased fire loading permitted in any fire area will not exceed the areas fire protection capabilities. Where transient combustibles exceed the amounts qualified in Calculation XX-X-004, additional administrative controls are implemented commensurate with the hazard.
 
Wolf Creek Nuclear Operating Corporation                                                Page 9 of 281 Fire Hazard Analysis 4.3.6      Fire Protection
: 1. Automatic detection features are discussed.
: a. Automatic fire and smoke detection systems are provided throughout the plant on the basis of the Attachment B fire hazards analysis and consequences of specific postulated fires. Attachment A identifies the automatic detection protection arrangement for each room that is encompassed within the Attachment B FHA. In each case the FHA considers the impact to safe shutdown where no or partial automatic detection is provided.
: 2. Automatic suppression features are discussed.
: a. Automatic suppression systems are provided in the plant on the basis of the Attachment B fire hazards analysis and consequences of specific postulated fires. Attachment A identifies the automatic suppression protection arrangement for each room that is encompassed within the Attachment B FHA. In each case the FHA considers the impact to safe shutdown where no or partial automatic suppression is provided.
: b. KC-M-006 calculates the fire water delivery system supply, sprinkler system demands, standpipe demands, and evaluates the overall hydraulic adequacy of the fire water suppression systems.
: 3. Typical fire alarm system annunciation is identified in Table 4.3.6.3.
: 4. Suppression equipment available in the area for manual fire fighting is discussed.
: 5. Fire Area accessibility is discussed.
: 6. Fire water drainage is discussed.
: a. All areas of the plant protected with water suppression systems have sufficient drainage capacity to prevent the run-off of water into other Fire Areas such that it would affect equipment operability. All drains throughout the plant drain to their respective building sumps, from there, sump pumps transfer the water to the radwaste system.
: b. The method by which sprinkler systems control fire is termed fire control approach. This method anticipates that a certain number of sprinklers will be opened surrounding the fire event area. All sprinkler heads installed in a given Fire Area will not open for a given fire event.
Table 16.3.1 from the NFPA Handbook (20th Edition) reveals that the majority of fires are suppressed by a small number of sprinkler heads (10 or less). Additionally, hose stream application for a fire event would be controlled and of a short duration.
 
Wolf Creek Nuclear Operating Corporation                                          Page 10 of 281 Fire Hazard Analysis Table 4.3.6.3, Typical Fire Alarm System Annunciation System Type and Condition                                Local              Control Room General Area Detection General area detection or manual pull                        X                      X station activated                        Area notification appliance(s)
Detector trouble or circuit fault                        None                      X Automatic Wet Pipe Sprinkler System discharge                                            X                      X Notification appliance controlled at local junction box.
Pressure switch circuit fault                            None                      X Automatic Preaction Sprinkler Detection activated                                          X                      X System discharge (automatic)            Notification appliance controlled by      X release panel, which is activated concurrent with system discharge System discharge (manual/pneumatic)                      None                      X Low supervisory air pressure                              None                      X General trouble condition                                None                      X Automatic Water Spray Sprinkler (Single Zoned Detection)
Detection activated                                          X                      X System discharge (automatic)            Notification appliance controlled by      X release panel, which is activated concurrent with system discharge System discharge (manual/pneumatic)                      None                      X General trouble condition                                None                      X Automatic Water Spray Sprinkler (Crossed Zoned Detection) 1st zone detector activated                                  X                      X Notification appliance controlled by release panel 2nd zone detector activated              Notification appliance already            X activated by 1st detector in alarm System discharge (automatic)                              None                      X System discharge (manual/pneumatic)                      None                      X General trouble condition                                None                      X Automatic Halon Suppression (Crossed Zoned Detection) 1st zone detector activated                                  X                      X Area notification appliance 2nd zone detector activated              Notification appliance already            X activated by 1st detector in alarm System discharge (automatic)                                X                      X Notification appliance controlled by release panel System discharge (manual/pneumatic)                          X                      X Notification appliance controlled by release panel HVAC isolation                                            None                      X Visual General trouble condition                                    X                      X Fire Water Valve Supervision Fire Water system isolation valve out of                  None                      X normal position Circuit fault                                            None                      X
 
Wolf Creek Nuclear Operating Corporation                                                    Page 11 of 281 Fire Hazard Analysis 4.3.7      Isolation and Smoke Removal
: 1. A description of fire isolation is provided.
: 2. AP 10-106, Fire Preplans, identifies fixed HVAC supply and exhaust fans servicing each Fire Area. Smoke removal tactics are dependent on several variables and fire ground conditions including wind patterns, fire intensity, smoke dispersion rate, location of the fire within the Fire Area, location of redundant PFSSD equipment, availability of normal exhaust, and power supply availability for portable ventilation. Therefore, it is not considered feasible to discuss each potential ventilation scenario within a given Fire Area. Portable ventilation strategies and tactics are addressed by the Fire Brigade training program.
NUREG/CR-4596 demonstrates that exposure to the corrosive products of a smoke environment can result in equipment damage. Therefore, the potential to expose redundant PFSSD equipment to a smoke environment is an important consideration during smoke control and removal activities.
However, corrosion from a secondary smoke environment is not expected to be a factor that impacts immediate PFSSD capability. This is substantiated by DE88003808 (SAND87-2484C), which identifies that corrosion from a smoke environment is an event that presents a problem on a time scale of days or even weeks. Additionally, NUREG/CR-6476 identifies that the most important fire scenarios from a plant risk perspective occur during time frames of roughly one hour or less. Thus, the issue of longer term exposures are more important to the question of general post-fire equipment reliability, which is ultimately a secondary concern to that of achieving initial safe shutdown.
4.3.8      Analysis
: 1. Fire Suppression
: a. A discussion of the fire suppression systems (fixed and manual) use and effectiveness in extinguishing a fire is provided.
: 2. Safe Shutdown Capability
: a. The safe shutdown design basis is the cold shutdown operational mode. If a fire hazard within the plant necessitates the plant being placed in a safe condition, the reactor will first be taken to a hot shutdown condition. An extended hot shutdown condition prior to achieving cold shutdown in order to perform repairs or temporary routings, if required, is a stable, safe condition.
: b. USAR Section 7.4 describes in detail how safe shutdown can be performed with safety related equipment, and provides a discussion of component redundancies and system diversity for achieving the safe shutdown functions. System and component redundancy for the various support and auxiliary systems is provided in the associated USAR section.
: c. The fuel storage pool cooling system components are listed as being required for safe shutdown for the fire hazards analysis of the Fuel
 
Wolf Creek Nuclear Operating Corporation                                                Page 12 of 281 Fire Hazard Analysis Building. However, they are neither required for safe shutdown nor are they associated circuits as defined in10 CFR 50 Appendix R, Section III.G. They have been included to ensure that repairs are not required for fires in the Fuel Building. Fuel storage pool cooling system component failures resulting from fires in the Auxiliary and Control Buildings are not evaluated in the FHA or E-1F9910.
: d. Associated circuits were reviewed as if they were redundant safe shutdown items.
: e. The determination of safe shutdown capability following a fire is based on the PFSSD Fire Area analysis documented in E-1F9910 and the PFSSD manual action feasibility analysis documented in E-1F9900, coupled with the FHA evaluation addressing fire hazards, fire protection features, and suppression capability. PFSSD capability is satisfied when analysis demonstrates that Wolf Creeks comparison response to 10 CFR 50 Appendix R, Section III.G is met.
4.4      Assumptions 4.4.1      The following assumptions were made in accordance with 10 CFR 50 Appendix R, to define the plant conditions for analysis purposes:
: 1. Only one fire is postulated to occur at any one time. Multiple fires are not postulated.
: 2. A design basis accident occurring simultaneously with a fire hazard is not assumed.
: 3. Extreme environmental phenomena, i.e., earthquake, flood, tornado, etc.,
occurring simultaneously with fire hazard are not assumed.
: 4. Failure of plant systems and components required for safe shutdown is not postulated unless that equipment is exposed to the fire. Wolf Creeks comparison response to Section III.G.2 of Appendix R is considered to provide an acceptable means to protect redundant safe shutdown equipment. Random single failures are not postulated in safe shutdown systems; only fire-related failures are evaluated. It should be noted that where automatic fire suppression systems are installed, the fire hazards analysis evaluates the effects of a failure of the automatic systems.
: 5. Loss of offsite power (LOSP) is assumed to occur simultaneously with the fire unless the area has been specifically evaluated to show that a LOSP could not occur as a result of the fire. For alternate shutdown, a LOSP is considered a simultaneous event. Failure of any of the onsite vital power supplies is not assumed unless it is caused as a direct consequence of a fire. Calculation XX-E-013 identifies the Fire Areas were LOSP due to fire is possible.
: 6. Refer to XX-E-013 and E-1F9910 for additional assumptions that are specific to the PFSSD analysis.
4.5      Fire Effects on Electrical Equipment and Safe Shutdown Information
 
Wolf Creek Nuclear Operating Corporation                                                  Page 13 of 281 Fire Hazard Analysis 4.5.1      The following discussions provide information on the WCGS plant design and nomenclature, the assumed effects of fire, and the response of certain devices.
: 1. Redundant PFSSD mechanical systems are referred to in the analysis as Train A and Train B. Train A is served by electrical separation groups 1 and 3, while Train B is served by electrical separation groups 2 and 4.
Electrical separation groups 5 and 6 are typically for non-safety related equipment. However, in limited cases these groups also provide a PFSSD success path.
: 2. The FHA and supporting documents XX-E-013 and E-1F9910 include the effects of a postulated fire hazard on PFSSD cables, exposed conduit and instrumentation. Embedded conduits are not considered due to the heat sink provided by the encasing barrier. Section 8.3.1.4 of the USAR provides the basis and criteria for the interdependence of redundant systems.
: 3. If a fire is postulated to cause a short in a circuit and that circuit is protected by an individual overcurrent protection device, that device is assumed to function to clear the fault without further degradation of the power source.
: 4. Separation of the devices for nuclear safety-related controls and instrumentation is achieved by physical separation, use of fire-resistive cable or barriers between separation groups for the same protective function, in accordance with Regulatory Guide 1.75.
4.6      General Information on Design Features 4.6.1      Redundant equipment and circuits required for safe shutdown are also protected against the effects of potential exposure fires. These protection features include fixed fire detection and suppression systems, fire barriers, control of combustibles, use of fire-resistive cable, and physical separation. The design goal for safety-related areas outside of the Containment was to provide the equivalent of a 3-hour rated fire barrier between redundant trains, as described in 10 CFR 50, Appendix R, Paragraph III.G.2.a. Where this was not possible, credit was taken for the detection and suppression systems installed in the plant, the use of fire-resistive cable, and compliance to the provisions of Appendix R, Paragraphs III.G.2.b and c, was addressed.
4.6.2      In most fire areas, the boundaries are defined by walls, floors, and ceilings. In the Reactor Building, however, such natural boundaries do not completely enclose localized fire hazards. For the Fire Areas inside of the Containment, the provisions of 10 CFR 50 Appendix R, Paragraphs III.G.2.d, e, and f were addressed.
4.6.3      Emergency lighting is provided for areas required for operation of safe shutdown equipment and for access and egress to those areas. It consists of sealed beam units with individual 8-hour minimum battery power supplies.
4.6.4      Safety-related cable in the general plant area is qualified to IEEE-383-1974. All single conductors inside control panels meet the flame resistance requirements of IPCEA S-19-81 or S-61-402.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 14 of 281 Fire Hazard Analysis 4.6.5      Noncombustible materials are defined to meet one of the following criteria:
: 1. Material of which no part will burn.
: 2. Surface materials not over 1/16-inch thick with a flame spread rating of 50 or less as measured by ASTM E 84- 1976.
: 3. Interior finishes which meet 4.6.5.1, or are listed by an approved organization for surface flame spread of 25 or less per ASTM E 84-1976 and potential heat release of 3,500 Btu/lb or less per ASTM D 3286-1973.
4.6.6      Lighting, fire protection, communication and specialty cables which are flame retardant but not qualified to IEEE-383-1974; and other communication and specialty cable, such as cords and computer ribbon cable, are limited in use in the following manner:
: 1. Covered with a flame retardant coating per the requirements of (BTP)
APCSB 9.5-1, Appendix A; or
: 2. Installed in a totally enclosed metal conduit system; or
: 3. Consist of short lengths of exposed cable between the end of a totally enclosed metal conduit system routed to a component and the connection to the component (e.g. at light fixtures and public address devices; or
: 4. Located in non-safety-related areas which are separated from safety-related areas by fire rated boundaries; or
: 5. Evaluated on a case-by-case basis for adverse impact on the fire protection program.
4.7        PFSSD Historical Information Note:
The following historical information regarding the initial PFSSD analysis process was extracted verbatim from USAR Section 9.5B.6 (Rev. 14) so that the information would be readily available for reference purpose. E-15000 (Set-Route) is now the control means for PFSSD circuits.
The list of safe shutdown components shown on [USAR] Table 9.5B-2 was provided to electrical design engineers who located all associated circuits through the review of physical drawings and electrical schematics. Each circuit associated with these devices was then flagged as being safe shutdown related (following a fire) in the master electrical raceway routing program/data base E0580. This program is utilized to route the scheduled power block cable at WCGS. It ensures that train separation is maintained and provides the most direct/suitable routing for circuits.
 
Wolf Creek Nuclear Operating Corporation                                                Page 15 of 281 Fire Hazard Analysis After the E0580 data base was updated, a special program (Electrical Fire Hazards Analysis Program [EFHAP]) was run to produce a listing of safe shutdown circuits by fire area and room number, and by electrical separation group. This listing also included "from" and "to" information for each circuit. When a safe shutdown incompatibility was determined to exist, a failure modes analysis was performed on the circuit, the physical location(s) of the circuits were evaluated, the availability of an alternate (diverse) shutdown system was identified, and/or the need for a rated fire barrier wrap was evaluated.
The need for a fire wrap was determined based on the installed detection and suppression systems and the physical distance separating the incompatible circuits. A summary of the final evaluation for each area is provided in Section X.X.7.2 of each fire area described in
[USAR] Appendix 9.5B (where "X.X" identifies the fire area).
Since the power block safety-related circuits are all routed in the design office through the application of computer technology and the EFHAP listings were generated from the base E0580 program, it has been determined that the inclusion of listings of conduit and raceway numbers in the USAR descriptions of each fire area is inappropriate. These listings would be of no benefit to any USAR holder or reviewer. The listings would be voluminous and add several hundred pages to the fire hazards analyses.
4.8      FHA Revision 4.8.1      The FHA is part of the Approved Fire Protection Program. As discussed in Operating License Condition 2.C.(5)(b), changes are allowed to the Approved Fire Protection Program provided they do not adversely affect the capability to achieve and maintain PFSSD. Therefore, technical changes to this analysis document require an evaluation in accordance with AI 26A-003. This evaluation, which requires Plant Safety Review Committee (PSRC) approval, is necessary to determine if proposed technical changes require prior NRC approval.
 
Wolf Creek Nuclear Operating Corporation                                                      Page 16 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 1 of 14)
Fire Area Rm #  Bldg. Elev.                  Description            Auto.      Auto. PFSSD      RCA  FHA Detection Suppression  Circuits  (Typ.) Page A-1        1101  Aux. 1974-0 General Floor Area No. 1                    T          T        Yes      Yes    30 1102  Aux. 1974-0 Chiller & Surge Tanks Area                  T          T        Yes      Yes 1103  Aux. 1974-0 Letdown Chiller Heat Exch Room              N        N          No      Yes (Note 0) 1104  Aux. 1974-0 Letdown Reheat Heat Exch Room              N        N          No      Yes (Note 0) 1105  Aux. 1974-0 Valve Compartment                          N        N          No      Yes (Note 0) 1106  Aux. 1974-0 Moderating Heat Exch Room                  N        N          No      Yes (Note 0) 1115  Aux. 1974-0 Normal Charging Pump Rm                    T        N          Yes      Yes 1120  Aux. 1974-0 General Floor Area No. 2                    T          P        Yes      Yes 1121  Aux. 1974-0 Access Pit                                  T        N          No      Yes 1122  Aux. 1974-0 General Floor Area No. 3                    T          P        Yes      Yes 1123  Aux. 1974-0 Passage                                    N        N          No      Yes (Note 0) 1124  Aux. 1974-0 Valve Compartment                          N        N          No      Yes (Note 0) 1125  Aux. 1974-0 Letdown Heat Exch Room                      N        N          No      Yes (Note 0) 1128  Aux. 1974-0 Auxiliary Feedwater Pump Room              T        N          Yes      Yes 1129  Aux. 1974-0 Aux Steam Cond Recovery & Storage Tank      T        N          Yes      Yes 1130  Aux. 1974-0 North Corridor                              T          P        Yes      Yes 1201  Aux. 1988-0 Vestibule                                  T        N          No      Yes 1202  Aux. 1988-0 Access Area B & Chiller Surge Tank Area    N        N          Yes      Yes 1203  Aux. 1988-0 Pipe Space B                                N        N          Yes      Yes (Cold shutdown only) 1204  Aux. 1988-0 Pipe Space A                                N        N          Yes      Yes (Cold shutdown only) 1205  Aux. 1988-0 Access Area A                              N        N          No      Yes 1203A  Aux. 1988-0 Electrical Chase                            T          T        Yes      Yes A-2        1111  Aux. 1974-0 Residual Heat Removal Pump Room A          T        N          Yes      Yes    33 1112  Aux. 1974-0 Containment Spray Pump Room A              T        N          Yes      Yes 1113  Aux. 1974-0 Safety Injection Pump Room A                T        N          Yes      Yes 1114  Aux. 1974-0 Centrifugal Charging Pump Room A            T        N          Yes      Yes A-3        1116  Aux. 1974-0 Boric Acid Tank Room B                      T        N          Yes      Yes    37 1117  Aux. 1974-0 Boric Acid Tank Room A                      T        N          Yes      Yes 1407  Aux. 2026-0 Boric Acid Batching Tank Area              N        N          Yes      Yes A-4        1107  Aux. 1974-0 Centrifugal Charging Pump Room B            T        N          Yes      Yes    40 1108  Aux. 1974-0 Safety Injection Pump Room B                T        N          Yes      Yes 1109  Aux. 1974-0 Residual Heat Removal Pump Room B          T        N          Yes      Yes 1110  Aux. 1974-0 Containment Spray Pump Room B              T        N          Yes      Yes A-5        1119  Aux. Stair Aux. Stair A-1 & A-1A                      N        N          No      Yes    43 1601  Aux. 2064-4 Elevator Machine Room No. 2                N        N          No      Yes A-6        1127  Aux. Stair Aux. Stair A-2                              N        N          Yes      Yes    45 A-7        1126  Aux. 1974-0 Boron Injection Tank & Pump Room            T        N          Yes      Yes    47
 
Wolf Creek Nuclear Operating Corporation                                                          Page 17 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 2 of 14)
Fire Area Rm #  Bldg. Elev.                  Description            Auto.      Auto.      PFSSD      RCA  FHA Detection Suppression    Circuits  (Typ.) Page A-8        1301  Aux. 2000-0 Corridor No. 1                              P          P          Yes      Yes    49 1302  Aux. 2000-0 Filter Compartments Typical of 5            N          N            No      Yes 1306  Aux. 2000-0 Valve Compartments Typical of 5            N          N            No      Yes 1307  Aux. 2000-0 Corridor No. 2                              N          N            No      Yes 1308  Aux. 2000-0 Valve Compartments Typical of 8            N          N            No      Yes 1311  Aux. 2000-0 Sampling Room                              T          N          Yes      Yes 1312  Aux. 2000-0 Boron Meter & R.C. Activity Monitor Rm      N    Above Ceiling -    No      Yes T
Below Ceiling -
N 1313  Aux. 2000-0 Volume Control Tank Rm                      N          N          Yes      Yes (Note 0) 1314  Aux. 2000-0 Corridor No. 3                              T          N          Yes      Yes 1315  Aux. 2000-0 Ctmt Spray Additive Tank Area              T          N          Yes      Yes 1318  Aux. 2000-0 Valve Compartment                          T          N          Yes      Yes 1319  Aux. 2000-0 Demineralizer Compartments Typical of 8    N          N            No      Yes 1320  Aux. 2000-0 Corridor No. 4                              T          P          Yes      Yes 1321  Aux. 2000-0 Exit Vestibule                              T          T            No      Yes A-9        1309  Aux. 2000-0 Residual Heat Removal Heat Exch Rm B        N          N          Yes      Yes    54 (Note 0)
A-10      1310  Aux. 2000-0 Residual Heat Removal Heat Exch Rm A        N          N          Yes      Yes    56 (Note 0)
A-11      1335  Aux. 2000-0 Electrical Chase                            T          T          Yes      Yes    58 A-12      1336  Aux. 2000-0 Electrical Chase                            T          T          Yes      Yes    61 A-13      1325  Aux. 2000-0 Aux Feedwater Pump Rm B                    T          N          Yes      No    63 A-14      1326  Aux. 2000-0 Aux Feedwater Pump Rm A                    T          N          Yes      No    65 A-15      1331  Aux. 2000-0 Aux Feedwater Pump Rm C                    T          N          Yes      No    67 (Note 0)
A-16      1401  Aux. 2026-0 Component Cooling Pump & Heat Exch Area    T          N          Yes      Yes    70 B
1402  Aux. 2026-0 Corridor No. 1                              T          T          Yes      Yes 1406  Aux. 2026-0 Component Cooling Pump & Heat Exch Area    T          N          Yes      Yes A
1408  Aux. 2026-0 Corridor No. 2                              T          P          Yes      Yes A-17      1409  Aux. 2026-0 Electrical Penetration Rm B                T          T          Yes      Yes    74 A-18      1410  Aux. 2026-0 Electrical Penetration Rm A                T          T          Yes      Yes    77 A-19      1504  Aux. 2047-6 Ctmt Purge Exhaust & Mech Equip Rm B        T          N          Yes      Yes    80 1506  Aux. 2047-6 Ctmt Purge Supply Air Handling Unit A      T          N          Yes      Yes 1513  Aux. 2047-6 Control Bldg Vent Supply A/C Unit Rm        T          N          Yes      Yes A-20      1502  Aux. 2047-6 Component Cooling Water Surge Tk Area B    P          N          Yes      Yes    83 1503  Aux. 2047-6 Component Cooling Water Surge Tk Area A    N          N          Yes      Yes (Note 0) 1505  Aux. 2047-6 Corridor                                    T          N            No      Yes 1507  Aux. 2047-6 Personnel Hatch Area                        T          N          Yes      Yes A-21      1501  Aux. 2047-6 Control Rm A/C & Filtration Units B        T          N          Yes      Yes    86 A-22      1512  Aux. 2047-6 Control Rm A/C & Filtration Units A        T          N          Yes      Yes    89
 
Wolf Creek Nuclear Operating Corporation                                                                            Page 18 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 3 of 14)
Fire Area Rm #      Bldg.        Elev.                    Description                    Auto.      Auto.        PFSSD      RCA  FHA Detection Suppression        Circuits  (Typ.) Page A-23      1411      Aux.        2037-7  Main Feedwater Rm No. 1                            T          N            Yes      Yes    92 1412      Aux.        2037-7  Main Feedwater Rm No. 2                            T          N            Yes      Yes 1508      Aux.        2042-0  Main Steam Isolation Valve Rm No. 1                T          N            Yes      Yes 1509      Aux.        2042-0  Main Steam Isolation Valve Rm No. 2                T          N            Yes      Yes A-24      1323      Aux.        2000-0  Pipe Penetration Rm A                              T          N            Yes      Yes    95 A-25      1322      Aux.        2000-0  Pipe Penetration Rm B                              T          N            Yes      Yes    97 A-26      1405      Aux.        2026-0  Chemical Storage Area                              T          N            Yes      Yes    100 1415      Aux.        2026-0  I & C Hot Shop                                      T          N            Yes      Yes A-27      1403      Aux.        2026-0  MG Set Room                                        T            T            Yes      Yes    103 A-28      1413      Aux.        2026-0  Auxiliary Shutdown Panel Room                      T          N            Yes      Yes    106 A-29      1304      Aux.        2013-6  Aux Feedwater Pipe Chase                            N          N            Yes        No    108 (Note 0) 1324      Aux.        2000-0 Feedwater Pump Valve Compartment No. 1              N          N            Yes        No (Note 0) 1327      Aux.        2000-0 Feedwater Pump Valve Compartment No. 2              N          N            Yes        No (Note 0)
A-30      1305      Aux.        2013-6 Aux Feedwater Pipe Chase                            N          N            Yes      Yes    110 (Note 0) 1328      Aux.        2000-0 Feedwater Pump Valve Compartment No. 3              N          N            Yes      Yes (Note 0) 1330      Aux.        2000-0 Feedwater Pump Valve Compartment No. 4              N          N            Yes      Yes (Note 0)
A This Fire Area has been deleted.
A This Fire Area has been deleted.
A-33      1206      Aux.        1989-0  Pipe Chase                                          T            T            Yes        No    112 1207      Aux.        1989-0  Pipe Chase                                          T            T            Yes        No 1329      Aux.        2000-0  Vestibule                                          N          N              No        No A-34      1316      Aux.        2000-0  Seal Water Heat Exch. Valve Comp.                  N          N              No        No    115 1317      Aux.        2000-0  Seal Water Heat Exchanger                          N          N            Yes      Yes AB-1      4315    Turbine      2000-0  Auxiliary Boiler Room                              T            T            No        No    117 C-1        3101    Control      1974-0  Pipe Space & Tank Area                              P            T            Yes      Yes    119 3104    Control        Stair  Control, Stair No. C-2                              N          N            Yes      Yes N/A    Control      1974-0  Duct Chase - East Wall of 3101                      N          N              No      Yes C-2        3106    Control      1974-0  Electrical Chase                                    T            T            No      Yes    122 C-3        3105    Control      1974-0  Electrical Chase                                    T            T            No      Yes    124 C This fire area has been deleted. The area above the suspended ceiling is now included in Fire Areas C-5 and C-6.
 
Wolf Creek Nuclear Operating Corporation                                                          Page 19 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 4 of 14)
Fire Area Rm #    Bldg. Elev.                  Description                Auto.      Auto. PFSSD      RCA  FHA Detection Suppression Circuits  (Typ.) Page C-5        3206  Control 1984-0 R.C.A. Egress                                  T          T        No      No    125 3212  Control 1984-0 H.P. Lounge Area                                T          T        Yes      No 3213  Control 1984-0 H.P. Conference Room (West)                    T          T        No      No 3214  Control 1984-0 Hall                                            N          T        No      No 3216  Control 1984-0 R.P. Calibration Lab 2                          T          T        Yes      No 3217  Control 1984-0 Mens Toilet                                    N          N        Yes      No 3218  Control 1984-0 Exit Monitor Area                              T          T        Yes      No 3220  Control 1984-0 Sign In/Out Area                                T          N        Yes      No 3221  Control 1984-0 Vestibule No. 1                                P          T        No      No 3222  Control 1984-0 H.P. office                                    T          T        Yes      No 3223  Control 1984-0 Closet                                          T          T        No      No 3224  Control 1984-0 Vestibule No. 2                                N          N        Yes      No 3231  Control 1984-0 Womens Toilet                                  N          N        Yes      No None  Control 1984-0 Pipe Chase South of 3213                        N          N        N        No None  Control 1984-0 Pipe Chase South of 3216                        N          N        N        No None  Control 1984-0 Pipe Chase North of 3217/ 3231                  N          N        N        No None  Control 1984-0 Pipe Chase South of 3217/3231                  N          N        N        No None  Control 1984-0 Pipe Chase North of 3213                        N          N        N        No None  Control 1984-0 Pipe Chase North of 3223                        N          N        N        No 3212A Control 1984-0 Partial Height Electrical Chase (Accessible  (Note 0)  (Note 0)    Y        No from 3212)
NAC  Control 1984-0 Area Above Suspended Ceiling                    P          P        Y        No
 
Wolf Creek Nuclear Operating Corporation                                                          Page 20 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 5 of 14)
Fire Area Rm #    Bldg. Elev.                  Description                Auto.      Auto. PFSSD      RCA  FHA Detection Suppression Circuits  (Typ.) Page C-6        3201  Control  Stair Control, Stair C-1                              N          N        No      Yes    128 3202  Control 1984-0 Controlled H.P. Tool & Inst. Storage Room      T          T        No      Yes 3203  Control 1984-0 Hot Janitors Closet                            T          T        No      Yes 3204  Control 1984-0 Corridor No. 1                                  N          T        Yes      Yes 3205  Control 1984-0 H.P. Area                                      T          T        No      Yes 3207  Control 1984-0 R.C.A. Ingress                                  T          T        No      Yes 3208  Control 1984-0 R.P. Calibration Lab 1                          T          T        Yes      Yes 3209  Control 1984-0 Decon Area                                      T          T        No      Yes 3210  Control 1984-0 Decon Shower                                    N          N        No      Yes 3211  Control 1984-0 H.P Conference Room (East)                      T          T        Yes      Yes None  Control 1984-0 Pipe Chase North of 3207                        N          N        N      Yes None  Control 1984-0 Pipe Chase South of 3207                        N          N        N      Yes None  Control 1984-0 Pipe Chase South of 3209                        N          N        N      Yes None  Control 1984-0 Pipe Chase North of 3210                        N          N        N      Yes None  Control 1984-0 Pipe Chase Behind Hose Cabinet in 3204          N          N        N      Yes 3205A Control 1984-0 Partial Height Electrical Chase (Accessible  (Note 0)  (Note 0)    Y      Yes from 3205)
SAC  Control 1984-0 Area Above Suspended Ceiling                    P          P        Y      Yes C-7        3230  Control 1984-0 Electrical Chase                                T          T        Yes      No    132 C-8        3229  Control 1984-0 Electrical Chase                                T          T        No      Yes    134 C-9        3301  Control 2000-0 ESF Switchgear Room No. 1                      T          T        Yes      No    136 C-10      3302  Control 2000-0 ESF Switchgear Room No. 2                      T          T        Yes      No    139 C-11      3305  Control 2000-0 Electrical Chase                                T          T        Yes      No    142 C-12      3306  Control 2000-0 Electrical Chase                                T          T        Yes      No    144 C-13      3415  Control 2016-0 Access Ctrl & Elec Equip A/C Units No. 1        T          N        Yes      No    146 C-14      3416  Control 2016-0 Access Ctrl & Elec Equip A/C Units No. 2        T          N        Yes      No    149 C-15      3403  Control 2016-0 Non-Vital Swgr & Xfmr Rm No. 1                  T          T        Yes      No    152 3404  Control 2016-0 Switchboard Rm No. 4                            T          T        Yes      No 3405  Control 2016-0 Battery Rm No. 4                                T          N        Yes      No 3410  Control 2016-0 Switchboard Rm No. 2                            T          T        Yes      No 3411  Control 2016-0 Battery Rm No. 2                                T          N        Yes      No C-16      3407  Control 2016-0 Battery Rm No. 1                                T          N        Yes      No    155 3408  Control 2016-0 Switchboard Rm No. 1                            T          T        Yes      No 3409  Control 2016-0 Non-Vital Swgr & Xfmr Rm No. 2                  T          T        Yes      No 3413  Control 2016-0 Battery Rm No. 3                                T          N        Yes      No 3414  Control 2016-0 Switchboard Rm No. 3                            T          T        Yes      No C-17      3418  Control 2016-0 Electrical Chase                                T          T        Yes      No    159 C-18      3419  Control 2016-0 Electrical Chase                                T          T        Yes      No    161 C-19        C19  Control 2016-0 Cable Chase @ CA-C3, 2016-0 to 2032-0          T          T        Yes      No    163 C-20        C20  Control 2016-0 Cable Chase @ CA-C6, 2016-0 to 2032-0          T          T        Yes      No    165 C-21      3501  Control 2032-0 Lower Cable Spreading Room                      T          P        Yes      No    167 C-22      3801  Control 2073-6 Upper Cable Spreading Room                      T          P        Yes      No    170 C-23      3505  Control 2032-0 Electrical Chase                                T          T        Yes      No    173 C-24      3504  Control 2032-0 Electrical Chase                                T          T        Yes      No    175 C-25        C25  Control 2032-0 Cable Chase @ CA-C6, 2032-0 to 2047-6          T          T        Yes      No    177 C-26        C26  Control 2032-0 Cable Chase @ CA-C3, 2032-0 to 2047-6,          T          T        Yes      No    179 C-27      3601  Control 2047-6 Control Room                                    T          N        Yes      No    181
 
Wolf Creek Nuclear Operating Corporation                                                      Page 21 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 6 of 14)
Fire Area Rm #    Bldg. Elev.                  Description              Auto.      Auto. PFSSD      RCA  FHA Detection Suppression Circuits  (Typ.) Page RL001  2047-6 Panel Board                                T        N        Yes      No RL002  2047-6 Panel Board                                T        N        Yes      No RL003  2047-6 Panel Board                                T        N        Yes      No RL004  2047-6 Panel Board                                T        N          No      No RL005  2047-6 Panel Board                                T        N        Yes      No RL006  2047-6 Panel Board                                T        N        Yes      No RL011  2047-6 Panel Board                                T        N          No      No RL012  2047-6 Panel Board                                T        N          No      No RL013  2047-6 Panel Board                                T        N          No      No RL014  2047-6 Panel Board                                T        N          No      No RL015  2047-6 Panel Board                                T        N        Yes      No RL016  2047-6 Panel Board                                T        N        Yes      No RL017  2047-6 Panel Board                                T        N        Yes      No RL018  2047-6 Panel Board                                T        N        Yes      No RL019  2047-6 Panel Board                                T        N        Yes      No RL020  2047-6 Panel Board                                T        N        Yes      No RL021  2047-6 Panel Board                                T        N        Yes      No RL022  2047-6 Panel Board                                T        N        Yes      No RL023  2047-6 Panel Board                                T        N        Yes      No RL024  2047-6 Panel Board                                T        N        Yes      No RL025  2047-6 Panel Board                                T        N        Yes      No RL026  2047-6 Panel Board                                T        N          No      No RL027  2047-6 Panel Board                                T        N        Yes      No RL028  2047-6 Panel Board                                T        N          No      No 3603  Control 2047-6 Shift Supervisors office                    T        N          No      No 3604  Control 2047-6 Foyer                                      N        N          No      No 3605  Control 2047-6 Equipment Cabinet Area                      P        N        Yes      No RP068  2047-6 Panel Board                                T        N        Yes      No NF039A  2047-6 Panel Board                                T        N        Yes      No NF039B  2047-6 Panel Board                                T        N        Yes      No NF039C  2047-6 Panel Board                                T        N        Yes      No 3606  Control 2047-6 Emergency Equipment Storage Room            T        N          No      No 3616  Control 2047-6 Vestibule                                  N        N          No      No N/A  Control 2047-6 Duct Chase - Northwest Corner of 3601      N        N          No      No N/A  Control 2047-6 Duct Chase - Southeast Corner of 3604      N        N          No      No N/A  Control Varies Cable Trenches and Vertical Shaft          T          T        Yes      No C-28      3602  Control 2047-6 Pantry                                      T        N        Yes      No    186 3607  Control 2047-6 Toilet                                      N        N        Yes      No 3608  Control 2047-6 Janitors Closet                            T        N        Yes      No C-29      3609  Control 2047-6 SAS Room                                    T        N          No      No    188 C-30      3617  Control 2047-6 Electrical Chase                            T          T        Yes      No    190 C-31      3618  Control 2047-6 Electrical Chase                            T          T        Yes      No    192 C-32      C32  Control 2047-6 Cable Chase @ CA-C6, 2047-6 to 2073-6,      T          T        Yes      No    194 C-33      3804  Control 2073-6 Electrical Chase                            T          T        Yes      No    196 C-34      C34  Control 2073-6 Cable Chase @ CA-C6                        T          T        Yes      No    198 C-35      3401  Control 2016-0 Corridor No. 1                              N        N        Yes      No    200 (Note 0)
 
Wolf Creek Nuclear Operating Corporation                                                      Page 22 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 7 of 14)
Fire Area Rm #    Bldg. Elev.                Description              Auto.      Auto. PFSSD      RCA  FHA Detection Suppression Circuits  (Typ.) Page 3406  Control 2016-0 Corridor No. 2                              N        N          No      No (Note 0) 3412  Control 2016-0 Emergency Shower & Eyewash Area            N        N        Yes      No (Note 0)
C-36        C36  Control 2000-0 Cable Chase @ CA-C6, 2000-0 to 2016-0,      N        T        Yes      No    202 (Note 0)
C-37        C37  Control 2000-0 Cable Chase @ CA-C3, 2000-0 to 2016-0      N        T        Yes      No    204 (Note 0)
CC-1      3102  Cm Corr. 1974-0 Pipe Space, Tank & Storage Area            P        N          No      No    206 3103  Cm Corr. Stair Stair No. CC-1                              T        N          No 3225  Cm Corr. 1984-0 Corridor No. 2                              P        N        Yes 3226  Cm Corr. 1984-0 Counting Room                            Above      N        Yes      Yes Ceiling - T Below Ceiling - T 3227  Cm Corr. 1984-0 Vestibule No. 3                            N        N        Yes      Yes 3228  Cm Corr. 1984-0 Hot Laboratory                          Above      N        Yes      Yes Ceiling - T Below Ceiling - T N/A  Cm Corr. 1984-0 Pipe Chase - South of 3227 & 3228          N        N          No      No 3303  Cm Corr. 2000-0 Corridor                                    T        N        Yes      No 3304  Cm Corr. 2000-0 General Floor Area                          N        N        Yes      No 3402  Cm Corr. 2016-0 Corridor No. 3                              T        N        Yes      No 3502  Cm Corr. 2032-0 Lobby                                      T        N        Yes      No 3503  Cm Corr. 2032-0 General Floor Area                          P        N        Yes      No 3611  Cm Corr. 2047-6 Corridor No. 2                              P        N          No      No 3612  Cm Corr. 2047-6 Operations Conference Room                  T        N          No      No 3613  Cm Corr. 2047-6 Work Control Center                        T        N          No      No 3614  Cm Corr. 2047-6 Corridor No. 3                              T        N        Yes      No 3619  Cm Corr. 2047-6 General Floor Area                          N        N        Yes      No 3701  Cm Corr. 2061-6 General Floor Area                          P        N        Yes      No 3702  Cm Corr. 2061-6 Battery Room                                T        N        Yes      No 3703  Cm Corr. 2061-6 Radio Equipment Room                        T        N        Yes      No 3704  Cm Corr. 2061-6 General Floor Area                          T        N        Yes      No 3705  Cm Corr. 2061-6 Battery Room                                T        N        Yes      No 3802  Cm Corr. 2078-0 Elevator No. 1 Machine Room                T        N          No      No 3803  Cm Corr. 2073-6 Corridor                                    T        N        Yes      No OP-7  Cm Corr. 2032-0 Observation Post                            N        N          No      No CST        9101    Other  N/A  Condensate Storage Tank & Pipe House        N        N        Yes      No    271 D-1        5203  D. Gen. 2000-0 Emergency Diesel Generator A Room        T        T        Yes      No    209 5203A  Yard  Buried Emergency Fuel Oil Tank Area                N        N        Yes      Yes
 
Wolf Creek Nuclear Operating Corporation                                                                Page 23 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 8 of 14)
Fire Area Rm #    Bldg. Elev.                    Description                  Auto.      Auto. PFSSD      RCA  FHA Detection Suppression Circuits  (Typ.) Page D-2        5201  D. Gen. 2000-0  Emergency Diesel Generator B Room              T          T        Yes      No    212 5201A    Yard    Buried  Emergency Fuel Oil Tank Area                    N        N        Yes      Yes ESWA      K105    ESW      2000-0  ESW Pump House - Room A                          T        N        Yes      No    215 K105A    ESW      2000-0  Train A ESW Electrical Duct Banks and Vaults    N        N        Yes      No ESWB      K104    ESW      2000-0  ESW Pump House - Room B                          T        N        Yes      No    218 K104A    ESW      2000-0  Train B ESW Electrical Duct Banks and Vaults    N        N        Yes      No ESWV      AV1,    Yard    Multiple ESW Vaults                                      N        N          No      No    221 AV2, AV3, AV4, AV5, AV6 F-1        6101    Fuel    Stair  Stair F-1                                        N        N          No      Yes    223 6102    Fuel    2000-0  Laydown Area                                    T          P        No      Yes 6103    Fuel    2000-0  Cask Loading Pool                                N        N          No      Yes 6106    Fuel    2000-0  Spent Fuel Pool & Storage Racks                  N        N          No      Yes 6201    Fuel    2026-0  Passage                                          N        N          No      Yes 6204    Fuel    2026-0  Cask Washdown Pit                                N        N          No      Yes 6205    Fuel    2026-0  Fuel Transfer Canal                              N        N          No      Yes 6210    Fuel    2032-6  New Fuel Storage Area                            N        N          No      Yes 6301    Fuel    2047-6  General Floor Area                              P        N        Yes      Yes 6302    Fuel    2047-6  Laydown Area                                    N        N          No      Yes F-2        6104    Fuel    2000-0  Fuel Pool Cooling Heat Exch Room                T        N        Yes      Yes    226 F-3        6105    Fuel    2000-0  Fuel Pool Cooling Heat Exch Room                T        N          No      Yes    228 F-4        6203    Fuel    2026-0  Air Handling Equipment Room                      P        N        Yes      Yes    230 F-5        6202    Fuel    2026-0  Electrical Equipment Room                        T        N        Yes      Yes    232 F-6        6304    Fuel    2047-6  Exhaust Filter Absorber Room A                  T        N          No      Yes    234 F-7        6303    Fuel    2047-6  Exhaust Filter Absorber Room B                  T        N        Yes      Yes    236 HMS-1      1332 Hot Machine 2000-0 Hot Machine Shop                                  T        N          No      Yes    238 Shop 1333 Hot Machine 2000-0 Decontamination Room                              T        N          No      Yes Shop 1334 Hot Machine 2000-0 Hot Instrument Shop                                T        N          No      Yes Shop
 
Wolf Creek Nuclear Operating Corporation                                                        Page 24 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 9 of 14)
Fire Area Rm #  Bldg. Elev.                    Description              Auto.      Auto. PFSSD      RCA  FHA Detection Suppression Circuits  (Typ.) Page RB        RB1  Reactor  2000-0  Area Within Secondary Shield Wall            N        N        Yes      Yes    241 RB2  Reactor  2000-0  Area Outside Secondary Shield Wall          P        N        Yes      Yes 2201 RB3  Reactor  2026-0  North Electrical Penetration Area            P        N        Yes      Yes RB4  Reactor  2026-0  South Electrical Penetration Area            P        N        Yes      Yes RB5  Reactor  2047-6  Cable Tray Area                              P        N        Yes      Yes RB6  Reactor  2068-8  General Area, Pressurizer Valve Control      N        N        Yes      Yes 2601                  Room, & Pressurizer Safety Valve Room 2602 RB6  Reactor  2068-8  Elevator Machine Room                        N        N          No      Yes 2603 RB7  Reactor  2026-0  West Area                                    P        N        Yes      Yes RB8  Reactor  2026-0  East Area                                    P        N        Yes      Yes RB9  Reactor  1974-0  Tendon Access Gallery                        N        N          No      Yes 2101 RB10 Reactor  2047-6  El 2047-6, Except Cable Tray Area            N        N        Yes      Yes RB11 Reactor  Multiple Area Within Primary Shield Wall              N        N        Yes      Yes 2102
 
Wolf Creek Nuclear Operating Corporation                                                        Page 25 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 10 of 14)
Fire Area Rm #  Bldg. Elev.                  Description                Auto.      Auto. PFSSD      RCA  FHA Detection Suppression Circuits  (Typ.) Page RW        7101 Radwaste 1976-0 Waste Gas Compressor Room No. 1                N        N          No      Yes    248 (Note 0) 7102 Radwaste 1976-0 Hydrogen Recombiner Room No. 1                N        N          No      Yes (Note 0) 7103 Radwaste 1976-0 Valve Room No. 1                              T        N          No      Yes 7104 Radwaste 1976-0 Recycle Evaporator Feed Pump Room              N        N          No      Yes 7105 Radwaste 1976-0 Recycle Hold-Up Tank Room No. 1                N        N          No      Yes 7106 Radwaste 1976-0 Waste Gas Compressor Room No. 2                N        N          No      Yes (Note 0) 7107 Radwaste 1976-0 Hydrogen Recombiner Room No. 2                N        N          No      Yes (Note 0) 7108 Radwaste 1976-0 Valve Room No. 2                              T        N          No      Yes 7109 Radwaste 1976-0 Corridor No. 1                                T        N          No      Yes 7110 Radwaste 1976-0 Recycle Hold-Up Tank Room No. 2                N        N          No      Yes 7111 Radwaste 1976-0 Waste Gas Decay Tank Room No. 1                N        N          No      Yes (Note 0) 7112 Radwaste 1976-0 Valve Room No. 3                              N        N          No      Yes (Note 0) 7113 Radwaste 1976-0 Load Center and General Area                  T        N        Yes      Yes 7114 Radwaste  Stair Radwaste, Stair RW-1                          N        N          No      Yes 7115 Radwaste 1976-0 Waste Gas Decay Tank Room No. 2                N        N          No      Yes (Note 0) 7116 Radwaste 1976-0 Valve Room No. 4                              N        N          No      Yes (Note 0) 7117 Radwaste 1976-0 Corridor No. 2                                T        N          No      Yes 7118 Radwaste 1976-0 Steam Gen Blowdown Surge Tank and Pump        N        N          No      Yes Room 7119 Radwaste 1976-0 Radioactive Pipe Chase                        N        N          No      Yes 7120 Radwaste 1976-0 Chemical Drain Tank and Pump Room              N        N          No      Yes 7121 Radwaste 1976-0 Waste Evaporator Feed Pump Room                T        N          No      Yes 7122 Radwaste 1976-0 Waste Hold-Up Tank Room                        N        N          No      Yes (Note 0) 7123 Radwaste 1976-0 Waste Evaporator Bottoms Tank Room            N        N          No      Yes Primary                                    (Note 0) 7124 Radwaste 1976-0 Waste Evaporator Bottoms Tank Pump Room        T        N          No      Yes 7125 Radwaste 1976-0 Floor Drain Tank Pump Room No. 1              T        N          No      Yes 7126 Radwaste 1976-0 Floor Drain Tank Room No. 1                    N        N          No      Yes (Note 0) 7127 Radwaste 1976-0 Waste Monitor Tank and Pump Room              N        N          No      Yes (Note 0) 7128 Radwaste 1976-0 Floor Drain Tank Pump Room No. 2              T        N          No      Yes 7129 Radwaste 1976-0 Floor Drain Tank Room No. 2                    N        N          No      Yes (Note 0) 7130 Radwaste 1976-0 Waste Evaporator Condensate Tank and          N        N          No      Yes Pump Room                                  (Note 0) 7131 Radwaste 1976-0 Vestibule                                      N        N          No      Yes (Note 0) 7132 Radwaste  Stair Radwaste, Stair RW-2                          N        N          No      Yes 7135 Radwaste 1976-0 Gaseous Radwaste Drain Collection Tk & Gas    N        N          No      Yes Decay Tk Drain Pump Room 7201 Radwaste 2000-0 Recycle Evapor Room                            N        N          No      Yes (Note 0) 7202 Radwaste 2000-0 Recycle Evaporator Valve Gallery              N        N          No      Yes (Note 0) 7203 Radwaste 2000-0 Corridor No. 1                                T        N          No      Yes RW        7204 Radwaste 2000-0 Waste Evapor Room                              N        N          No      Yes (Note 0) 7205 Radwaste 2000-0 Waste Evaporator Valve Gallery                N        N          No      Yes
 
Wolf Creek Nuclear Operating Corporation                                                        Page 26 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 11 of 14)
Fire Area Rm #  Bldg. Elev.                  Description              Auto.      Auto. PFSSD      RCA  FHA Detection Suppression Circuits  (Typ.) Page (Note 0) 7206 Radwaste 2000-0 SLWS Evaporator Reagent Tank Room            N        N          No      Yes (Note 0) 7207 Radwaste 2000-0 SLWS Pump Room                                N        N          No      Yes (Note 0) 7208 Radwaste 2000-0 MCC Equipment, Load Center & General Area    T        N        Yes      Yes 7209 Radwaste 2000-0 Control Room                                  T        N        Yes      Yes 7210 Radwaste 2000-0 Nuclear Sample Panel Room                    N        N          No      Yes 7211 Radwaste 2000-0 Sample Lab                                    N        N          No      Yes 7212 Radwaste 2000-0 Spent Resin Stg. Tank Room Primary            N        N          No      Yes (Note 0) 7213 Radwaste 2000-0 Corridor No. 3                                N        N          No      Yes (Note 0) 7214 Radwaste 2000-0 Spent Resin and Evaporator Bottom Tk and      N        N          No      Yes Pump Room Secondary                        (Note 0) 7215 Radwaste 2000-0 Liquid Radwaste Demineralizer Room            N        N          No      Yes (Note 0) 7216 Radwaste 2000-0 Corridor No. 2                                T        N          No      Yes 7217 Radwaste 2000-0 SLWS Monitor Tank Room                        N        N          No      Yes (Note 0) 7218 Radwaste 2000-0 Solid Radwaste Disposal Station              N        N          No      Yes (Note 0) 7219 Radwaste 2000-0 Solidification Control Panel Room            N        N          No      Yes 7220 Radwaste 2000-0 Valve Room                                    N        N          No      Yes (Note 0) 7221 Radwaste 2000-0 Emergency Shower and Eyewash Area            T        N          No      Yes 7222 Radwaste 2000-0 Misc. Storage Area                            T        N          No      Yes 7223 Radwaste 2000-0 Vestibule                                    T        N          No      Yes 7224 Radwaste 2000-0 High Level Drum Storage Area                  N        N          No      Yes 7225 Radwaste 2000-0 Low Level Drum Storage Area                  N        N          No      Yes 7226 Radwaste 2000-0 Empty Drum Storage / Truck Bay                T        N          No      Yes 7227 Radwaste 2000-0 Dewatering Station                            N        N          No      Yes (Note 0) 7228 Radwaste 2000-0 Drywaste Compactor Area                      T          P        No      Yes 7229 Radwaste 2000-0 Concentrates Pump Room                        N        N          No      Yes (Note 0) 7230 Radwaste 2000-0 Instrument Rack Area                          N        N          No      Yes (Note 0) 7231 Radwaste 2010-6 Subcoolers and Condenser Room                N        N          No      Yes 7232 Radwaste 2000-0 Elec Chase                                    T        N          No      Yes 7233 Radwaste 2013-4 Area Over Valve Room                          N        N          No      Yes (Note 0) 7234 Radwaste 2000-0 Drum Storage Area A                          T        N          No      Yes 7235 Radwaste 2000-0 Drum Storage Area B                          T        N          No      Yes 7236 Radwaste 2000-0 Waste Bale Corridor                          T        N          No      Yes 7301 Radwaste 2022-0 Radioactive Pipe Chase Area                  N        N          No      Yes 7302 Radwaste 2022-0 HVAC Equip Area                              N        N          No      Yes 7303 Radwaste 2022-0 Vestibule                                    N        N          No      Yes 7304 Radwaste 2022-0 MCC Equip Area                                N        N          No      Yes 7305 Radwaste 2022-0 Electrical Chase                              T        N          No      Yes 7401 Radwaste 2031-6 Filter Compartment Typ of 19                  N        N          No      Yes RW        7402 Radwaste 2031-6 Valve Room Typ of 19                          N        N          No      Yes 7403 Radwaste 2031-6 Corridor                                      T        N          No      Yes 7404 Radwaste 2031-6 Valve Room Typ of 12                          N        N          No      Yes
 
Wolf Creek Nuclear Operating Corporation                                                        Page 27 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 12 of 14)
Fire Area Rm #    Bldg. Elev.                  Description                Auto.      Auto. PFSSD      RCA  FHA Detection Suppression Circuits  (Typ.) Page 7405 Radwaste 2031-6 Demineralizer Compartments, Typ of 12          N        N          No      Yes 7406 Radwaste 2031-6 Valve Room                                    N        N          No      Yes 7407 Radwaste 2031-6 Fuel Pool Cleanup Demin Compartment            N        N          No      Yes (Note 0) 7408 Radwaste 2031-6 Laundry and Hot Shower Tank Area              N        N          No      Yes (Note 0) 7409 Radwaste 2031-6 Acid Tank Area                                N        N          No      Yes (Note 0) 7410 Radwaste 2031-6 General Fl Area                                T        N          No      Yes 7411 Radwaste 2031-6 Waste Monitor Tank Area                        N        N          No      Yes (Note 0) 7413 Radwaste 2031-6 HVAC Platform                                  N        N          No      Yes 7501 Radwaste 2040-6 General Fl Area                                N        N          No      Yes 7502 Radwaste 2041-6 General Fl Area                                N        N          No      Yes 7503 Radwaste 2047-6 General Fl Area                                N        N          No      Yes 7504 Radwaste 2051-6 Platform                                      N        N          No      Yes None Radwaste 2000-0 Radwaste Storage Building                      N          T        No      Yes Storage RW-1      7133 Radwaste 1974-0 Elec. Chase Non Radioactive Pipe Tunnel &      T        N        Yes      Yes    251 Tunnel        Personnel Access 7134 Radwaste 1974-0 Radioactive Pipe Tunnel                        N        N          No      Yes Tunnel RWST      9102  Other    N/A  Refueling Water Storage Tank & Valve House    N        N        Yes      Yes    271 SBO      SBOA    SBO    2000-0 SBO Diesel Generator KU01A                    P        N          No      No    254 SBOB    SBO    2000-0 SBO Diesel Generator KU01B                    P        N          No      No SBOC    SBO    2000-0 SBO Diesel Generator KU01C                    P        N          No      No SBOD    SBO    1981-5 Manhole EMH175 and Duct Bank                  N        N          No      No SBOE    SBO    2000-0 SBO Power Equipment Center                    P        N          No      No T-1        4101  Turbine  Stair Turbine, Stair T-1                            T        N        Yes      No    254 T-2        4301  Turbine 2000-0 General Fl Area, Col TF-TG, T8-A1              T          P        Yes      No    259 4302  Turbine 2000-0 Condensate Vacuum Pump Area                    T          P        Yes      No 4303  Turbine 2000-0 Air Compressor Area                            T          P        No      No 4304  Turbine 2000-0 Mens Toilet                                  N        N          No      No 4305  Turbine 2000-0 Womens Toilet                                N        N          No      No 4306  Turbine 2000-0 Janitors Closet                                N        N          No      No 4322  Turbine 2000-0 Truck Bay & Laydown Area                      T          P        Yes      No 4351  Turbine 2015-4 General Floor Area                            T          T        Yes      No 4401  Turbine 2033-0 General Fl Area, Col TA-TG, T8-A1              T          T        Yes      No 4501  Turbine 2065-0 General Fl Area, Col TA-TG, T8-A1              N        N        Yes      No 4504  Turbine 2065-0 EHC Control Cabinet Room                      N        N        Yes      No T-4        4308  Turbine 2000-0 Lube Oil Storage Tanks                        T          T        No      No    263 T-10      4403  Turbine 2033-0 Lube Oil Reservoir Room                        T          T        Yes      No    265
 
Wolf Creek Nuclear Operating Corporation                                                      Page 28 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 13 of 14)
Fire Area Rm #    Bldg. Elev.                  Description              Auto.      Auto. PFSSD      RCA  FHA Detection Suppression Circuits  (Typ.) Page TURB      4201  Turbine 1983-0 Condenser Pit - General Floor Area          P          P        No      No    267 4203  Turbine 1983-0 SGFP Turbine Lube Oil Conditioner, Cond      N          P        No      No Pump 4204  Turbine 1983-0 Secondary Liquid Waste Collection Tank      N          T        No      No Pumps 4205  Turbine 1983-0 High TDS & Low TDS Tank & Pump Area          N          T        No      No 4309  Turbine  Stair Turbine, Stair T-2                          N        N          No      No 4310  Turbine  Stair Turbine, Stair T-3                          N        N          No      No 4312  Turbine  Stair Turbine, Stair T-5                          N        N          No      No 4313  Turbine  Stair Turbine, Stair T-4                          N        N          No      No 4314  Turbine  Stair Turbine, Stair T-6                          N        N          No      No 4316  Turbine 2000-0 Condensate Polishing Area                    T          P        Yes      No 4317  Turbine 2000-0 Process Sampling Lab                        T        N        Yes      No 4318  Turbine 2000-0 Turbine Cool Water Heat Exchange Area        T          T        No      No 4319  Turbine 2000-0 Condensate Chemical Add Units Area          T          T        No      No 4320  Turbine 2000-0 Secondary Liquids Drain Collection Tanks    T          T        No      No 4321  Turbine 2000-0 Railroad Bay & Laydown Area                  P          T        No      No 4323  Turbine 2010-0 Cold Chemistry Lab                          T        N        Yes      No 4324  Turbine 2000-0 Acid Day Tank Area                          T          P        No      No 4325  Turbine 2000-0 Caustic Day Tank Area                        T          P        No      No 4326  Turbine 2000-0 Ph Control & O2 Control Chemical Storage    T          T        No      No Area 4402  Turbine 2033-0 Battery Room                                T        N          No      No 4404  Turbine 2033-0 Battery Room                                T        N        Yes      No 4405  Turbine 2033-0 Battery Charger Room                        T        N        Yes      No 4502  Turbine 2065-0 Womens Toilet                              N        N          No      No 4503  Turbine 2065-0 Mens Toilet                                N        N          No      No 4505  Turbine 2065-0 Turbine Deck office and Storage Area        N          T        No      No 4601  Turbine 2083-0 Elevator Machine Room                        N        N          No      No 4301E Turbine 2000-0 General Fl Area, Col TA-TD, T4-T8            T          T        No      No 4301W Turbine 2000-0 General Fl Area, Col TD-TG, T4-T8            T          T        Yes      No 4401E Turbine 2033-0 General Fl Area, Col TA-TD, T1-T8            T          T        No      No 4401W Turbine 2033-0 General Fl Area, Col TD-TG, T1-T8            T          T        Yes      No 4501E Turbine 2065-0 General Fl Area, Col TA-TD, T1-T8            P          P        Yes      No 4501W Turbine 2065-0 General Fl Area, Col TD-TG, T1-T8            N        N        Yes      No OP-1  Turbine 2065-0 Observation Post                            N        N          No      No OP-2  Turbine 2000-0 Observation Post                            N        N          No      No OP-7  Turbine 2087-0 Observation Post                            N        N          No      No YARD-    EXFMR  Yard  2000-0 ESF Transformer XNB01                        T          T        Yes      No    273 ESF EXFMR  Yard  2000-0 ESF Transformer XNB02                        T          T        Yes      No YARD-SU SXFMR    Yard  2000-0 Startup Transformer XMR01                    T          T        Yes      No    275 ESWC        8000 ESWC    2000-0 ESW Vertical Loop Chase                      T        N          No      No    243
 
Wolf Creek Nuclear Operating Corporation                                                Page 29 of 281 Fire Hazard Analysis ATTACHMENT A PLANT AREAS PROVIDED WITH A FIRE HAZARD ANALYSIS (Page 14 of 14)
Legend:
T -    Total Coverage P -    Partial Coverage N -    No Coverage Notes:
: 1. Fire Areas A-29 and A-30 contain no fire detectors. These areas contain low fixed and transient combustibles. Each area consists of three small rooms.
: 2. Fire Areas A-9 and A-10 consist of one room each, which can be high radiation areas (depending upon plant conditions). The rooms contain low fixed and transient combustibles. Typically, only mechanical equipment and piping are present.
: 3. Electrical Chase is open to the area above suspended ceiling where smoke detection and sprinkler protection is provided.
: 4. Fire Area C-35 has no detection. Low fixed combustibles are present.
: 5. Fire Areas C-36 and C-37 are small electrical chases containing separation group 2 and 3 circuits, respectively. A wet pipe sprinkler system is installed. Transient combustibles are low. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
: 6. Room is open to an area with detection.
: 7. A fixed manual water spray system is provided for the steam driven auxiliary feedwater pump lubricating oil lines and bearings.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 30 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 1 of 250)
Fire Area A-1 (Reference A-1801)
A.1.1      Fire Area Description Auxiliary building - El. 1974 1988, general area Rooms 1101, 1102, 1103, 1104, 1105 1106, 1115, 1120, 1121,1122, 1123, 1124, 1125, 1128, 1129 1130, 1201, 1202, 1203, 1204, and 1205.
A.1.2      Major Equipment Letdown heat exchanger and associated piping, valves and instrumentation, reactor makeup water pumps, normal charging pump, CVCS chiller pumps, moderating heat exchanger, letdown reheat heat exchanger, letdown chiller heat exchanger, chiller surge tank, CVCS chiller unit, auxiliary steam deaerator feed pumps, auxiliary steam condenser recovery and storage tank, auxiliary building sump pumps, auxiliary feedwater pump room sump and sump pumps.
A.1.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 31 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 2 of 250)
Table A.1.3-1 Fire Area A-1, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category North equipment hatch                            Hatch South equipment hatch                            Hatch Hatches for RHR & containment spray              Hatch valve encapsulation tanks Flanges for encapsulated valve                  Fire Barrier Tanks Personnel hatch from Room 1129 to 1207 Hatch Dumbwaiter doors and shaft                      Fire Door South personnel elevator doors and shaft Fire Door 1-hour rated fire wrap protection for            Fire Wrap redundant PFSSD circuits Penetration seals that exceed the                Penetration Seal bounding limitations of M-663-00017 Structural Steel Fireproofing with              Structural Steel Fireproofing unprotected thermal shorts The letdown heat exchanger (Room 1125) and the valve compartment (Room 1124) are enclosed by 18-inch-thick (minimum) concrete walls. Openings are located in these walls, near the ceiling, for venting these rooms in the event of a high-energy pipe break.
The normal charging pump room (Room 1115) is enclosed by 2-foot-thick concrete walls with a 3-hour-rated fire door and penetration seals. However, Room 1115 is not credited as a separate Fire Area.
A.1.4      Combustible Loading The cumulative combustible loading classification for Fire Area A-1 is Low.
A.1.5      Fire Protection An automatic smoke detection system is installed in this area, except as noted in Attachment A. Manual-pull stations are located at exit doors. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Attachment A summarizes the partial automatic suppression coverage provided for this Fire Area. Specifically, an automatic preaction-type sprinkler system is installed over inaccessible cable tray concentrations in Rooms 1101, 1102, 1130, and 1122. The system also provides protection for the north and south hatchways at the ceiling of this area (El. 2000'). Sprinklers are located to minimize obstructions with structural steel.
Hose stations and portable extinguishers are located throughout the area, as delineated on drawing A-1801.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 32 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 3 of 250)
Access to this area for manual firefighting is available as follows:
: a. Stairwell 4101 from the Turbine Building.
: b. Stairwell 1119 at the south end from El. 2000'-0".
: c. Stairwell 1127 at the north end from El. 2000'-0".
: d. Control Building through Access Control.
One 4-inch drain per 1,000 square feet of floor area is provided throughout this Fire Area.
The floor drains are piped to the Auxiliary Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.1.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.1.7      Analysis A.1.7.1        Fire Suppression The automatic detection system will provide an early warning of a fire in this area. Hose stations or portable extinguishers can be used to suppress the fire. The automatic sprinkler system installed over the cable trays will actuate to control a fire below and to assist the fire brigade by keeping the environment cool. The sprinkler actuation or a malfunction will be identified by Control Room annunciation. In the event of a failure of the automatic system, the fire can be extinguished manually, using hose stations and/or portable extinguishers. Adequate floor drains are provided to remove the fire suppression system discharge.
A.1.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-1 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-1.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 33 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 4 of 250)
Fire Area A-2 (Reference A-1801)
A.2.1      Fire Area Description Auxiliary Building safety-related pump area Rooms 1111, 1112, 1113, and 1114.
A.2.2      Major Equipment Centrifugal charging pump, safety-injection pump, RHR pump, containment spray pump, coolers for the above pump rooms, RHR room sump pumps, valves, and piping auxiliary lube oil pump for the centrifugal charging pump.
A.2.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.2.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.2.3-1 Fire Area A-2, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts The Centrifugal Charging Pump Room 1114, is separated from the Safety-Injection Pump Room 1113, by a 2-foot-thick concrete wall with a 3 foot 4 inch x 7 foot 2 inch access way.
The RHR Pump Room 1111, is separated from the other rooms by 2-foot-thick concrete walls. A 3-hour fire door is provided for access to this room from Room 1112. However, Room 1111 is not credited as a separate Fire Area.
 
Wolf Creek Nuclear Operating Corporation                Page 34 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 5 of 250)
 
Wolf Creek Nuclear Operating Corporation                                                    Page 35 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 6 of 250)
A.2.4      Combustible Loading The cumulative combustible loading classification for Fire Area A-2 is Low.
A.2.5      Fire Protection Smoke detectors are installed in each room. Manual-pull fire alarm stations are located near the exit doorways for this elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are located in Rooms 1101 and 1122 (corridors). In addition, portable fire extinguishers are located within the Fire Area, in Rooms 1112 and 1113. Specific fire hose and extinguisher locations are delineated on drawing A-1801.
Access to Room 1112 is from Room 1121 (corridor) through a watertight door. Access to Room 1111 is from Room 1112 through a 3-hour-rated fire door. Access to Rooms 1113 and 1114 is from Room 1101 through a watertight door.
Rooms 1113 and 1114 have two 4-inch floor drains per room. There is one 4-inch floor drain in Rooms 1111 and 1112. A sump with two sump pumps is located in Room 1111.
The floor drains are piped to this sump. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.2.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.2.7      Analysis A.2.7.1          Fire Suppression This area is protected from a fire in adjacent areas by 3-hour barriers. A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers. A fire in this area will be contained by the fire barriers, until extinguished manually. Adequate drainage is provided in each room to drain away the fire-fighting water. The watertight doors will protect the safe shutdown equipment from damage by water discharge from extinguishing systems in the adjacent areas.
 
Wolf Creek Nuclear Operating Corporation                                                Page 36 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 7 of 250)
A.2.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-2 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-2 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-2.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 37 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 8 of 250)
Fire Area A-3 (Reference A-1801 and A-1803)
A.3.1      Fire Area Description Boric Acid Tank Rooms 1116, 1117, and 1407.
A.3.2      Major Equipment Boric acid tanks and transfer pumps, unit heaters, boric acid batching tank, boron injection makeup pump, and piping and valves. None are required for safe shutdown following a fire.
A.3.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.3.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.3.3-1 Fire Area A-3, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                    Page 38 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 9 of 250)
The Fire Area extends from Elevation 1974 to the floor slab of Elevation 2047 feet - 6 inches. Room 1116 houses the Separation Group 4 boric acid tank and transfer pump.
The corresponding Separation Group 1 equipment is located in Room 1117. Rooms 1116 and 1117 are separated by a 6-foot-high, 12-inch-thick concrete barrier wall with no openings, which acts as a radiant heat shield. The redundant transfer pumps are located approximately 4 feet away from the barrier wall. A 6-foot-wide platform extending from the east to the west fire barrier is located at Elevation 2013. Steps are provided to Elevation 2026 from the platform with an intermediate landing at Elevation 2015 feet - 3 inches.
The boric acid batching tank and the boron injection makeup pumps are located on steel grating above Elevation 2026.
A.3.4      Combustible Loading The cumulative combustible loading classification for Fire Area A-3 is Low.
A.3.5      Fire Protection A smoke detector is installed under the Elevation 2026 slab in Rooms 1116 and 1117.
One infrared flame detector is installed on either side of the 6-foot-high barrier wall to provide early warning of a fire at the floor elevation. Manual-pull stations located at the exit doors on this floor can also provide warning in the event of a fire. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A hose station and one portable extinguisher are located in the corridor (Room 1101),
outside Room 1116, and in Room 1122, as delineated on drawing A-1801. For fighting a fire from the platform or at Room 1407, the hose stations in Room 1408 can be used (see A-1803). Additional hose lengths can be added (if required) for manual fire fighting above the boric acid tanks. Access for manual fire fighting at the floor elevation is from Room 1122 for Room 1117 and from Room 1101 for Room 1116. For access to Rooms 1101 and 1122, see Fire Area A-1.
Access to Room 1407 and the platform is from Room 1408. For a description of access to Room 1408, see Fire Area A-16.
A 4-inch floor drain is provided in each room. The floor drains are located 10 feet away from the barrier wall. The floor drains discharge to a sump in the corridor area, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.3.6      Isolation and Smoke Removal A fire in this area will be contained by the fire barriers. The barrier wall will protect one room from a floor fire in the other. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 39 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 10 of 250)
A.3.7      Analysis A.3.7.1      Fire Suppression Due to the fire barrier separation, a fire in one of the adjacent areas cannot damage the equipment in this area. A fire in one of the rooms at Elevation 1974 will be detected and alarmed by the flame detectors and/or smoke detectors. The fire can be extinguished manually, using the hose stations and/or the portable extinguishers. A fire in this area will be contained by the fire barriers until extinguished. The combustible loading is low. Since the floor on either side of the barrier slopes to drains in the middle of each room, any transient combustible spill (such as lube oil) will flow away from the barrier wall.
Since there is no equipment requiring maintenance in the vicinity of the platform, introduction of transient combustibles in such quantities as to cause fire damage at this elevation is unlikely. A fire in the cable tray will be detected and alarmed by the smoke detector located in this fire area.
The fire can be extinguished from the platform (or the steps leading to the platform) by manual hose stream brought in from Room 1408. A fire in Room 1407 will be detected and alarmed by the detectors in the ceiling.
The fire can be extinguished manually by hose stream brought in from Room 1408. The floor drains in Rooms 1116 and 1117 are adequate to drain the fire fighting water. The floor slopes away from the access doors and barrier walls to the floor drains in the corridor in these rooms.
Therefore, an extinguishing system discharge in one of the adjacent areas will not damage the equipment within this fire area.
A.3.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-3 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-3 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-3.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 40 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 11 of 250)
Fire Area A-4 (Reference A-1801)
A.4.1      Fire Area Description Auxiliary building safety-related pump area Rooms 1107, 1108, 1109, and 1110.
A.4.2      Major Equipment Centrifugal charging pump, safety-injection pump, RHR pump, containment spray pump, coolers for the above pump rooms, RHR room sump pumps, and auxiliary lube oil pump for the centrifugal charging pump.
A.4.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.4.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.4.3-1 Fire Area A-4, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts The Centrifugal Charging Pump Room, is separated from the Safety-Injection Pump Room 1108, by a 2-foot-thick concrete wall with a 3 foot 4 inch x 7 foot 2 inch access way. The RHR Pump Room 1109, is separated from the other rooms by a 2-foot-thick concrete wall. A 3-hour fire door is provided for access to this room from Room 1110.
However, Room 1109 is not credited as a separate Fire Area.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 41 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 12 of 250)
A.4.4      Combustible Loading The cumulative combustible loading classification for Fire Area A-4 is Low.
A.4.5      Fire Protection Smoke detectors are installed in each room. Manual-pull fire alarm stations are located near the exit doorways for this elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A hose station and a portable extinguisher are located in Room 1101. In addition, portable extinguishers are located within the fire area, in Rooms 1110 and 1108. Hose stations and portable extinguishers are also located in Rooms 1120 and 1121 (corridors).
Specific fire hose and extinguisher locations are delineated on drawing A-1801.
Access to Room 1110 is from Room 1121 (corridor) through a watertight door. Access to Room 1109 is from Room 1110 through a 3-hour fire-rated door. Access to Rooms 1107 and 1108 is from Room 1101 through a watertight door.
Rooms 1107 and 1108 have two 4-inch floor drains each. There is one 4-inch floor drain in Rooms 1110 and 1109. A sump with two sump pumps is located in Room 1109. The floor drains are piped to this sump. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.4.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.4.7      Analysis A.4.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers. A fire in this area will be contained by the fire barriers until extinguished manually. Adequate drainage is provided in each room to remove the fire-fighting water. The watertight doors will protect the safe shutdown equipment from damage by water discharge from extinguishing systems in the adjacent areas.
 
Wolf Creek Nuclear Operating Corporation                                                Page 42 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 13 of 250)
A.4.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-4 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-4 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-4.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 43 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 14 of 250)
Fire Area A-5 (Reference A-1801 thru A-1804)
A.5.1      Fire Area Description Auxiliary Building Stairway Room 1119, Elevator Shaft, and Elevator Penthouse Room 1601.
A.5.2      Major Equipment Electric cable and elevator.
A.5.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.5.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.5.3-1 Fire Area A-5, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category South personnel elevator doors and shaft          Fire Door Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts Since no Fire Areas are above the ceiling, it is not rated. Roof construction is non-combustible concrete with built up Class A roofing. Therefore, structural integrity will be maintained in the event of a fire.
A.5.4      Combustible Loading The cumulative combustible loading classification for Fire Area A-5 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 44 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 15 of 250)
A.5.5      Fire Protection A smoke detector is installed at the ceiling of the stairwell. Smoke detectors are installed at the elevator lobby on each floor. Manual-pull stations are located near the exit doors on each floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are located outside the stairway on each floor.
Access to the Fire Area is achieved from any floor elevation of the stairwell, as depicted on drawings A-1801 thru A-1804.
No drains are provided for this Fire Area, as manual fire water suppression efforts will be minimal, considering the limited combustible loading and equipment in the Fire Area.
Additionally, a floor drain is located in Fire Area A-1 just outside the stairwell door at the 1974 elevation. There are no PFSSD equipment or circuits in this area. Therefore, water accumulation in the area would not affect safe shutdown capability.
A.5.6      Isolation and Smoke Removal A fire in the stairway or elevator will be confined by the fire barriers until extinguished.
Refer to Section 4.3.7.2 for smoke removal discussion.
A.5.7      Analysis A.5.7.1          Fire Suppression The stairwell and elevator will be protected from a fire in the adjoining areas by the fire-rated barriers. A fire in the stairway will be detected and alarmed by the smoke detector. The fire will be contained by the fire-rated barrier until extinguished manually, using the hose stations and/or portable extinguishers.
A.5.7.2          Safe Shutdown Capability There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-5.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 45 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 16 of 250)
Fire Area A-6 (Reference A-1801 thru A-1804)
A.6.1      Fire Area Description Auxiliary Building Stairway Room 1127 A.6.2      Major Equipment Electric cable.
A.6.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.6.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.6.3-1 Fire Area A-6, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category 3-hour rated fire wrap protection for            Fire Wrap redundant PFSSD circuits Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts The ceiling in this area forms part of the roof. Since no fire areas are above the ceiling, it is not rated. Roof construction is non-combustible concrete with built up Class A roofing.
Therefore, structural integrity will be maintained in the event of a fire.
A.6.4      Combustible Loading The cumulative combustible loading classification for Fire Area A-6 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                      Page 46 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 17 of 250)
A.6.5      Fire Protection A smoke detector is installed at the ceiling of the stairway tower. The addressable detector alarms locally and in the Control Room. Manual-pull stations are located near the exit doors on each floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are located outside the stairwell on each floor.
Access to the Fire Area is achieved from any floor elevation of the stairwell, as depicted on drawings A-1801 thru A-1804.
No drains are provided for this Fire Area, as manual fire water suppression efforts will be minimal, considering the limited combustible loading and equipment in the Fire Area.
Additionally, a floor drain is located in Fire Area A-1 just outside the stairwell door at the lowest (1974) elevation. There is no PFSSD equipment susceptible to water damage in this area. Therefore, water accumulation in the area would not affect safe shutdown capability.
A.6.6      Isolation and Smoke Removal A fire in the stairway will be contained by the fire barriers until extinguished. Refer to Section 4.3.7.2 for smoke removal discussion.
A.6.7      Analysis A.6.7.1          Fire Suppression The fire barriers will protect the stairwell from a fire in the adjacent areas.
A fire in the stairway will be detected and alarmed by the smoke detector.
The fire can be extinguished manually, using the hose stations and portable extinguishers located at each floor. A fire within the stairway will be contained by the fire barriers until extinguished.
A.6.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-6 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-6 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-6.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 47 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 18 of 250)
Fire Area A-7 (Reference A-1801)
A.7.1      Fire Area Description Boron Injection Tank and Pump Room 1126.
A.7.2      Major Equipment Boron injection tank, boron injection surge tank, boron injection recirculation pumps, piping, and valves.
A.7.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.7.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.7.3-1 Fire Area A-7, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts A.7.4      Combustible Loading The cumulative combustible loading classification for Fire Area A-7 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 48 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 19 of 250)
A.7.5      Fire Protection A smoke detector is installed at the ceiling of this area. A manual-pull station is provided in the corridor adjacent to the watertight door. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A hose station and two portable extinguishers are located in Room 1122 (corridor),
adjacent to the access door.
Access to this area is from Room 1122 through a watertight door. For access to Room 1122, see Fire Area A-1.
One 4-inch floor drain with a sealed cover (to prevent back flooding) is located in this area. The drain is piped to the Auxiliary Building floor drain sump; however, it would not be available during a fire. Fire-fighting water would drain from the room through the open door and into the Auxiliary Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.7.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.7.7      Analysis A.7.7.1          Fire Suppression The fire barriers protect the components within the area from a fire in the adjacent areas. A fire in this area will be detected and alarmed by the smoke detector. The fire can be extinguished manually, using the hose station and/or portable extinguishers located outside the area. The watertight door will protect the equipment in this area against damage from a fire suppression system discharge in the adjacent area.
A.7.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-7 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-7 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-7.
 
Wolf Creek Nuclear Operating Corporation                                                        Page 49 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 20 of 250)
Fire Area A-8 (Reference A-1802)
A.8.1      Fire Area Description Auxiliary building - El. 2000, general area Rooms 1301, 1302, 1306, 1307, 1308, 1311, 1312, 1313, 1314, 1315, 1318, 1319, 1320, and 1321.
A.8.2      Major Equipment Volume control tank and associated piping and valves, containment spray additive tank, reactor coolant filter, seal water return filter, seal water injection filters (2), and boric acid filter, boron thermal regeneration demineralizers (5), cation bed demineralizer and mixed bed demineralizers (2), resin charging tank, ground floor fan coil unit, auxiliary building sampling panel, and load center.
A.8.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.8.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
 
Wolf Creek Nuclear Operating Corporation                                                Page 50 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 21 of 250)
Table A.8.3-1 Fire Area A-8, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category North equipment hatches                            Hatch South equipment hatches                            Hatch Resin loading chute cover plate                    Hatch Hatches for RHR & containment spray valve          Hatch encapsulation tanks Containment post-tensioning hatch covers at Hatch C Buttress Dumbwaiter doors and shaft                        Fire Door South personnel elevator doors and shaft          Fire Door Missile door 13331                                Fire Door Missile door 33044                                Fire Door 1-hour rated fire wrap protection for              Fire Wrap redundant PFSSD circuits Penetration seals that exceed the bounding        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts The Volume Control Tank Room is separated from adjacent rooms by heavy concrete walls and a fire rated floor and ceiling. The wall separating the VCT from the seal water heat exchanger is fire rated for a minimum of 3 hours. Personnel access to the room is through a labyrinth opening with wire mesh doors.
Access to the Volume Control Tank Room is from Room 1320 through a door in Room 1318 and a labyrinth opening (Refer to A-1802). To promote radiological protection, an additional locked wire mesh door has been provided between Rooms 1313 and 1318.
The Volume Control Tank Room 1313 has the tank, piping, and two exposed conduits routed east-west 18 feet above the floor. The adjoining valve compartment, Room 1318, has two motor-operated valves, piping, manual valves, and five exposed conduits.
Therefore, the combustible loading in these two rooms is low. Since access from Room 1320 (corridor) is limited to these two rooms, the transient combustibles introduced into these rooms will be those required for maintenance of equipment located in these rooms.
Any cutting or welding operation will be administratively controlled. Therefore, the quantity of transient combustibles introduced into these rooms will be low and will not produce enough heat, in the event of a fire, to damage the tank, piping, and valves.
 
Wolf Creek Nuclear Operating Corporation                                                      Page 51 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 22 of 250)
A.8.4      Combustible Loading The cumulative combustible loading classification for Fire Area A-8 is Low.
The new resin for the demineralizers in Room 1319 will be brought in through the south end of the corridor and transported up to El. 2026 by the elevator in the south end. The resin will be in a hydrated form and therefore, does not ignite or sustain combustion easily. The demineralizers will be charged with new resin from the floor above. The demineralizers are ASME pressure vessels filled with water. Spent resin in the demineralizers is sluiced and piped to a spent resin storage tank located in the radwaste building. Consequently, the resin in the demineralizers do not pose a fire hazard.
The spent cartridges in the CVCS filters in Room 1302 will be moved to 55-gallon drums, sealed, and removed from the area. Administrative controls ensure that only new cartridges in quantities required for immediate use will be brought into this area and the containers are removed after they are emptied. The demineralizers and filters are not required for a safe shutdown of the plant.
A.8.5      Fire Protection An automatic smoke detection system is installed throughout the Fire Area except in several rooms with low combustible loading and no safe shutdown circuits or equipment (See Attachment A and XX-E-013). Manual-pull stations are located at the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic preaction sprinkler system is installed over cable tray concentrations in Rooms 1301, 1314, and 1320 as identified in Attachment A. In the west corridor (Room 1301), additional sprinkler heads are provided below the cable tray elevation between columns A-2 and A-4. These additional sprinkler heads are provided to protect the cable trays from a transient fire located on the floor. This area contains three racks of cable trays and other obstructions, which may reduce the effectiveness of the ceiling-mounted sprinklers in controlling a transient combustible fire. The system also provides protection for the hatchways at the ceiling of this area located at the north and south ends of the building. The hatches at the center of the building are protected as detailed in M-663-00017A. Hose stations and portable extinguishers are located throughout the area, as delineated on drawing A-1802.
Access to this area for manual fire fighting is available as follows:
: a. Stairwell 4101 from the Turbine Building.
: b. Stairwell 1119 (at the south end) from outside and other buildings.
: c. Stairwell 1127 (at the north end) from other elevations of the Auxiliary Building.
: d. Doors (at the south end) of Room 1301 from outside.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 52 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 23 of 250)
: e. Access to Room 1313 (Volume Control Tank Room) is through Room 1318 and Room 1320 (corridor).
: f. Access to Room 1317 is from Room 1315 and Room 1316.
One 4-inch drain per 1,000 square feet of floor area is provided throughout this Fire Area.
Rooms 1313, 1318, 1311, and 1312 have one 4-inch floor drain per room. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974.
Sump pumps empty the sump. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.8.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.8.7      Analysis A.8.7.1        Fire Suppression The smoke detection system installed throughout the Fire Area except where noted in Attachment A will provide early warning of a fire. Due to low combustible loading, detectors are not installed in the rooms where the CVCS demineralizers, filters, and volume control tank are located.
Hose stations and/or portable extinguishers can be used to extinguish a fire in these areas. The preaction sprinkler system installed over the cable tray concentration will actuate to control a fire below and keep the area cool for fire brigade entry. The sprinkler actuation or malfunction will be identified by Control Room annunciation. In the event of a failure of the automatic system, the fire can be extinguished manually using hose stations. Adequate floor drains are provided to remove the fire suppression system discharge. There is no safe shutdown equipment susceptible to water damage in this area.
The volume control tank in Room 1313 is enclosed by concrete walls of adequate thickness to prevent damage from a fire in the adjacent areas.
A water inventory is maintained within the tank at all times. The combustible loading in this area is low. Therefore, a fire in this room will not damage the tank.
 
Wolf Creek Nuclear Operating Corporation                                              Page 53 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 24 of 250)
A.8.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-8 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-8 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-8.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 54 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 25 of 250)
Fire Area A-9 (Reference A-1802 and A-1803)
A.9.1      Fire Area Description RHR Heat Exchanger Room 1309.
A.9.2      Major Equipment RHR heat exchanger (B) and associated piping and valves.
A.9.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.9.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.9.3-1 Fire Area A-9, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts This Fire area extends through two floor elevations. The ceiling forms the roof of the building and is not required to be fire rated. A hatch with a removable concrete cover is provided in the ceiling for pulling the tube bundle or the heat exchanger. A 1-foot-6-inch-thick, 8-foot-0-inch-high concrete partition wall is located within the Fire Area between the heat exchanger and the valve compartment.
A.9.4      Combustible Loading The cumulative combustible loading classification for Fire Area A-9 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 55 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 26 of 250)
A.9.5      Fire Protection Due to the low combustible loading in this area and the separation of redundant equipment by fire barriers, smoke detectors are not installed in this area. In the event of a fire in this area, plant notification can be made by the activation of a manual-pull station in the corridor.
Hose stations are located in Room 1301 outside the Fire Area. Two portable extinguishers are located in Room 1301.
Access to this area is from Room 1301 through a door. For access to Room 1301, see Fire Area A-8.
Two 4-inch floor drains, one on either side of the partition wall, are provided. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974.
The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.9.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.9.7      Analysis A.9.7.1          Fire Suppression The fire barriers protect the safe shutdown equipment from a fire in adjacent areas. Hose stations or portable extinguishers are available to manually extinguish a fire. A fire in this area will be contained by the fire barriers. Adequate drainage is provided to remove any fire-fighting water.
Since the floor in adjoining corridor Room 1301 slopes away from the door to a floor drain, a fire suppression system discharge in the adjacent area cannot damage the equipment in this area.
A.9.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-9 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area A-9 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-9.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 56 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 27 of 250)
Fire Area A-10 (Reference A-1802 and A-1803)
A.10.1    Fire Area Description RHR Heat Exchanger Room 1310.
A.10.2    Major Equipment RHR heat exchanger (A) and associated piping and valves.
A.10.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.10.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.10.3-1 Fire Area A-10, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts This Fire Area extends through two floor elevations. The ceiling forms the roof of the building and is not required to be fire rated. A hatch with a removable concrete cover is provided in the ceiling for pulling the tube bundle or the heat exchanger. A 1-foot-6-inch-thick, 8-foot-0-inch-high concrete partition wall is located within the Fire Area between the heat exchanger and the valve compartment.
A.10.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-10 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                      Page 57 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 28 of 250)
A.10.5    Fire Protection Due to low combustible loading and redundant train separation, smoke detectors are not installed in this area. In the event of a fire in this area, plant notification can be made by the activation of a manual-pull station in the corridor.
A hose station is located in Room 1301 outside the Fire Area. Two portable extinguishers are located in Room 1301.
Access to this area is from Room 1301 through a door. For access to Room 1301, see Fire Area A-8.
Two 4-inch floor drains, one on either side of the partition wall, are provided. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974.
The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.10.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.10.7    Analysis A.10.7.1          Fire Suppression The fire barriers protect the safe shutdown equipment from a fire in adjacent areas. Hose stations or portable extinguishers can be used to manually suppress a fire. The fire will be contained by the fire barriers.
Adequate drainage is provided to remove the fire-fighting water. Since the floor in the adjoining corridor Room 1301 slopes away from the door to a floor drain, a fire suppression system discharge in the adjacent area cannot damage the equipment in this area.
A.10.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-10 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-10 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-10.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 58 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 29 of 250)
Fire Area A-11 (Reference A-1802)
A.11.1    Fire Area Description Cable Chase Room 1335, Auxiliary Building - El. 2000 to 2026.
A.11.2    Major Equipment Electric cable only.
A.11.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.11.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.11.3-1 Fire Area A-11, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A.11.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-11 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 59 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 30 of 250)
A.11.5    Fire Protection Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located at normal exits from this floor area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Room 1320 (Fire Area A-8).
Access to the chase is through a 3 foot 6 inch by 4 foot 0 inch, 3-hour-rated fire door. The access door is within 25 feet of the hose station.
Drainage in this area is by one 4-inch floor drain. This is more than adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Auxiliary Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.11.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
A.11.7    Analysis A.11.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, hose streams can be directed through the access opening to extinguish the fire.
 
Wolf Creek Nuclear Operating Corporation                                              Page 60 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 31 of 250)
A.11.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-11 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-11 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-11.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 61 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 32 of 250)
Fire Area A-12 (Reference A-1802)
A.12.1    Fire Area Description Cable Chase Room 1336, Auxiliary Building - El. 2000 to 2026.
A.12.2    Major Equipment Electric cable only A.12.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.12.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.12.3-1 Fire Area A-12, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A.12.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-12 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 62 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 33 of 250)
A.12.5    Fire Protection Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located at normal exits from this floor area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Room 1314 (Fire Area A-8).
Access to the chase is through a 3 foot 6 inch by 4 foot, 3-hour-rated door. The access door is within 30 feet of the hose station.
Drainage in this area is by one 4-inch floor drain. This is more than adequate to handle maximum sprinkler system discharge or hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Auxiliary Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.12.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
A.12.7    Analysis A.12.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers until extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
A.12.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-12 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-12 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-12.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 63 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 34 of 250)
Fire Area A-13 (Reference A-1802)
A.13.1    Fire Area Description Auxiliary Feedwater Pump Room 1325.
A.13.2    Major Equipment Motor-driven auxiliary feedwater pump B and pump room cooler.
A.13.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.13.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.13.3-1 Fire Area A-13, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts Watertight doors with 6-inch-high curb are located in the south and east fire barrier walls.
A.13.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-13 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 64 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 35 of 250)
A.13.5    Fire Protection Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A hose station and two portable extinguishers are located in the corridor (Room 1329) outside this fire area. All areas are within reach of this hose station.
Access for manual firefighting is through a watertight door from Room 1329. Access to Room 1329 is from the Turbine Building.
Two 4-inch floor drains are provided in this area. The floor drain is piped to the Auxiliary Feedwater Room sump located in Room 1128 (El. 1974). The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
A.13.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.13.7    Analysis A.13.7.1          Fire Suppression This area is protected from a fire in the adjacent areas by fire barriers. A fire in the area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using the hose station and/or the portable extinguishers located in the adjoining corridor (Room 1329). A fire will be contained by the fire barriers until extinguished.
Adequate drainage is provided to drain the fire-fighting water. The watertight doors will protect the safe shutdown equipment from damage by water discharged by extinguishing systems in the adjacent areas.
A.13.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-13 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-13 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 65 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 36 of 250)
Fire Area A-14 (Reference A-1802)
A.14.1    Fire Area Description Auxiliary Feedwater Pump Room 1326.
A.14.2    Major Equipment Motor-driven auxiliary feedwater pump A and pump room cooler.
A.14.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.14.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.14.3-1 Fire Area A-14, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A watertight door with 6-inch-high curb is located in the east fire barrier walls.
A.14.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-14 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 66 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 37 of 250)
A.14.5    Fire Protection Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A hose station and two portable extinguishers are located in the corridor (Room 1329) outside this fire area. All areas are within reach of this hose station.
Access for manual fire fighting is through a watertight door from Room 1329. Access to Room 1329 is from the Turbine Building.
Two 4-inch floor drains are provided in this area. The floor drain is piped to the Auxiliary Feedwater Room sump located in Room 1128 (Elevation 1974). The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
A.14.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.14.7    Analysis A.14.7.1          Fire Suppression This area is protected from a fire in the adjacent areas by fire barriers. A fire in the area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using the hose station and/or the portable extinguishers located in the adjoining corridor (Room 1329). A fire will be contained by the fire barriers. Adequate drainage is provided to drain all fire-fighting water. The watertight doors will protect the safe shutdown equipment from damage by water discharge from extinguishing systems in the adjacent areas.
A.14.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-14 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-14 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 67 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 38 of 250)
Fire Area A-15 (Reference A-1802)
A.15.1    Fire Area Description Auxiliary Feedwater Pump Room 1331.
A.15.2    Major Equipment Turbine-driven auxiliary feedwater pump.
A.15.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.15.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.15.3-1 Fire Area A-15, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Blowout panel                                      Hatch Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A watertight, missile-protection door with 6-inch- high curb is located in the west fire barrier wall.
A.15.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-15 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 68 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 39 of 250)
A.15.5    Fire Protection Automatic smoke detection is provided in this area. Rate-compensated thermal detectors are also installed in this area. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A hose station and two portable extinguishers are located in the corridor (Room 1329) outside this Fire Area. All areas are within reach of this hose station. In addition to the above, a manually charged fixed water spray system is installed to protect the turbine and pump lubricating oil lines and bearings. A manual system precludes any water damage to the turbine due to inadvertent actuation. The manual valve to activate the system is located outside the Fire Area in Room 1329 and is electrically supervised.
Access for manual fire fighting is through a watertight door from Room 1329. Access to Room 1329 is from the Turbine Building.
Two 4-inch floor drains are provided in this area. The floor drain is piped to the Auxiliary Feedwater Room sump located in Room 1128 (El. 1974). The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
A.15.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.15.7    Analysis A.15.7.1        Fire Suppression This area is protected from a fire in the adjacent areas by fire barriers. A fire in the area will be detected and alarmed by the automatic detection system. The manual spray system can be actuated to extinguish the fire.
In case of a malfunction of the spray system, the hose station and/or the portable extinguishers located in the adjoining corridor (Room 1329) will provide adequate backup for fire suppression. A fire will be contained by the fire barriers. Adequate drainage is provided to drain the fire-fighting water. The watertight doors will protect the safe shutdown equipment from damage by water discharged by extinguishing systems in the adjacent areas.
 
Wolf Creek Nuclear Operating Corporation                                              Page 69 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 40 of 250)
A.15.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-15 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-15 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 70 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 41 of 250)
Fire Area A-16 (Reference A-1803)
A.16.1    Fire Area Description Auxiliary Building El. 2026, general area Rooms 1401, 1402, 1406, and 1408.
A.16.2    Major Equipment CCW heat exchangers, pumps, pump room coolers, piping, and valves.
A.16.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.16.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.16.3-1 Fire Area A-16, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category North equipment hatches                            Hatch South equipment hatches                            Hatch Containment post-tensioning hatch covers at Hatch C Buttress South personnel elevator doors and shaft            Fire Door Missile door 41015                                  Fire Door Cable tray firestops and cable tray covers          Cable Tray Firestops & Cable Tray within Combustible Control Zone                    Covers Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                      Page 71 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 42 of 250)
Six-inch high curbs are installed around Rooms 1401 and 1406 containing the redundant CCW system equipment. These rooms are separated horizontally by 75 feet (minimum).
The fire barrier enclosure around Fire Areas A-9 and A-10 is located between these two rooms.
A.16.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-16 is Low.
A 20 ft. Combustible Control Zone separation area is administratively maintained to strictly control transient combustibles in the limiting separation area between redundant PFSSD circuits within the east corridor of 1408. Specifically, the Combustible Control Zone is located between columns A7 and A8 from the Containment wall to the east wall of RHR Heat Exchanger Room 1309. Insitu combustibles within the Combustible Control Zone do not pose a fire propagation path that would disable both trains of redundant PFSSD equipment.
A.16.5    Fire Protection Automatic smoke detection is provided in this area. Manual-pull stations are located at exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic preaction-type sprinkler system is installed over cable tray concentrations in Rooms 1402 and 1408 as detailed in Attachment A. The system also provides protection for the hatchways at the ceiling of this area.
In the east corridor (Room 1408), additional sprinkler heads are provided below the cable tray elevation between columns A-1 and A-4. These additional sprinkler heads are provided to protect the cable trays from a transient fire located on this floor. This area contains cable trays and other obstructions, which may reduce the effectiveness of the ceiling-mounted sprinklers in controlling a transient combustible fire.
Hose stations and portable extinguishers are located throughout the area, as delineated on drawing A-1803.
Access to this area for manual fire fighting is available as follows:
: a. Stairwell 4101 from the Turbine Building
: b. Stairwell 1119 (at the south end) from other elevations of the Auxiliary Building
: c. Stairwell 1127 (at the north end) from other elevations of the Auxiliary Building
 
Wolf Creek Nuclear Operating Corporation                                                    Page 72 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 43 of 250)
Steel cable tray covers are provided for cable trays within the Combustible Control Zone, while cable tray raceways 116J5B30, 116U5D30, and 116U5E30 are provided with a Silicone Foam RTV firestop. These cable tray covers and fire stops are administratively controlled.
One 4-inch drain per 1,000 square feet of floor area is provided in the corridor area (Rooms 1402 and 1408). Six 4-inch and two 4-inch drains are provided in Rooms 1401 and 1406, respectively. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.16.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. The 6-inch-high curbing in Rooms 1401 and 1406 and the floor drains will prevent any transient combustible spill (such as lube oil) from spreading from one room to the other. The curb will also protect Rooms 1401 and 1406 against a spill in the corridor (Room 1408). Refer to Section 4.3.7.2 for smoke removal discussion.
A.16.7    Analysis A.16.7.1        Fire Suppression The fire barriers will contain a fire in this area and will also protect this area from a fire in any of the adjoining areas. The smoke detectors will provide an early warning of a fire in this area. The fire can be extinguished manually using the hose stations and/or the portable extinguishers.
The Combustible Control Zone ensures that fire will not involve redundant PFSSD components within the Fire Area.
The automatic detection system will trip the sprinkler system deluge valve when a cable tray fire is detected. The automatic system will actuate to extinguish the fire. The sprinkler actuation or a malfunction will be identified by Control Room annunciation. In the event of a failure of the automatic system, the fire can be extinguished manually using the hose stations.
Adequate drainage is provided in each room to remove the fire-fighting water. The 6-inch-high curb installed around Rooms 1401 and 1406 will protect the safe shutdown equipment against damage from water discharged by the sprinkler system in Rooms 1402 and 1408.
 
Wolf Creek Nuclear Operating Corporation                                              Page 73 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 44 of 250)
A.16.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-16 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-16 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-16.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 74 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 45 of 250)
Fire Area A-17 (Reference A-1803)
A.17.1    Fire Area Description South Electrical Penetration Room 1409.
A.17.2    Major Equipment Motor control centers, load center, switchgear, room cooler, electric cable, balance of plant computer cabinets.
A.17.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.17.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.17.3-1 Fire Area A-17, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Reactor Building electrical penetrations            Penetration Seal Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A.17.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-17 is Low.
Internal panel surfaces of RJ160A/B/C/D are finished with paint of low fire rating. All cable in these panels meets the vertical flame requirements of IPCEA S-19-81 and/or IEEE 383 for flame resistance. The panels are provided with keylocks to control access to the panel interiors.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 75 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 46 of 250)
A.17.5    Fire Protection This area is provided with a cross-zoned smoke detection system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
The Halon 1301 system serves the room, with the exception of the electrical chase area, and is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An actuation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation.
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
An automatic wet pipe sprinkler system serves the electrical chase area of Room 1409.
The system is equipped with closed head spray nozzles and a standard sprinkler, with deflector shield, at an intermediate level.
Access to the area is via adjacent Corridor 1408.
Two 4-inch floor drains are provided in this area. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.17.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.17.7    Analysis A.17.7.1        Fire Suppression The fire barriers enclosing the Fire Area will protect this area from a fire in the adjoining areas and will contain a fire within this area until extinguished. The fire will be detected, alarmed, and suppressed by the Halon system or the wet pipe sprinkler system. The Halon system discharge or a malfunction will be identified Control Room annunciation.
In the event of a malfunction of the automatic systems, the hose station in Room 1408 can be used to extinguish the fire.
 
Wolf Creek Nuclear Operating Corporation                                              Page 76 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 47 of 250)
A.17.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-17 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-17 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-17.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 77 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 48 of 250)
Fire Area A-18 (Reference A-1803)
A.18.1    Fire Area Description North Electrical Penetration Room 1410.
A.18.2    Major Equipment Motor control centers, load center, switchgear, room cooler, electric cable, balance of plant computer cabinets.
A.18.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.18.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.18.3-1 Fire Area A-18, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Reactor Building electrical penetrations                Penetration Seal 1-hour rated fire wrap protection for redundant        Fire Wrap PFSSD circuits Penetration seals that exceed the bounding              Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected          Structural Steel Fireproofing thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                    Page 78 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 49 of 250)
A.18.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-18 is Low.
Internal panel surfaces of RJ159A/B/C/D are finished with paint of low fire rating. All cable in these panels meets the vertical flame requirements of IPCEA S-19-81 and/or IEEE 383 for flame resistance. The panels are provided with keylocks to control access to the panel interiors.
A.18.5    Fire Protection This area is provided with a cross-zoned smoke detection system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
The Halon 1301 system serves the room with the exception of the electrical chase area and is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An actuation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation.
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
An automatic wet pipe sprinkler system serves the electrical chase area of Room 1410.
The system is equipped with closed head spray nozzles and a standard sprinkler, with deflector shield, at an intermediate level.
A hose station and portable extinguishers are located outside the area in Room 1408 (corridor). Access for manual fire fighting is through the two doors from Room 1408. For access to Room 1408, see Fire Area A-16.
Access to the area is via adjacent Corridor 1408.
Two 4-inch floor drains are provided in this area. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.18.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                Page 79 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 50 of 250)
A.18.7    Analysis A.18.7.1      Fire Suppression The fire barriers enclosing this Fire Area will protect this area from a fire in the adjoining areas and will contain a fire within the area until extinguished. The fire will be detected, alarmed, and suppressed by the automatic Halon system or the wet pipe sprinkler system. The Halon system discharge or a malfunction will be identified by Control Room annunciation. In the event of a malfunction of the automatic systems, the hose station in Room 1408 can be used to extinguish the fire.
Adequate drainage is provided to drain the fire-fighting water. Should manual firefighting be required, water damage to the electrical equipment in this room could result (with or without associated fire damage);
however, the water damage would not adversely affect safe shutdown.
The redundant equipment is located in another fire area. Since the floor in Room 1408 (corridor) slopes away from the doors to this room, water damage due to a sprinkler discharge in adjoining areas is not possible.
A.18.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-18 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-18 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-18.
 
Wolf Creek Nuclear Operating Corporation                                                      Page 80 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 51 of 250)
Fire Area A-19 (Reference A-1804)
A.19.1    Fire Area Description Auxiliary Building El. 2047'-6" general area Rooms 1504, 1506, and 1513.
A.19.2    Major Equipment Auxiliary/fuel building normal exhaust filter, adsorber and exhaust fans, containment purge filter adsorber unit, containment minipurge and shutdown purge exhaust fans, access control exhaust filter adsorber unit and exhaust fans, condenser air removal filtration system filter adsorber unit and fans, control building air supply unit, control building exhaust fans, electrical equipment room cooler, auxiliary building supply air unit, containment purge and minipurge supply units, main steam enclosure supply unit, main steam enclosure building exhaust fans, unit heaters, hydrogen analyzers.
A.19.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.19.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.19.3-1 Fire Area A-19, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category North equipment hatch                              Hatch Containment post-tensioning hatch covers at        Hatch C Buttress Missile door 41017                                Fire Door Reactor Building mechanical penetrations          Penetration Seal Penetration seals that exceed the bounding        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected    Structural Steel Fireproofing thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                    Page 81 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 52 of 250)
A.19.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-19 is Low.
A small cylinder of hydrogen/nitrogen mix is located on the hydrogen analyzer skid. The skid is specifically designed for use with hydrogen. The cylinder, which contains 10%
hydrogen is used as a calibration gas. If the gas were to leak, it would quickly dissipate below the 4% LEL of hydrogen. Therefore, the small cylinder does not introduce any additional impact on safe shutdown capability.
A.19.5    Fire Protection An automatic smoke detection system is installed in this area. A duct smoke detector is provided for the air intake of SGK02 in Room 1513. Manual-pull stations are located near the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
All charcoal adsorber units, except the containment purge filter adsorber, operate during normal plant operation. Downstream of each charcoal bed is a thermistor-type continuous thermal detector, which alarms in the control room at high air stream temperature. The bed temperature is therefore constantly monitored for the containment purge adsorber units and for the other units when not in use. The charcoal beds are equipped with a hose connection to provide manual water spray protection.
Hose stations and portable extinguishers are located throughout this area, as delineated on drawing A-1804.
Access to this area is as follows:
: a. From Turbine Building stairway (Room 4101)
: b. From Control Room A/C and Filtration Room 1512
: c. From the north and south stairways (Rooms 1127 and 1119)
One 4-inch floor drain per 1,000 square feet of floor area is provided in this area. The drains are piped to a sump at El. 1967 accessed from Auxiliary Building floor El. 1974.
The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.19.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                Page 82 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 53 of 250)
A.19.7    Analysis A.19.7.1      Fire Suppression The fire barrier separation provided for this area will contain a fire until extinguished and will protect the area from a fire in any one of the adjoining areas. The automatic detection system will provide an early warning of a fire in this area. The fire can be extinguished manually, using the hose stations and/or portable extinguishers located throughout the area. Adequate drainage is provided to remove the fire-fighting water.
There is no safe shutdown equipment susceptible to water damage in this area.
A.19.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-19 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-19 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-19.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 83 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 54 of 250)
Fire Area A-20 (Reference A-1804)
A.20.1    Fire Area Description Personnel Hatch and CCW Surge Tank Area Rooms 1502, 1503, 1505, and 1507.
A.20.2    Major Equipment CCW surge tanks, CCW chemical addition tank, piping and valves.
A.20.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.20.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.20.3-1 Fire Area A-20, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category South equipment hatch                              Hatch Reactor Building personnel hatch                  Hatch South personnel elevator doors and shaft          Fire Door Reactor Building mechanical penetrations          Penetration Seal Penetration seals that exceed the bounding        Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected    Structural Steel Fireproofing thermal shorts A 12-inch-thick concrete barrier wall extending 15 feet from the west barrier separates the redundant CCW surge tanks. The tank outside diameter is 8 feet.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 84 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 55 of 250)
A.20.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-20 is Low.
A small cylinder of hydrogen/nitrogen mix is located on the hydrogen analyzer skid. The skid is specifically designed for use with hydrogen. The cylinder, which contains 10%
hydrogen is used as a calibration gas. If the gas were to leak, it would quickly dissipate below the 4% LEL of hydrogen. Therefore, the small cylinder does not introduce any additional impact on safe shutdown capability.
A.20.5    Fire Protection Smoke detectors are installed in the elevator lobby and over the cable trays in Rooms 1505 and 1507. Manual-pull stations are installed at the exit door to the stairway.
Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A hose station and one portable extinguisher are installed in the elevator lobby within the Fire Area. If access to these are blocked by a fire in the area, the hose station located in Room 1504 (approximately 50 feet from the fire area) and portable extinguisher outside the area will provide backup fire-fighting capability (see drawing A-1804).
Access for manual fire fighting is as follows:
: a. From Room 1504 (see Fire Area A-19 for access to Room 1504)
: b. From stairway 1119
: c. From Fuel Building (Room 6301)
Four-inch floor drains are provided in this area as follows:
Room                        No. of Drains 1502                                    1 1503                                    1 Elevator lobby                          1 1505                                    1 1507                                    2 The drains are piped to a sump at El. 1967 accessed from Auxiliary Building floor El.
1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 85 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 56 of 250)
A.20.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.20.7    Analysis A.20.7.1        Fire Suppression The fire barrier separation provided will protect this area from a fire in adjacent areas and will also contain a fire within the area until extinguished. A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using the hose stations and/or portable extinguishers located inside the area or in the adjacent Room 1504.
Adequate drainage is provided to remove the fire-fighting water. There is no safe shutdown equipment susceptible to water damage in this area.
A.20.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-20 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-20 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-20.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 86 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 57 of 250)
Fire Area A-21 (Reference A-1804)
A.21.1    Fire Area Description Control Room AC and Filtration Units Room 1501.
A.21.2    Major Equipment Control room ac unit (B), control room filtration system filter/adsorber unit (B), control filtration fan (B), motor control center.
A.21.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.21.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.21.3-1 Fire Area A-21, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts A.21.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-21 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 87 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 58 of 250)
A.21.5    Fire Protection Automatic smoke detectors are installed in this room. Manual-pull stations are installed at the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A hose station is installed in this area. If access to this hose station is blocked by a fire, the hose station located in Room 1506 (corridor) can be used (see drawing A-1804). This hose station is approximately 20 feet away from the access door to this area. Two portable extinguishers are located in Room 1506.
The charcoal/adsorber unit is in the control room filtration system. Downstream of each charcoal bed is a thermistor-type continuous detector, which alarms in the Control Room at high airstream temperature. The charcoal filters are equipped with a hose connection to provide manual water spray protection.
Access to this fire area is as follows:
: a. From Room 1506 (see Fire Area A-19 for access to Room 1506)
: b. From Control Building through the adjacent Fire Area A 22 (Room 1512)
Two 4-inch floor drains are provided in this area. The drains are piped to a sump at El.
1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.21.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.21.7    Analysis A.21.7.1        Fire Suppression The fire barrier separation provided for this area will contain a fire within the area until extinguished and will protect this area from a fire in adjacent areas. The automatic detection system will provide an early warning of a fire. The fire can be extinguished manually, using the hose stations and/or the portable extinguishers. Adequate drainage is provided to remove the fire-fighting water. Water or fire damage to the safe shutdown equipment will not prevent the safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                              Page 88 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 59 of 250)
A.21.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-21 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-21 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-21.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 89 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 60 of 250)
Fire Area A-22 (Reference A-1804)
A.22.1    Fire Area Description Control Room AC and Filtration Units Room 1512.
A.22.2    Major Equipment Control room AC unit (A), control room filtration system filter/adsorber unit (A), control filtration fan (A), motor control center.
A.22.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.22.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.22.3-1 Fire Area A-22, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Fire dampers GKD0180 and GKD0182                    Fire Damper located beyond barrier plane Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A.22.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-22 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 90 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 61 of 250)
A.22.5    Fire Protection Automatic smoke detectors are installed in this room. Manual-pull stations are installed at the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
The charcoal/adsorber unit is in the control room filtration system. Downstream of each charcoal bed is a thermistor-type continuous detector, which alarms in the control room at high airstream temperature. The charcoal filters are equipped with a hose connection to provide manual water spray protection.
Two portable extinguishers are installed in this area. Additional portable extinguishers and a hose station are located in Room 1513 (see drawing A-1804).
Access to this fire area is as follows:
: a. From Room 1506 (see Fire Area A-19 for access to Room 1506)
: b. From Turbine Building through Room 1513
: c. From Control Building Two 4-inch floor drains are provided in this area. The drains are piped to a sump at El.
1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.22.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.22.7    Analysis A.22.7.1        Fire Suppression The fire barrier separation provided for this area will contain a fire within the area until extinguished and will protect this area from a fire in adjacent areas. The automatic detection system will provide an early warning of a fire.
The fire can be extinguished manually, using the hose stations and/or the portable extinguishers. Adequate drainage is provided to remove the fire-fighting water. Water or fire damage to the safe shutdown equipment will not prevent the safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                              Page 91 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 62 of 250)
A.22.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-22 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-22 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-22.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 92 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 63 of 250)
Fire Area A-23 (Reference A-1803 and A-1804)
A.23.1    Fire Area Description Main Steam and Feedwater Valve Compartment Room 1508, 1509, 1411, and 1412.
A.23.2    Major Equipment Main steam piping and isolation valves, feedwater piping and isolation valves, main steam safety relief valves, main steam atmospheric relief valves, steam generator blowdown isolation valves, auxiliary feedwater pump turbine steam supply valves, pressure transmitters, flow transmitters.
A.23.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.23.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.23.3-1 Fire Area A-23, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Emergency escape hatch                              Hatch 20 unsealed floor drains to Turbine Building      Fire Barrier Missile Shield                                      Fire Barrier Reactor Building mechanical penetrations            Penetration Seal Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                    Page 93 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 64 of 250)
The fire area below the 2065 elevation is divided into two compartments by a 2-foot-thick concrete wall. A 9-foot x 24-foot vent opening is located at the ceiling of each compartment. The barrier wall between the two compartments has a 27-foot wide x 23-foot high vent opening located approximately 34 feet above the floor. These vent openings are required to prevent over pressurization of the compartment in the event of a postulated break of main steam piping. Due to the existence of the vent opening, the barrier wall is not fire rated.
A.23.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-23 is Low.
A.23.5    Fire Protection An automatic detection system consisting of infrared flame detectors is installed in this Fire Area. Manual-pull stations are installed in Room 1408. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a pull station alarm is point addressable, while detection is zoned, for a quick and easy means to identify the location associated with the device in alarm.
Portable extinguishers are located in each compartment. A hose station and additional portable extinguishers are located in Room 1506. The hose station is approximately 25 feet from the access door into Room 1508. All areas of the two compartments are within reach of this hose station. Additional hose length, if required, can be added from adjacent hose racks in Room 1506.
Access to this area is through an alarmed access door from stairway Room 1127.
Access openings in the barrier wall and platforms installed at El. 2042 and 2030 provide access between compartments. An intermediate platform is installed at El. 2037 feet            1/2 inches in each compartment; however, access between compartments at this elevation is not possible. An emergency escape hatch to the Turbine Building is located in the torsional restraint structure adjacent to this fire area. Access to this area is from the platform at El. 2030 in Room 1412.
Adequate fire water drainage is ensured by the two 20 diameter unsealed floor drains to the Turbine Building that are provided for drainage in the event of a feedwater pipe rupture within the area. Additionally, drainage is provided from the area by the oily waste drain system, which is piped to the Auxiliary Feedwater Room sump located in Room 1128 (El. 1974). The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
A.23.6    Isolation and Smoke Removal A fire in one of the compartments will be contained by the fire barriers and the concrete barrier wall until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                Page 94 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 65 of 250)
A.23.7    Analysis A.23.7.1      Fire Suppression A fire in this area will be detected and alarmed by the detection system.
The fire can be extinguished manually, using the portable extinguishers and/or the hose station in Room 1506. The safe shutdown instrumentation in this area has watertight enclosures. All the safe shutdown equipment in these rooms is qualified to a steam environment and an ambient temperature of 320 F.
Since the access to this area is controlled and limited, the transient combustibles introduced into these rooms will be those associated with the maintenance of equipment located in these rooms. Any major maintenance work on the isolation valves or the atmospheric relief valves will require a plant shutdown. (Maintenance on these valves will normally be done during refueling outage). Any postulated transient fire will not damage the 2-foot-thick concrete wall. Due to low combustible loading and control on access and transient combustibles, this area is judged to require a degree of fire protection equivalent to the Reactor Building.
Therefore, the provisions of Appendix R, Section III.G.2.f are applied to this area.
A.23.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-23 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-23 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-23.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 95 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 66 of 250)
Fire Area A-24 (Reference A-1802)
A.24.1    Fire Area Description North Pipe Penetration Room 1323.
A.24.2    Major Equipment Containment isolation valves and piping.
A.24.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.24.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.24.3-1 Fire Area A-24, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category 3-hour rated fire wrap protection for redundant      Fire Wrap PFSSD circuits Reactor Building mechanical penetrations              Penetration Seal Penetration seals that exceed the bounding            Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected        Structural Steel Fireproofing thermal shorts A.24.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-24 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 96 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 67 of 250)
A.24.5    Fire Protection An automatic smoke detection system is installed in this area. Manual-pull stations are located at the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A hose station and portable extinguishers are located outside the area in Room 1320.
Access is from Room 1320 through a door.
For access to Room 1320, see Fire Area A-8.
Three 4-inch floor drains are provided in this area. These drains are piped to a sump at El. 1967 accessed from Auxiliary Building floor El. 1974. This sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.24.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.24.7    Analysis A.24.7.1        Fire Suppression Due to low combustible loading, a fire in this area is unlikely. A fire will be detected by the smoke detection system and can be extinguished manually, using the portable extinguishers and/or the hose station in Room 1320. The fire barriers protect the safe shutdown equipment from a fire in all adjacent areas. A fire occurring in this area will be contained by the fire barriers.
Adequate drainage is provided to remove the fire-fighting water.
A.24.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-24 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-24 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-24.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 97 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 68 of 250)
Fire Area A-25 (Reference A-1802)
A.25.1    Fire Area Description South Pipe Penetration Room 1322.
A.25.2    Major Equipment Containment isolation valves and piping.
A.25.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.25.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.25.3-1 Fire Area A-25, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Reactor Building mechanical penetrations            Penetration Seal Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A.25.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-25 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 98 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 69 of 250)
A.25.5    Fire Protection An automatic smoke detection system is installed in this area. Manual pull stations are located at the exit doors of this floor.
A hose station and two portable extinguishers are located outside the area in Room 1314.
Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Access is from Room 1314 through a 3-hour-rated fire door. For access to Room 1314, see Fire Area A-8.
Three 4-inch floor drains are provided in this area. The drains are piped to a sump at El.
1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.25.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.25.7    Analysis A.25.7.1        Fire Suppression Due to a low combustible loading, a fire in this area is highly unlikely. A fire will be detected by the smoke detection system and can be extinguished manually, using the portable extinguishers and/or hose stations in Room 1314. The fire barriers protect the safe shutdown equipment from a fire in all adjacent areas. A fire occurring within this area will be contained by the fire barriers.
Adequate drainage is provided to remove any fire-fighting water.
 
Wolf Creek Nuclear Operating Corporation                                              Page 99 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 70 of 250)
A.25.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-25 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-25 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-25.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 100 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 71 of 250)
Fire Area A-26 (Reference A-1803)
A.26.1    Fire Area Description Room 1405 and Room 1415.
A.26.2    Major Equipment Decontamination area scrubbers and I&C Hot Shop.
A.26.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.26.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.26.3-1 Fire Area A-26, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Resin loading chute cover plate                    Hatch Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A.26.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-26 is Low. Room 1405 is a designated combustible material staging area.
 
Wolf Creek Nuclear Operating Corporation                                                      Page 101 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 72 of 250)
The resin loading chute for the demineralizers located in El. 2000 is located in this area.
Resins are received in a hydrated form, and, therefore, they do not readily ignite or sustain combustion. Administrative controls will ensure that resins only in quantities required for immediate use in recharging the demineralizers will be brought into this area.
In the event that the resins dehydrate and ignite, the fire barriers enclosing this area will contain the fire and prevent damage to equipment in adjacent areas.
A.26.5    Fire Protection An automatic smoke detection system is installed in Rooms 1405 and 1415. Manual-pull stations are located at the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Two hose stations located in Room 1408 are within reach of this area. Two portable extinguishers are located in Room 1408 outside the area.
Access to Room 1405 is from 1408, through a 3-hour fire door, and access to Room 1415 is from Room 1408 through a 3-hour fire door. Fire separation between rooms 1405 and 1415 is not required. For access to Room 1408, see Fire Area A-16.
One 4-inch floor drain is provided in Room 1405 and two 4-inch drains in Room 1415.
The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building Floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.26.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.26.7    Analysis A.26.7.1          Fire Suppression The fire barrier separation provided for this area (Rooms 1405 and 1415) will contain a fire in this area and will protect this area from a fire in any of the adjoining areas. The detection system will provide an early warning of a fire. The fire can be extinguished manually, using the hose station and/or portable extinguishers located outside the fire area.
Adequate drainage is provided to remove all fire-fighting water. There is no safe shutdown equipment susceptible to water damage in area A-26.
 
Wolf Creek Nuclear Operating Corporation                                              Page 102 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 73 of 250)
A.26.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-26 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-26 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-26.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 103 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 74 of 250)
Fire Area A-27 (Reference A-1803)
A.27.1    Fire Area Description Reactor Trip Switchgear Room 1403.
A.27.2    Major Equipment Reactor trip switch gear, MG sets, load centers, rod control and rod-drive power supply control cabinets, 125-V dc panel.
A.27.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.27.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.27.3-1 Fire Area A-27, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Missile door 14032                                  Fire Door Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A.27.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-27 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 104 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 75 of 250)
A.27.5    Fire Protection This area is provided with a cross-zoned smoke detection system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
The Halon 1301 system installed is capable of attaining a minimal 5 percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An actuation station is provided to discharge the system manually. An activation by any automatic method will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air conditioning fan motors, and discharge the system after an adequate time delay for evacuation. The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
A hose station and three portable extinguishers are located within the area. If access to these are blocked by a fire, additional hose stations and portable extinguishers located outside the area in Rooms 1402 and 3503 (Communications Corridor) are available.
Access for manual fire-fighting is from Rooms 1402 and 3503. For access to Rooms 1402 and 3503, see Fire Areas A-16 and CC-1, respectively.
Four 4-inch floor drains are provided in this area. The drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
A.27.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.27.7    Analysis A.27.7.1        Fire Suppression The fire barriers enclosing this area will protect this area from a fire in the adjoining areas and will contain a fire within the area until extinguished.
The fire will be detected, alarmed, and suppressed by the automatic Halon system. The Halon system discharge or a malfunction will be identified by Control Room annunciation. In the event of a malfunction of the automatic system, the portable extinguishers and/or the hose stations can be used to extinguish the fire.
 
Wolf Creek Nuclear Operating Corporation                                              Page 105 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 76 of 250)
Adequate drainage is provided to drain the fire-fighting water. Should manual firefighting be required, water damage could result to the electrical equipment in this room (with or without fire damage); however, the water damage would not prevent safe shutdown. Since the floor in Room 1402 (corridor) slopes away from the doors in this room, water damage due to a sprinkler discharge in adjoining areas is not possible.
A.27.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-27 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-27 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-27.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 106 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 77 of 250)
Fire Area A-28 (Reference A-1803)
A.28.1    Fire Area Description Auxiliary Shutdown Panel Room 1413.
A.28.2    Major Equipment Auxiliary shutdown and control panels.
A.28.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature. In addition, within the room, the two auxiliary shutdown panels are separated by a fire barrier, which contains two normally closed fire rated doors. One door is located in front and one is located behind the panels.
Each auxiliary shutdown panel contains the controls and instrumentation for one safe shutdown train. Cable to the panels enter from the top for Separation Group 4 and from below for the redundant Separation Group 1. The Separation Group 1 circuits to the auxiliary shutdown panel enter the panel bottom directly through a penetration seal at the floor. Therefore, no exposed Separation Group 1 raceways appear in the room. The panels are provided with keylocks to control access to the panel interiors. Access to the Auxiliary Shutdown Panel Room is controlled and alarmed.
A.28.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-28 is Low. Due to the small floor area of the Auxiliary Shutdown Panel Room and the Security control of the room, combustibles are typically limited to those required for operation. Calculation XX-X-004 provides the bounding transient combustible package for this Fire Area.
(Reference 3.1, Section F.6)
Internal surfaces of the auxiliary shutdown panels are finished with paint of low flame spread. All cables in these panels meet the vertical flame spread requirements of IPCEA S-19-81 and/or IEEE 383-1974.
A.28.5    Fire Protection Smoke detectors are installed at the ceiling of this fire area. Manual-pull stations are installed adjacent to the exit doors of this floor. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.6)
 
Wolf Creek Nuclear Operating Corporation                                                    Page 107 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 78 of 250)
A hose station and one portable extinguisher are installed in Room 1408 (corridor) outside the area. (Reference 3.1, Section F.6)
Access for manual firefighting is from Room 1408 through an alarmed access door. For access to Room 1408, see Fire Area A-16.
No drains are provided for this Fire Area, as manual fire water suppression efforts will be minimal, considering the limited combustible loading and small footprint of the Fire Area.
Additionally, a floor drain is located in Fire Area A-16 just outside the access door to A-28.
A.28.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.28.7    Analysis A.28.7.1        Fire Suppression The fire barriers around the room will protect the panels from a fire in one of the adjoining areas. The fire separation between the panels will protect either auxiliary shutdown panel from a fire postulated in the other. The smoke detectors will provide an early warning of a fire either in a cabinet or in the room. The fire can be extinguished manually, using the portable extinguisher.
A.28.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-28 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area A-28 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in A-28.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 108 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 79 of 250)
Fire Area A-29 (Reference A-1802)
A.29.1    Fire Area Description Auxiliary Feedwater Pump Valve Compartment Rooms 1304, 1324, and 1327.
A.29.2    Major Equipment Auxiliary feedwater piping and valves, backup compressed gas accumulator tanks.
A.29.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.29.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.29.3-1 Fire Area A-29, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A.29.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-29 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 109 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 80 of 250)
A.29.5    Fire Protection Due to low combustible loading in this area, a detection system is not installed. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
Fire extinguishers are located in Rooms 1324 and 1329. A hose station is provided for this area in Room 1329. For specific locations, see A-1802.
Access to the area is via the Turbine Building.
One 4-inch drain is provided in each room. The drains are piped to a sump at El. 1974.
The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
A.29.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.29.7    Analysis A.29.7.1        Fire Suppression The fire barriers enclosing this area will protect this area from a fire in the adjoining areas and will contain a fire within the area until extinguished.
Adequate drainage is provided to drain any fire-fighting water.
A.29.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-29 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-29 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 110 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 81 of 250)
Fire Area A-30 (Reference A-1802)
A.30.1    Fire Area Description Auxiliary Feedwater Pump Valve Compartment Rooms 1305, 1328, and 1330.
A.30.2    Major Equipment Auxiliary feedwater piping and valves, backup compressed gas accumulator tanks.
A.30.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.30.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.30.3-1 Fire Area A-30, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts A.30.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-30 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 111 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 82 of 250)
A.30.5    Fire Protection Due to low combustible loading in this area, a detection system is not installed. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
Fire extinguishers are located in Rooms 1324 and 1329. A hose station is provided for this area in Room 1329. For specific locations, see drawing A-1802.
Access to the area is via the Turbine Building.
One 4-inch drain is provided in each room. The drains are piped to a sump at El. 1974.
The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
A.30.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.30.7    Analysis A.30.7.1        Fire Suppression The fire barriers enclosing this area will protect this area from a fire in the adjoining areas and will contain a fire within the area until extinguished.
Adequate drainage is provided to drain the fire-fighting water.
A.30.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-30 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-30 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 112 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 83 of 250)
Fire Area A-33 (Reference A-1801 and A-1802)
A.33.1    Fire Area Description Auxiliary Building - El. 1989 and El. 2000, Rooms 1206, 1207, and 1329.
A.33.2    Major Equipment Auxiliary feedwater piping, valves, and instrumentation.
A.33.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table A.33.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table A.33.3-1 Fire Area A-33, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Personnel hatch from Room 1129 to 1207                Hatch 1-hour rated fire wrap protection for redundant      Fire Wrap PFSSD circuits Penetration seals that exceed the bounding            Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected        Structural Steel Fireproofing thermal shorts A.33.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-33 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 113 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 84 of 250)
A portion of Room 1207 within this Fire Area is administratively maintained as a Combustible Control Zone to strictly control transient combustibles in the 20 ft. separation area between redundant PFSSD motor operated valves AL-HV-0032 and AL-HV-0033.
These valves provide a suction path for the turbine drive auxiliary feedwater pump. Insitu combustibles within the Combustible Control Zone do not pose a fire propagation path that would disable both trains of redundant PFSSD equipment.
A.33.5    Fire Protection An automatic smoke detection system is installed in this area, except for Corridor 1329.
No detection is provided in this area due to low combustible loading. An automatic wet pipe sprinkler system is provided for Rooms 1206 and 1207. Manual-pull fire alarm stations are located at normal exits from the Turbine Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. Sprinklers system actuation results in a local bell alarm and a point addressable Control Room alarm.
A hose station and portable extinguishers are located in the area, as delineated on drawings A-1801 and A-1802.
Access to this area for manual fire fighting is available as follows:
: a. Door 13291 from the Turbine Building
: b. Door 11281 from the Auxiliary Building through the personnel hatch between Rooms 1129 and 1207 One 4-inch drain per 1,000 square feet of floor area is provided throughout this fire area.
The floor drains are piped to the auxiliary feedwater pump rooms sump. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
A.33.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.33.7    Analysis A.33.7.1        Fire Suppression The automatic detection system will provide an early warning of fire in this area. The detection, automatic suppression, fire wrap, and combustible control within Rooms 1206 and 1207 ensure that a fire in this area will not involve redundant PFSSD components. The hose station in 1329 or portable extinguishers can also be used to suppress fire within this Fire Area.
 
Wolf Creek Nuclear Operating Corporation                                              Page 114 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 85 of 250)
A.33.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-33 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-33 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 115 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 86 of 250)
Fire Area A-34 (Reference A-1802)
A.34.1    Fire Area Description Auxiliary Building - El. 2000, Rooms 1316 and 1317.
A.34.2    Major Equipment Seal water heat exchanger and associated piping and valves.
A.34.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
A.34.4    Combustible Loading The cumulative combustible loading classification for Fire Area A-34 is Low.
A.34.5    Fire Protection No detection or automatic suppression is provided in this fire area due to low combustible loading. Manual-pull fire alarm stations are located at normal exits from the Auxiliary Building. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are located in an adjacent fire area, as delineated on drawing A-1802.
Access to this area for manual firefighting is available through door 13161 from room 1315.
One 4-inch floor drain is provided in rooms 1316 and 1317. The floor drains are piped to a sump located at El. 1967 accessed from Auxiliary Building floor El. 1974. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 116 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 87 of 250)
A.34.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
A.34.7    Analysis A.34.7.1        Fire Suppression The fire barriers enclosing this area will protect against a fire in the adjoining areas and will contain a fire within the area until extinguished.
Adequate drainage is provided to drain any firefighting water.
A.34.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an A-34 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area A-34 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 117 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 88 of 250)
Fire Area AB-1 (Reference A-1802)
AB.1.1    Fire Area Description Auxiliary Boiler Room 4315.
AB.1.2    Major Equipment Auxiliary boiler.
AB.1.3    Design Features The portions of this Fire Area that directly communicate with other Fire Areas are separated by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature. Stairwell T-6 enclosure is 2-hour fire rated. The roof, grade floor, and walls of the Auxiliary Boiler Room that communicate to the exterior are not credited fire boundaries.
AB.1.4    Combustible Loading The cumulative combustible loading classification for Fire Area AB-1 is Low.
AB.1.5    Fire Protection Infrared flame detectors are provided in this area. A manual-pull fire alarm station is located near the exit doorways from this area. An automatic wet-pipe sprinkler system is provided to protect the entire area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is zoned for a quick and easy means to identify the location associated with the device in alarm. Sprinklers system actuation results in a local bell alarm and a point addressable Control Room alarm.
Hose stations and portable extinguishers are provided just outside this area in the Turbine Building. In addition, a portable extinguisher is provided inside the area, near the exterior door.
The auxiliary boiler is provided with an emergency stop switch located in the Turbine Building just outside the Auxiliary Boiler Room.
Auxiliary boiler fuel oil tank 1FO01T has a capacity of 469,980 gallons and is located outside of the protected area in the southwest portion of the owner controlled area. A manual foam extinguishing system is provided with internal injection into the tank. It also supplies a hose station for external use. The tank is provided with a dike to contain fuel oil tank contents and fire suppression water.
Access to the Auxiliary Boiler Room is via the Turbine Building or the exterior or the room on the southeast side.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 118 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 89 of 250)
Floor drains in the area are piped to the Auxiliary Boiler Room sump. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
AB.1.6    Isolation and Smoke Removal A fire in the area will be contained by the fire barriers until extinguished. No ventilation ductwork penetrates the fire barriers of this Fire Area. Fusible link operated smoke and heat venting is also provided in the roof of AB-1. Refer to Section 4.3.7.2 for smoke removal discussion.
AB.1.7    Analysis AB.1.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event of the failure of the automatic sprinkler system, fire barriers will prevent fire spread to communicating Fire Areas. Fire may be extinguished manually, using a fire extinguisher and/or hose station.
AB.1.7.2        Safe Shutdown Capability This area contains no PFSSD equipment or circuits and is separated from adjoining safe shutdown areas by a fire barrier construction. Therefore, a fire within Fire Area AB-1 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 119 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 90 of 250)
Fire Area C-1 (Reference A-1801)
C.1.1      Fire Area Description Pipe Space and Tank Area Control Building, El. 1974 Room 3101 and 3104.
C.1.2      Major Equipment ESW piping and motor-operated isolation valves, detergent drain tank and pumps, control building floor and equipment drain sump pumps, chemical equipment drain sump pumps.
C.1.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.1.3-1 Fire Area C-1, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts Stairwell 3104 is separated by 3101 by a 2-hour rated fire barrier and where room 3104 interfaces with other fire areas the barrier is rated for 3-hours.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 120 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 91 of 250)
C.1.4      Combustible Loading The cumulative combustible loading classification for Fire Area C-1 is Low.
A portion of Room 3101 within this Fire Area is administratively maintained as a Combustible Control Zone to strictly control transient combustibles in the 20 ft. separation area between redundant PFSSD motor operated valves for the essential service water (ESW) system. Insitu combustibles within the Combustible Control Zone do not pose a fire propagation path that would disable both trains of redundant PFSSD equipment.
C.1.5      Fire Protection Room 3101 is provided with smoke detectors in the area of the ESW motor-operated isolation valves to provide early warning of a fire in this area. A manual-pull station is located at the north exit into Room 3102. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system is provided for Room 3101.
Two manual hose stations are located within the area as delineated on drawing A-1801.
Portable extinguishers are located within the area and in the corridor outside access doors between the Control Building and the Auxiliary Building (Room 1101).
Access to this area for manual fire fighting is available via Auxiliary Building Corridor 1101 and Communications Corridor 3102.
Drainage in this area is by nine 4-inch floor drains. This is adequate to handle maximum sprinkler and hose station discharge. The drains discharge to the Control Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.1.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
C.1.7      Analysis C.1.7.1          Fire Suppression A fire in this area will be detected and alarmed by the smoke detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the wet pipe system. The Combustible Control Zone ensures that fire will not involve redundant PFSSD components within the Fire Area. Should the automatic suppression system fail, manual hose streams and extinguishers can be used to extinguish the fire.
 
Wolf Creek Nuclear Operating Corporation                                              Page 121 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 92 of 250)
C.1.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-1 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in C-1.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 122 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 93 of 250)
Fire Area C-2 (Reference A-1801)
C.2.1      Fire Area Description North vertical cable chase Room 3106, Control Building. El. 1974 to 1984.
C.2.2      Major Equipment Electric cable only.
C.2.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.2.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.2.3-1 Fire Area C-2, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts C.2.4      Combustible Loading The cumulative combustible loading classification for Fire Area C-2 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 123 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 94 of 250)
C.2.5      Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent Room 3101. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler systems is by portable extinguishers and manual hose stations located in Fire Area C-1.
Access to the chase is through a 2 foot 8 inch by 4 foot 6 inch, 3-hour-rated fire door.
No drains are provided for this Fire Area. Fire suppression water will escape under the rollup access fire door and into floor drains within Fire Area C-1. There are no PFSSD equipment or circuits in this area. Therefore, water accumulation in the area would not affect safe shutdown capability.
C.2.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.2.7      Analysis C.2.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barrier and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.2.7.2          Safe Shutdown Capability There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in C-2.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 124 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 95 of 250)
Fire Area C-3 (Reference A-1801)
C.3.1      Fire Area Description South vertical cable chase Room 3105, Control Building. El. 1974 to 1984.
C.3.2      Major Equipment Electric cable only.
C.3.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.3.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area. .
Table C.3.3-1 Fire Area C-3, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts C.3.4      Combustible Loading The cumulative combustible loading classification for Fire Area C-3 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 125 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 96 of 250)
C.3.5      Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent Room 3101. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler systems is by portable extinguishers and manual hose stations located in Fire Area C-1.
Access to the chase is through a 2 foot 8 inch by 4 foot 6 inch, 3-hour-rated fire door.
No drains are provided for this Fire Area. Fire suppression water will escape under the rollup access fire door and into floor drains within Fire Area C-1. There are no PFSSD equipment or circuits in this area. Therefore, water accumulation in the area would not affect safe shutdown capability.
C.3.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.3.7      Analysis C.3.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.3.7.2          Safe Shutdown Capability There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in C-3.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 126 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 97 of 250)
Fire Area C-5 (Reference A-1801)
C.5.1      Fire Area Description Access Control area above and below suspended ceiling Rooms 3206, 3212 through 3224, Pipe Chases, and Electrical Chase accessible from 3212.
C.5.2      Major Equipment Electric cable, laundry machinery, medical supplies, and office equipment C.5.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.5.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.5.3-1 Fire Area C-5, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Fire door 32092                                      Fire Door Penetration seals that exceed the bounding            Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected        Structural Steel Fireproofing thermal shorts C.5.4      Combustible Loading The cumulative combustible loading classification for Fire Area C-5 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 127 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 98 of 250)
C.5.5      Fire Protection Smoke detectors are installed above and below the suspended ceiling except as noted in Attachment A. Manual-pull fire alarm stations are located near the exit doorways from the Access Control area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system is provided in this area above and below the suspended ceiling as detailed in Attachment A. Water flow in the system is alarmed in the Control Room.
Hose stations and portable extinguishers are provided in the corridors within the Access Control area, as indicated on drawing A-1801.
Access to this area for manual firefighting is available via Communications Corridor 3225 and Auxiliary Building Corridor 1101 through Fire Area C-6.
Adequate floor drains are provided to remove sprinkler and hose station discharge without appreciable accumulation. Any sprinkler discharge in the area above the suspended ceiling will drain through the suspended ceiling to the Access Control area below. Drainage is discharged to the Control Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.5.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
C.5.7      Analysis C.5.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire occurs, the automatic suppression system will actuate and extinguish the fire. In the event of failure of the automatic system, the manual hose stations provide the capability of extinguishing the fire.
The suspended ceiling panels may be removed as necessary during firefighting efforts involving the normally concealed space above the panels. The majority of the cable trays in this area are no more than 12 feet above the floor elevation, and no trays are more than 14 feet above the floor. Consequently, a fire in these cable trays can be extinguished by manual hose stations from the floor (assuming failure of the automatic wet pipe sprinkler system above the trays).
 
Wolf Creek Nuclear Operating Corporation                                              Page 128 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 99 of 250)
C.5.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-5 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-5 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 129 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 100 of 250)
Fire Area C-6 (Reference A-1801)
C.6.1      Fire Area Description Access Control area above and below suspended ceiling Rooms 3201 through 3205 and 3207 through 3211, Pipe Chases, and Electrical Chase accessible from 3205.
C.6.2      Major Equipment Electric cable, laundry machinery, medical supplies, and office equipment.
C.6.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.6.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.6.3-1 Fire Area C-6, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Fire door 32015                                  Fire Door Fire door 32092                                  Fire Door Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts The stairway enclosure at the 1984 elevation is 2-hour rated, The remaining elevations are 3-hour rated with the exception of the ceiling. The ceiling of the stairway in this area forms part of the roof. Since no Fire Areas are above the ceiling, it is not rated. The roof is non-combustible concrete with built up Class A roofing. Therefore, structural integrity will be maintained in the event of a fire. Safe shutdown cable is separated from the Access Control area below by a noncombustible suspended ceiling.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 130 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 101 of 250)
C.6.4      Combustible Loading The cumulative combustible loading classification for Fire Area C-6 is Low.
C.6.5      Fire Protection Smoke detectors are installed above and below the suspended ceiling except as noted in Attachment A. Manual-pull fire alarm stations are located near the exit doorways from the Access Control area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system is provided in this area above and below the suspended ceiling as detailed in Attachment A. Water flow in the system is alarmed in the Control Room.
Hose stations and portable extinguishers are provided in the corridors within the Access Control area, as indicated on drawing A-1801.
Access to this area for manual firefighting is available via Communications Corridor 3225 through Fire Area C-5 and Auxiliary Building Corridor 1101.
Adequate floor drains are provided to remove sprinkler discharge without appreciable accumulation. Any sprinkler discharge in the area above the suspended ceiling will drain through the suspended ceiling to the Access Control area below. Drainage is discharged to the Control Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.6.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
C.6.7      Analysis C.6.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire occurs, the automatic suppression system will actuate and extinguish the fire. In the event of failure of the automatic system, the manual hose stations provide the capability of extinguishing the fire.
The suspended ceiling panels may be removed as necessary during firefighting efforts involving the normally concealed space above the panels. The majority of the cable trays in this area are no more than 12 feet above the floor elevation, and no trays are more than 14 feet above the floor. Consequently, a fire in these cable trays can be extinguished by
 
Wolf Creek Nuclear Operating Corporation                                              Page 131 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 102 of 250) manual hose stations from the floor (assuming failure of the automatic wet pipe sprinkler system above the trays).
C.6.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-6 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-6 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in C-6.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 132 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 103 of 250)
Fire Area C-7 (Reference A-1801)
C.7.1      Fire Area Description North vertical cable chase Room 3230, Control Building. El. 1984 to 2000.
C.7.2      Major Equipment Electric cable only C.7.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.7.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.7.3-1 Fire Area C-7, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.7.4      Combustible Loading The cumulative combustible loading classification for Fire Area C-7 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 133 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 104 of 250)
C.7.5      Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler systems is by portable extinguishers and manual hose stations located in the Access Control area.
Access to the chase is through a 3-hour-rated fire door.
Drainage in this area is by one 4-inch floor drain. This is more than adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.7.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.7.7      Analysis C.7.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers until extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.7.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-7 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-7 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 134 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 105 of 250)
Fire Area C-8 (Reference A-1801)
C.8.1      Fire Area Description South vertical cable chase Room 3229, Control Building. El. 1984 to 2000.
C.8.2      Major Equipment Electric cable only.
C.8.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.8.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.8.3-1 Fire Area C-8, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.8.4      Combustible Loading The cumulative combustible loading classification for Fire Area C-8 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 135 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 106 of 250)
C.8.5      Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in the Access Control area.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is more than adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.8.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.8.7      Analysis C.8.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barrier and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.8.7.2          Safe Shutdown Capability There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in C-8.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 136 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 107 of 250)
Fire Area C-9 (Reference A-1802)
C.9.1      Fire Area Description North ESF Switchgear Room 3301.
C.9.2      Major Equipment Electric cable, ESF switchgear, load center unit substations.
C.9.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.9.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area. (Reference 3.1, Section F.5)
Table C.9.3-1 Fire Area C-9, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Missile door 33012                                  Fire Door Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts Cables which enter the Switchgear Room without terminating there are minimized.
(Reference 3.1, Section F.5)
C.9.4      Combustible Loading The cumulative combustible loading classification for Fire Area C-9 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 137 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 108 of 250)
C.9.5      Fire Protection This area is provided with a cross-zoned smoke detection system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
The Halon 1301 system installed is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An activation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation. (Reference 3.1, Section F.5)
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
Manual-pull fire alarm stations are located near the exit doorway from this area. The pull stations alarm locally and in the Control Room.
Hose stations and portable extinguishers are provided in this Fire Area, as delineated on drawing A-1802. (Reference 3.1, Section F.5)
The area is accessible through two double doorways in the south wall and one double doorway in the north wall.
Three 4-inch floor drains are provided in this area. The drains discharge to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
C.9.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
C.9.7      Analysis C.9.7.1          Fire Suppression A fire in this area will be detected and alarmed by the detection system.
Normally, since this is an unoccupied area, both zones of smoke detection would trip during a fire and the Halon system would discharge.
In the event of the failure of the Halon system (identified by Control Room annunciation) the fire can be extinguished manually with the portable extinguishers and/or hose stations.
 
Wolf Creek Nuclear Operating Corporation                                              Page 138 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 109 of 250)
C.9.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-9 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-9 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 139 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 110 of 250)
Fire Area C-10 (Reference A-1802)
C.10.1    Fire Area Description South ESF Switchgear Room 3302.
C.10.2    Major Equipment Electric cable, ESF switchgear, load center unit substations.
C.10.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.10.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area. (Reference 3.1, Section F.5)
Table C.10.3-1 Fire Area C-10, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts Cables which enter the Switchgear Room without terminating there are minimized.
(Reference 3.1, Section F.5)
C.10.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-10 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 140 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 111 of 250)
C.10.5    Fire Protection This area is provided with a cross-zoned smoke detection system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
The Halon 1301 system installed is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An activation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation. (Reference 3.1, Section F.5)
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
A manual-pull fire alarm station is located near the south stairwell exit and the north exit from Room 3301. The pull stations alarm locally and in the Control Room.
Hose stations and portable extinguishers are provided in this Fire Area, as delineated on drawing A-1802. (Reference 3.1, Section F.5)
The area is accessible through the southwest stairwell and the two double doorways in the north wall.
Three 4-inch floor drains are provided in this area. The drains discharge to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
C.10.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
C.10.7    Analysis C.10.7.1        Fire Suppression A fire in this area will be detected and alarmed by either zone of detection.
Normally, since this is an unoccupied area, both smoke detection zones would trip during the fire and the Halon system would discharge.
In the event of a failure of the Halon system (identified by Control Room annunciation) the fire can be extinguished manually with the portable extinguishers and/or hose stations.
 
Wolf Creek Nuclear Operating Corporation                                              Page 141 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 112 of 250)
C.10.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-10 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-10 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 142 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 113 of 250)
Fire Area C-11 (Reference A-1802)
C.11.1    Fire Area Description South vertical cable chase Room 3305, Control Building. El. 2000 to 2016.
C.11.2    Major Equipment Electric cable only.
C.11.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.11.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.11.3-1 Fire Area C-11, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.11.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-11 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 143 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 114 of 250)
C.11.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent area (C-10). Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and the manual hose stations located in Fire Area C-10.
Access to the chase is through a 3-hour-rated fire door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.11.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.11.7    Analysis C.11.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barrier and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.11.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-11 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-11 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 144 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 115 of 250)
Fire Area C-12 (Reference A-1802)
C.12.1    Fire Area Description North vertical cable chase Room 3306, Control Building. El. 2000 to 2016.
C.12.2    Major Equipment Electric cable only.
C.12.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.12.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.12.3-1 Fire Area C-12, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.12.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-12 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 145 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 116 of 250)
C.12.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent area (C-9). Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-9.
Access to the chase is through a 3-hour-rated fire door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.12.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.12.7    Analysis C.12.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.12.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-12 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-12 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 146 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 117 of 250)
Fire Area C-13 (Reference A-1802)
C.13.1    Fire Area Description Class IE Air Conditioning Equipment Room No. 1 (Room 3415).
C.13.2    Major Equipment Class IE electrical AC unit, control room pressurization fan, and control room pressurization system filter adsorber unit C.13.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.13.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.13.3-1 Fire Area C-13, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts C.13.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-13 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 147 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 118 of 250)
C.13.5    Fire Protection Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located near the exit doorways from this elevation of the Control Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are provided in the corridors just outside this Fire Area, as indicated on drawing A-1802.
The charcoal adsorber unit is provided with thermistor-type temperature detectors downstream of the charcoal bed, which alarm in the Control Room at high airstream temperature. The charcoal bed is equipped with a hose connection to provide manual water spray protection.
The area is accessible through the door from the adjacent corridor.
Drainage in this area is by two 4-inch floor drains. These drains are adequate to handle hose station discharge. The drains discharges to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
C.13.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
C.13.7    Analysis C.13.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers. Water or fire damage to the safe shutdown equipment will not prevent the safe shutdown of the plant.
A filter fire in the charcoal adsorber unit will be extinguished utilizing the manual spray system.
C.13.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-13 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
 
Wolf Creek Nuclear Operating Corporation                                              Page 148 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 119 of 250)
Therefore, a fire within Fire Area C-13 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 149 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 120 of 250)
Fire Area C-14 (Reference A-1802)
C.14.1    Fire Area Description Class IE Air Conditioning Equipment Room No. 2 (Room 3416).
C.14.2    Major Equipment Class IE electrical equipment AC unit, control room pressurization fan, and control room pressurization system filter adsorber unit.
C.14.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.14.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.14.3-1 Fire Area C-14, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Ceramic fiber and sheet metal fire barrier            Fire Barrier segment Penetration seals that exceed the bounding            Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected        Structural Steel Fireproofing thermal shorts C.14.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-14 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 150 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 121 of 250)
C.14.5    Fire Protection Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located near the exit doorways from this elevation of the Control Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are provided in the corridors just outside this Fire Area, as indicated on drawing A-1802.
The charcoal adsorber unit is provided with thermistor-type temperature detectors downstream of the charcoal bed, which alarm in the control room at high airstream temperature. The charcoal bed is equipped with a hose connection to provide manual water spray protection.
The area is accessible through the door from the adjacent corridor.
Drainage in this area is by one 4-inch floor drain. This drain is adequate to handle hose station discharge. The drain discharges to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
C.14.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
C.14.7    Analysis C.14.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers. Water or fire damage to the safe shutdown equipment will not prevent the safe shutdown of the plant.
A filter fire in the charcoal adsorber unit will be extinguished utilizing the manual spray system.
C.14.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-14 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
 
Wolf Creek Nuclear Operating Corporation                                              Page 151 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 122 of 250)
Therefore, a fire within Fire Area C-14 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 152 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 123 of 250)
Fire Area C-15 (Reference A-1802)
C.15.1    Fire Area Description Battery and Switchboard Rooms (south), Control Building. El. 2016. Rooms 3403, 3404, 3405, 3410, and 3411.
C.15.2    Major Equipment Switchgear, batteries, battery chargers, panels, inverters, transformers, and electric cable C.15.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.15.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area. (Reference 3.1, Section F.7)
Table C.15.3-1 Fire Area C-15, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts The area contains five rooms (including two battery rooms) that are separated by 3-hour fire barrier construction. (Reference 3.1, Section F.7)
C.15.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-15 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                      Page 153 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 124 of 250)
C.15.5    Fire Protection Except for the Battery Rooms (Rooms 3405 and 3411), a cross-zoned smoke detection system is installed in this area. The Battery Rooms are provided with one smoke detection zone. Manual-pull fire alarm stations are located near the exit doorways from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are provided in the corridors just outside this Fire Area, as indicated on drawing A-1802. The hose stations can reach all rooms in this area. (Reference 3.1, Section F.7)
Those areas provided with a cross-zoned detection system are also protected with an automatic Halon 1301 extinguishing system. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
The Halon 1301 system installed is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An actuation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation.
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
This area is accessible through any of the four doors opening into the access corridor.
Each room within the Fire Area is provided with one 4-inch drain. These drains are adequate to handle hose station discharge. The drains discharge to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
C.15.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 154 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 125 of 250)
The Battery Rooms in this Fire Area serving each of the safeguards equipment trains in the safe shutdown areas are served by two systems--the Control Building supply air system and the Class IE AC unit. Loss of either or both of these systems will be alarmed in the Control Room via the plant computer. These ventilation systems are capable of maintaining the hydrogen concentration well below two-volume percent. Additionally, each Battery Room is also provided with a hydrogen detector which will alarm in the Control Room whenever the hydrogen concentration exceeds 1 volume percent in any one of the Battery Rooms. (Reference 3.1, Section F.7)
The Control Building supply air system supplies outside air to each of the four DC Switchgear Rooms. This air is exhausted from the Switchgear Rooms through the Battery Rooms by the Control Building exhaust system. The supply air system and the exhaust system provide approximately one air change per hour in each Battery Room.
(Reference 3.1, Section F.7)
Battery Rooms 1, 3 and 2, 4 are each served by the Class IE ac system. Each Battery Room is supplied and exhausted separately. The Class IE AC systems each operate in a completely recirculating mode at all times. These systems also serve their respective ESF Switchgear and DC Switchgear Rooms. It has been conservatively calculated that with no fresh air the system can operate for approximately 3 days before the hydrogen concentration reaches 3 volume percent. (Reference 3.1, Section F.7)
C.15.7    Analysis C.15.7.1        Fire Suppression A fire in any of the rooms in this area will be detected and alarmed by the smoke detection system. In those areas protected with a Halon 1301 extinguishing system, the system will provide fire suppression of the fire.
In the event of a failure of the halon system or in areas not provided with an extinguishing system, the fire can be extinguished manually with the portable extinguishers and/or hose streams.
C.15.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-15 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-15 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 155 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 126 of 250)
Fire Area C-16 (Reference A-1802)
C.16.1    Fire Area Description Battery and Switchboard Rooms (north), Control Building. El. 2016 Rooms 3407, 3408, 3409, 3413, and 3414.
C.16.2    Major Equipment Switchgear, batteries, battery chargers, panels, inverters, transformers, and electric cable.
C.16.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.16.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area. (Reference 3.1, Section F.7)
Table C.16.3-1 Fire Area C-16, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Door 34071                                          Fire Door Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected      Structural Steel Fireproofing thermal shorts The area contains five rooms (including two battery rooms) that are separated by 3-hour fire barrier construction. (Reference 3.1, Section F.7)
C.16.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-16 is Low.
 
Wolf Creek Nuclear Operating Corporation                  Page 156 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 127 of 250)
 
Wolf Creek Nuclear Operating Corporation                                                    Page 157 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 128 of 250)
C.16.5    Fire Protection Except for the Battery Rooms (Rooms 3407 and 3413), a cross-zoned smoke detection system is installed in the area. One zone of smoke detectors is installed in the Battery Rooms. Manual-pull fire alarm stations are located near the exit doorways from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are provided in the corridors just outside this fire area, as indicated on drawing A-1802. The hose stations can reach all the various rooms in this area. (Reference 3.1, Section F.7)
Those areas provided with a cross-zoned smoke detection system are also protected with an automatic Halon 1301 extinguishing system. Detection by either zone will alarm locally and in the Control Room. Activation by both zones will initiate the discharge of the Halon 1301 suppression system installed in this area. If one detection zone is not available, detection by the remaining zone alone will activate the Halon system.
The Halon 1301 system installed is capable of attaining a minimum 5-percent concentration. The system is designed to maintain at least a 5-percent concentration at the level of the highest combustible for a soak time of 10 minutes. An actuation station is provided to discharge the system manually. An automatic activation will sound a local alarm, close required ventilation dampers, shut off associated ventilation and/or air-conditioning fan motors, and discharge the system after an adequate time delay for evacuation.
The Halon cylinders and the control panel are located outside the Fire Area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A 100-percent reserve cylinder bank is provided for this system.
This area is accessible through any of the four doors opening into the access corridor.
Each room within the Fire Area is provided with one 4-inch drain. These drains are adequate to handle hose station discharge. The drains discharge to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
C.16.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
The Battery Rooms in this Fire Area serving each of the safeguards equipment trains in the safe shutdown areas are served by two systems--the Control Building supply air system and the Class IE AC unit. Loss of either or both of these systems will be alarmed in the Control Room via the plant computer. These ventilation systems are capable of maintaining the hydrogen concentration well below two-volume percent. Additionally,
 
Wolf Creek Nuclear Operating Corporation                                                  Page 158 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 129 of 250) each Battery Room is also provided with a hydrogen detector which will alarm in the Control Room whenever the hydrogen concentration exceeds 1 volume percent in any one of the Battery Rooms. (Reference 3.1, Section F.7)
The Control Building supply air system supplies outside air to each of the four DC Switchgear Rooms. This air is exhausted from the Switchgear Rooms through the Battery Rooms by the control Building exhaust system. The supply air system and the exhaust system provide approximately 1 air change per hour in each Battery Room.
(Reference 3.1, Section F.7)
Battery Rooms 1, 3 and 2, 4 are each served by the Class IE AC system. Each Battery Room is supplied and exhausted separately. The Class IE ac systems each operate in a completely recirculating mode at all times. These systems also serve their respective ESF Switchgear and DC Switchgear Rooms. It has been conservatively calculated that with no fresh air the system can operate for approximately 3 days before the hydrogen concentration reaches 3 volume percent. (Reference 3.1, Section F.7)
C.16.7    Analysis C.16.7.1        Fire Suppression A fire in any of the rooms in this area will be detected and alarmed by the smoke detection system. In those areas protected with a Halon 1301 extinguishing system, the system will provide fire suppression of the fire.
In the event of a failure of the Halon system or in areas not provided with an extinguishing system, the fire can be extinguished manually with the portable extinguishers and/or hose streams.
C.16.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-16 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-16 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 159 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 130 of 250)
Fire Area C-17 (Reference A-1802)
C.17.1    Fire Area Description South Vertical Cable Chase (Room 3418), Control Building El. 2016 to 2032.
C.17.2    Major Equipment Electric cable only C.17.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.17.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.17.3-1 Fire Area C-17, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.17.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-17 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 160 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 131 of 250)
C.17.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in the access corridor (3401) at this elevation.
Access to the chase is through a 3-hour-rated fire door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.17.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.17.7    Analysis C.17.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.17.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-17 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-17 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 161 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 132 of 250)
Fire Area C-18 (Reference A-1802)
C.18.1    Fire Area Description North Vertical Cable Chase (Room 3419), Control Building El. 2016 to 2032.
C.18.2    Major Equipment Electric cable only C.18.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.18.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.18.3-1 Fire Area C-18, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.18.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-18 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 162 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 133 of 250)
C.18.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in the access corridor (3401) at this elevation.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.18.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.18.7    Analysis C.18.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.18.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-18 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-18 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 163 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 134 of 250)
Fire Area C-19 (Reference A-1802)
C.19.1    Fire Area Description Cable Chase at column line CA-C3, Control Building El. 2016 to 2032.
C.19.2    Major Equipment Electric cable only.
C.19.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
C.19.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-19 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
C.19.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in the access corridor (3401) at this elevation.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.19.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                Page 164 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 135 of 250)
C.19.7    Analysis C.19.7.1      Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.19.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-19 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-19 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 165 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 136 of 250)
Fire Area C-20 (Reference A-1802)
C.20.1    Fire Area Description Cable Chase at column line C-6, Control Building El. 2016 to 2032.
C.20.2    Major Equipment Electric cable only.
C.20.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.20.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.20.3-1 Fire Area C-20, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.20.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-20 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 166 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 137 of 250)
C.20.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from this floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in the access corridor (3401) at this elevation.
Access to the chase is through a 3-hour-rated fire door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.20.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.20.7    Analysis C.20.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.20.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-20 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-20 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 167 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 138 of 250)
Fire Area C-21 (Reference A-1803)
C.21.1    Fire Area Description Lower Cable Spreading Room 3501.
C.21.2    Major Equipment Electric cable.
C.21.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.21.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area. (Reference 3.1, Section F.3.a)(3))
Table C.21.3-1 Fire Area C-21, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Cable trenches                                      Fire Barrier Door 32015                                          Fire Door Missile door 35021                                  Fire Door Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts Stairwell C-1 is separated from this area by fire rated barriers.
C.21.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-21 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 168 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 139 of 250)
C.21.5    Fire Protection Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located near the exit doorways from this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
This area is provided with partial coverage automatic preaction sprinkler system installed at the ceiling. Location of the closed sprinkler heads considers cable tray sizing and arrangement. Cables are designed to allow wetting down with suppression water without electrical faulting. (Reference 3.1, Section F.3.a)(1))
Hose stations and portable extinguishers are provided in this fire area for backup protection, as indicated on drawing A-1803. (Reference 3.1, Section F.3.a)(2))
This area is accessible from the stairway at the south end and the Communications Corridor at the north end of the area. These entrances to the area are remote and separate. Generally, aisle separation between tray stacks is 3 feet wide by 7 feet high.
(Reference 3.1, Section F.3.a)(4) and F.3.a)(5))
Adequate floor drainage capacity is provided in this area to remove sprinkler system and hose station discharge without appreciable accumulation. Specifically, four 6-inch drains are provided throughout this Fire Area. The floor drains are piped to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
C.21.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
C.21.7    Analysis C.21.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. Detector actuation will also open the sprinkler system deluge valve, thus charging the system piping. In the event that a fire occurs, the automatic sprinkler system will discharge and suppress the fire. Should the automatic system fail to operate (identified by Control Room annunciation), or fail to completely extinguish the fire, it would be extinguished by utilizing the manual hose stations.
 
Wolf Creek Nuclear Operating Corporation                                              Page 169 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 140 of 250)
C.21.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-21 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-21 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 170 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 141 of 250)
Fire Area C-22 (Reference A-1804)
C.22.1    Fire Area Description Upper Cable Spreading Room 3801.
C.22.2    Major Equipment Electric cable.
C.22.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.22.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area. (Reference 3.1, Section F.3.a)(3))
Table C.22.3-1 Fire Area C-22, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Missile door 38011                                Fire door Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts The ceiling is the roof of the control building and is not rated. It is however constructed of concrete with built up Class A roofing. In addition, the structural steel supporting the roof is protected with 3-hour fire proofing material. Therefore, building structural integrity is maintained. (Reference 3.1, Section F.3.a)(3))
Stairwell C-1 is separated from this area by fire rated barriers.
Floor penetrations in this area are provided with raised sleeves or curbs, and all penetrations have watertight seals to prevent water damage in the Control Room below during fire-fighting operations in this area.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 171 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 142 of 250)
C.22.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-22 is Low.
C.22.5    Fire Protection Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located near the exit doorways from this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room.
The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
This area is provided with partial coverage automatic preaction sprinkler system installed at the ceiling. Location of the closed sprinkler heads considers cable tray sizing and arrangement. Cables are designed to allow wetting down with suppression water without electrical faulting. (Reference 3.1, Section F.3.a)(1))
Hose stations and portable extinguishers are provided in this fire area for backup protection, as indicated on drawing A-1804. (Reference 3.1, Section F.3.a)(2))
This area is accessible from the stairway at the south end and the Communications Corridor at the north end of the area. These entrances to the area are remote and separate. Generally, aisle separation between tray stacks is 3 feet wide by 7 feet high.
(Reference 3.1, Section F.3.a)(4) and F.3.a)(5))
Adequate floor drainage capacity is provided in this area to remove sprinkler system and hose station discharge without appreciable accumulation. Specifically, four 6-inch drains are provided throughout this Fire Area. The floor drains are piped to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
C.22.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
C.22.7    Analysis C.22.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. Detector actuation will also open the sprinkler system deluge valve, thus charging the system piping. In the event that a fire occurs, the automatic sprinkler system will discharge and suppress the fire. Should the automatic system fail to operate (identified by Control Room annunciation), or fail to completely extinguish the fire, it would be extinguished by utilizing the manual hose stations.
 
Wolf Creek Nuclear Operating Corporation                                              Page 172 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 143 of 250)
C.22.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-22 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-22 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 173 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 144 of 250)
Fire Area C-23 (Reference A-1803)
C.23.1    Fire Area Description South Vertical Cable Chase (Room 3505), Control Building. El. 2032 to 2047-6.
C.23.2    Major Equipment Electric cable only.
C.23.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.23.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.23.3-1 Fire Area C-23, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts C.23.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-23 is Moderate. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 174 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 145 of 250)
C.23.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the exits from the adjacent Room 3501. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-21.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.23.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.23.7    Analysis C.23.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.23.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-23 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-23 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 175 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 146 of 250)
Fire Area C-24 (Reference A-1803)
C.24.1    Fire Area Description North Vertical Cable Chase (Room 3504), Control Building. El. 2032 to 2047-6.
C.24.2    Major Equipment Electric cable only.
C.24.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.24.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.24.3-1 Fire Area C-24, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.24.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-24 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 176 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 147 of 250)
C.24.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the exits from the adjacent Room 3501. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-21.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.24.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.24.7    Analysis C.24.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.24.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-24 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-24 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 177 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 148 of 250)
Fire Area C-25 (Reference A-1803)
C.25.1    Fire Area Description Cable Chase at column line CA-C6, Control Building. El. 2032 to 2047-6.
C.25.2    Major Equipment Electric cable only.
C.25.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.25.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.24.3-1 Fire Area C-25, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 C.25.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-25 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 178 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 149 of 250)
C.25.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the exits from the adjacent Room 3501. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-21.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.25.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.25.7    Analysis C.25.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.25.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-25 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-25 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 179 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 150 of 250)
Fire Area C-26 (Reference A-1803)
C.26.1    Fire Area Description Vertical Cable Chase at column line CA-C3, Control Building El. 2032 to 2047-6.
C.26.2    Major Equipment Electric cable only.
C.26.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
C.26.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-26 is High.
C.26.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the exits from the adjacent Room 3501. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-21.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.26.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                Page 180 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 151 of 250)
C.26.7    Analysis C.26.7.1      Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.26.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-26 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-25 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 181 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 152 of 250)
Fire Area C-27 (Reference A-1804)
C.27.1    Fire Area Description Control Room area, Rooms 3601, 3603-3606, and 3616.
C.27.2    Major Equipment Main control board equipment cabinets, electric cable.
C.27.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.27.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area. (Reference 3.1, Section F.2)
All penetration seals are relatively airtight, as demonstrated by periodic Control Room pressurization testing. (Reference 3.1, Section F.2)
Table C.27.3-1 Fire Area C-27, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Cable trenches                                      Fire Barrier Missile door 36042                                  Fire Door Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts The following rooms at this elevation of the Control Building are considered peripheral rooms and are not part of the Control Room. These rooms are separated from this Fire Area by fire rated barriers.
 
Wolf Creek Nuclear Operating Corporation                                                Page 182 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 153 of 250)
: a. 3609, SAS room (See Fire Area C-29)
: b. 3602, Pantry (See Fire Area C-28)
: c. 3607, Toilet (See Fire Area C-28)
: d. 3608, Janitor's closet (See Fire Area C-28)
Some electric cable is routed above the suspended ceiling over Room 3601. However, none of these circuits are required for a safe shutdown. The floor of Room 3601 contains nine cable trenches (approximately 3-1/4 inches deep), which continue up the height of the west wall in the Control Room. The trenches are covered by steel plates, and the vertical chases are faced with sheet rock (not rated). Access panels are provided for each chase at several elevations within the Control Room, and the steel covers on the trenches are removable for manual fire-fighting access. The floor of 3605 contains two cable trenches (approximately 3-1/4 inches deep). These two trenches are covered by steel cover plates that are removable for firefighting access.
Electrical cables of redundant safety-related equipment trains are physically separated within the Control Room. Redundant safety-related circuits enter the Control Room from the Upper and Lower Cable Spreading Rooms. Circuits from the Lower Cable Spreading Room, which are in separation groups 1, 3, and 5 enter the control panels and cabinets directly. Circuits from the Upper Cable Spreading Room, which are in separation groups 2, 4, and 6 are routed to the control panels and cabinets through conduit, vertical wall trays, and under floor cable trenches. Within the control panels, safety-related wiring is separated from redundant circuits and protected in accordance with the guidelines of Regulatory Guide 1.75.
C.27.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-27 is Low.
Internal surfaces of control panels are finished with paint of low flame spread. All cables in these panels meet the vertical flame requirements of ICEA S-19-81 and/or IEEE 383-1974 for flame resistance.
The carpet material used in the control room is 100 percent nylon. This material meets or exceeds the surface flammability requirements per ASTM E84 or CPSC Standard FF1-70, the static propensity rating per ASTM D2679 or AATCC-134, smoke development rating per ASTM E662, and the critical radiant flux rating per ASTM E-648 or NFPA 253.
The suspended acoustical ceiling consists of panels with a maximum flame spread of 25 when tested in accordance with ASTM E 84.
The majority of the paper is stored in steel cabinets, book cases and drawers, which reduces the fire loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 183 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 154 of 250)
C.27.5    Fire Protection As delineated in Attachment A. Automatic smoke detectors are installed in each room containing fixed combustibles and in panels, which contain both trains of redundant safety-related conduit, cable, or wire required for safe shutdown. Smoke detection is also provided for the cable trenches in 3601 and the area above the Control Room proper suspended ceiling. (Reference 3.1, Section F.2)
Manual-pull fire alarm stations are located near the exit doorways from this area.
Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.2)
Automatic smoke detection is provided for the outside air intakes to the Control Room ventilation system. This detection is alarmed in the Control Room, and the Control Room ventilation system can be manually isolated. (Reference 3.1, Section F.2)
An automatic Halon 1301 extinguishing system is provided for the nine cable trench/wall chase combinations in the floor and west wall of Room 3601. The system is designed to maintain a minimum 5-percent concentration for approximately 7 minutes by utilizing an extended discharge following the initial release of Halon agent. This design configuration was accepted in SSER 5. (Reference 3.1, Section F.2)
The Halon cylinders and the control panel are located outside the cable trench protected area. The control panel has a keylock switch to disable system controls during maintenance to prevent any unwanted system actuation. A release button is provided on the control panel to discharge the system manually. Automatic activation will sound a local alarm and discharge the system following a brief time delay. One hundred percent capacity reserve cylinders are provided for connection to the system.
Hose stations and portable extinguishers are provided adjacent to the Control Room area, as indicated on drawing A-1804. Hose stations are equipped with Class "C" spray nozzles with rubber bumpers. These hose stations permit coverage of the area above the suspended ceiling. (Reference 3.1, Section F.2)
The area is accessible for manual firefighting from Communications Corridor Room 3611, Southwest Stairwell 3201, and Auxiliary Building Room 1512. Breathing apparatus are available for Control Room operators. (Reference 3.1, Section F.2)
Drainage in this area is by four 4-inch floor drains. This is adequate to handle maximum hose station discharge. The floor drains are piped to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 184 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 155 of 250)
C.27.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion. Air packs are provided for operating personnel to permit them to remain in the Control Room when smoke is present.
C.27.7    Analysis C.27.7.1        Fire Suppression Personnel access to the Control Room is limited to necessary personnel, and strict administrative controls exist to limit transient combustibles within the Control Room. For these reasons, it is highly improbable that any fire more severe than an electrical fire within a control panel or cabinet could occur.
The fixed paper combustibles are necessary for the safe operation of the plant and are not stored in the immediate vicinity of the panels containing redundant safe shutdown circuits. Nevertheless, exposure fires sufficiently large to destroy any single control panel, before being extinguished, have been postulated. The ability to take the plant to a safe shutdown condition under such a circumstance is addressed in Section C.27.7.2.
The physical separation discussed in Section C.27.3 for redundant cable separation groups prevents an electrically-initiated fire from propagating to the point that it could adversely affect redundant trains. This is based on the limited energy density associated with an electrical fire, the minimum separation distances within any control panel, the physical barriers provided within the panel, and the fire detection and suppression systems provided. Further, since there are no power cables in safety-related control panels, the probability of an electrical fire is low.
Additionally, consistent with the conclusions of NUREG/CR-4527, an internal cabinet fire is not postulated to propagate to an adjacent cabinet when the following are satisfied:
Cabinet of fire origin is protected by a predominantly noncombustible external shell.
Adjacent cabinet is protected by a predominantly noncombustible external shell.
At least a 1 air gap is provided between the cabinet of fire origin and the adjacent cabinet of concern.
The cabinet fire testing documented in NUREG/CR-4527 demonstrated that significant smoke obscuration did not occur until approximately six minutes following cabinet fire ignition.
 
Wolf Creek Nuclear Operating Corporation                                                Page 185 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 156 of 250)
The automatic Halon system will suppress a fire originating in a cable trench. Portable fire extinguishers and hose stations in the foyer to the Control Room and the vestibule to Stairway C-1 provide means of extinguishing any fire that may occur.
C.27.7.2      Safe Shutdown Capability A detailed study, entitled "SNUPPS Control Room Fire Hazards Analysis,"
was submitted to the NRC by letter SLNRC 82-046 dated November 15, 1982. That report addressed transient fires originating between the Control Room panels. Based on revised NRC positions, a report, "Fire Protection Review" was submitted to the NRC by letter SLNRC 84-109, dated August 23, 1984. This report provides the response plan necessary to ensure achievement and maintenance of hot standby conditions from outside the Control Room with postulated Control Room fire damage.
Modifications to the facility and procedure changes have resulted in enhancements to the original response plan identified in SLNRC 84-109.
However, the letters objective to achieve and maintain hot standby in a systematic, prioritized manner is preserved.
In the event that the Control Room is made uninhabitable by smoke, as a consequence of a fire, and there is no damage to safety-related circuits within the Control Room, the plant can be taken to and controlled in a safe hot standby condition from the auxiliary shutdown panel in the Auxiliary Building. The plant can be taken to a cold shutdown condition from outside the Control Room using the auxiliary shutdown panel and local controls at equipment locations and cabinets containing safety related equipment as described in USAR Section 7.4.3.
If, as a consequence of a fire, there is the potential for damage affecting safety-related circuits within Control Room panels, there are switches and contacts on the train B auxiliary shutdown panel (RP118B) that would be used to isolate Control Room circuits. With control at RP118B and following completion of specific actions at other locations outside the Control Room, the plant can be taken to and maintained at a safe hot standby condition. Refer to USAR Table 7.4-1 for the list of selected instrumentation and controls on RP118B that have the isolation feature.
Transition to hot standby as a result of a Control Room fire necessitating Control Room evacuation is procedurally controlled by OFN RP-017.
With the plant in a safe hot standby condition, controls and instrumentation for systems required to take the plant to cold shutdown can be evaluated for operability and cold shutdown activities can be performed from the auxiliary shutdown panels, and locally, as required.
Refer to letter SLNRC 84-109 for further discussion on safe shutdown following a Control Room fire. XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 186 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 157 of 250)
Fire Area C-28 (Reference A-1804)
C.28.1    Fire Area Description Service area by Control Room, Rooms 3602, 3607, and 3608.
C.28.2    Major Equipment None.
C.28.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
C.28.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-28 is Low.
C.28.5    Fire Protection Automatic smoke detection is installed in the janitors closet Room 3608. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A stand-alone heat detector/door closer system is installed in the pantry, room 3602, which actuates closure of the pantry to Control Room door which is normally in the open position. The heat detector actuates the door closer and a strobe located in the Control Room near the pantry door.
Hose stations and portable extinguishers are provided in the foyers of Fire Area C-27 as indicated on drawing A-1804.
The area is accessible for manual firefighting from Communications Corridor Room 3611, Southwest Stairwell 3201, and Auxiliary Building Room 1512.
A sanitary drain is provided in the floor of the restroom for this area. This is acceptable since manual fire water suppression efforts will be minimal, considering the small footprint of the area.
C.28.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                              Page 187 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 158 of 250)
C.28.7    Analysis C.28.7.1      Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually with the portable extinguishers and/or hose station located in the adjacent area.
Continuous occupancy of the adjacent Control room ensures a rapid response to a fire in this area.
C.28.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-28 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-28 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 188 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 159 of 250)
Fire Area C-29 (Reference A-1804)
C.29.1    Fire Area Description SAS Room 3609.
C.29.2    Major Equipment SAS panel.
C.29.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
C.29.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-29 is Low.
C.29.5    Fire Protection Automatic smoke detection is provided in this area. Manual-pull fire alarm stations are located near the exit doorways from the adjacent area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are provided in the foyers of Fire Area C-27, as indicated on drawingA-1804.
The area is accessible for manual fire fighting from Communications Corridor Room 3611, Southwest Stairwell 3201, and Auxiliary Building Room 1512.
No drains are provided for this Fire Area, as manual fire water suppression efforts will be minimal, considering the small footprint of the area.
C.29.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                              Page 189 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 160 of 250)
C.29.7    Analysis C.29.7.1      Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually with the portable extinguishers and/or hose station located in the adjacent area.
Continuous occupancy of the adjacent control room ensures a rapid response to a fire in this area.
C.29.7.2      Safe Shutdown Capability There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 190 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 161 of 250)
Fire Area C-30 (Reference A-1804)
C.30.1    Fire Area Description South Vertical Cable Chase (Room 3617), Control Building. El. 2047-6 to 2073-6.
C.30.2    Major Equipment Electric cable only.
C.30.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.30.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.30.3-1 Fire Area C-30, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts C.30.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-30 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 191 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 162 of 250)
C.30.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent area (C-27). Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-27 and Stairwell Vestibule 3616.
Access to the chase is through a 3-hour-rated fire door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.30.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.30.7    Analysis C.30.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.30.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-30 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-30 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 192 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 163 of 250)
Fire Area C-31 (Reference A-1804)
C.31.1    Fire Area Description North Vertical Cable Chase (Room 3618), Control Building. El. 2047-6 to 2073-6.
C.31.2    Major Equipment Electric cable only.
C.31.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.31.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.31.3-1 Fire Area C-31, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.31.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-31 is Low. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 193 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 164 of 250)
C.31.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent area (C-27). Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-27.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.31.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.31.7    Analysis C.31.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.31.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-31 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-31 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 194 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 165 of 250)
Fire Area C-32 (Reference A-1804)
C.32.1    Fire Area Description Vertical Cable Chase at column line CA-C6, Control Building El. 2047-6 to 2073-6.
C.32.2    Major Equipment Electric cable only.
C.32.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.32.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.32.3-1 Fire Area C-32, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017 C.32.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-32 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 195 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 166 of 250)
C.32.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent area (C-27). Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-27 and Stairwell Vestibule 3616.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.32.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.32.7    Analysis C.32.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barrier and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.32.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-32 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-32 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 196 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 167 of 250)
Fire Area C-33 (Reference A-1804)
C.33.1    Fire Area Description South Vertical Cable Chase (Room 3804), Control Building El. 2073-6.
C.33.2    Major Equipment Electric cable only.
C.33.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature. Since this is the highest elevation, the ceiling of the Fire Area is not rated.
C.33.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-33 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
C.33.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent Room 3801. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-22.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.33.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                              Page 197 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 168 of 250)
C.33.7    Analysis C.33.7.1      Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.33.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-33 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area C-33 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 198 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 169 of 250)
Fire Area C-34 (Reference A-1804)
C.34.1    Fire Area Description Vertical Cable Chase at column line CA-C6, Control Building El. 2073-6.
C.34.2    Major Equipment Electric cable only.
C.34.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, and penetration seals) that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature. Since this is the highest elevation, the ceiling of the Fire Area is not rated.
C.34.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-34 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
C.34.5    Fire Protection Automatic smoke detection is provided in this area. A manual-pull fire alarm station is located at the normal exit from the adjacent Room 3801. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and manual hose stations located in Fire Area C-22.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.34.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                              Page 199 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 170 of 250)
C.34.7    Analysis C.34.7.1      Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.34.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-34 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-34 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 200 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 171 of 250)
Fire Area C-35 (Reference A-1802)
C.35.1    Fire Area Description Control Building corridor, El. 2016 Rooms 3401, 3406, and 3412.
C.35.2    Major Equipment None.
C.35.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.35.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.35.3-1 Fire Area C-35, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Ceramic fiber and sheet metal fire barrier          Fire Barrier segment Missile door 34021                                  Fire Door Fire door 34071                                    Fire Door 3-hour rated fire wrap protection for              Fire Wrap redundant PFSSD circuits Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts
 
Wolf Creek Nuclear Operating Corporation                                                    Page 201 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 172 of 250)
C.35.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-35 is Low.
C.35.5    Fire Protection Due to low combustible loading in this area, a detection system is not installed. Manual-pull stations are located at exit doors. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Fire extinguishers and hose stations are located in this area, as delineated on drawing A-1802.
Access to the area for manual fire fighting is via Communications Corridor 3402 and Stairwell 3201.
There are four floor drains located in this area (a fifth drain in the area is capped). These drains are adequate to handle hose station discharge. The floor drains are piped to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps.
Refer to drawing series M-12LE for further information on the oily waste drain system.
C.35.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
C.35.7    Analysis C.35.7.1        Fire Suppression The fire barriers enclosing this area will protect this area from a fire in the adjoining areas and will contain a fire within this area until extinguished. A fire in this area would be extinguished manually using the hose stations and extinguishers shown on drawing A-1802.
C.35.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-35 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-35 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 202 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 173 of 250)
Fire Area C-36 (Reference A-1802)
C.36.1    Fire Area Description Cable Chase at column line CA-C6, Control building El. 2000 to 2016.
C.36.2    Major Equipment Electric cable only.
C.36.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.36.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.36.3-1 Fire Area C-36, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.36.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-36 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 203 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 174 of 250)
C.36.5    Fire Protection A manual-pull fire alarm station is located at the normal exit from this floor elevation. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and a manual hose station located in the ESF Switchgear Room (3302) at this elevation.
Access to the chase is through a 3-hour-rated fire door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.36.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.36.7    Analysis C.36.7.1        Fire Suppression In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.36.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-36 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-36 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 204 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 175 of 250)
Fire Area C-37 (Reference A-1802)
C.37.1    Fire Area Description Cable Chase at column line CA-C3, Control building El. 2000 to 2016.
C.37.2    Major Equipment Electric cable only.
C.37.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table C.37.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table C.37.3-1 Fire Area C-37, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Structural Steel Fireproofing with                Structural Steel Fireproofing unprotected thermal shorts C.37.4    Combustible Loading The cumulative combustible loading classification for Fire Area C-37 is High. Refer to Section 4.3.5 for further discussion regarding cable chase combustible loading.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 205 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 176 of 250)
C.37.5    Fire Protection A manual-pull fire alarm station is located at the normal exit from this floor elevation. Pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system, is installed in this area. The system is equipped with closed head spray nozzles. Backup to the automatic sprinkler system is by portable extinguishers and a manual hose station located in the ESF Switchgear Room (3301) at this elevation.
Access to the chase is through a 3-hour-rated door.
Drainage in this area is by one 4-inch floor drain. This is adequate to handle maximum sprinkler system discharge and hose station discharge. The drain discharges to the 1974 elevation and ultimately to the Control Building Sump, which is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
C.37.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. No ventilation ductwork penetrates the fire barriers in this Fire Area. Refer to Section 4.3.7.2 for smoke removal discussion.
C.37.7    Analysis C.37.7.1        Fire Suppression In the event that a fire develops, it will be contained by the fire barriers and extinguished by the automatic suppression system. Should the automatic suppression system fail, manual hose streams can be directed through the access opening to extinguish the fire.
C.37.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a C-37 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area C-37 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 206 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 177 of 250)
Fire Area CC-1 (Reference A-1801 through A-1804)
CC.1.1    Fire Area Description Communications corridor (all elevations) Rooms 3102, 3103, 3225, 3226 3227, 3228, 3303, 3304, 3402 3502, 3503, 3611 3612, 3613 3614, 3619, 3701, 3702, 3703, 3704, 3705, 3802, 3803, and OP-6.
CC.1.2    Major Equipment Plant computer, central chilled and hot water package, and HVAC equipment, batteries, hydrogen monitor, power distribution equipment.
CC.1.3    Design Features With the exception of the open communication with the Turbine Building on the east end, this Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table CC.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table CC.1.3-1 Fire Area CC-1, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Missile door 14032                                Fire Door Missile door 33012                                Fire Door Missile door 33044                                Fire Door Missile door 34021                                Fire Door Missile door 35021                                Fire Door Missile door 36042                                Fire Door Missile door 38011                                Fire Door Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017
 
Wolf Creek Nuclear Operating Corporation                                                    Page 207 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 178 of 250)
The ceiling of this area is the building roof, and the bottom floor is on grade. At floor El.
2000 feet and above, this area is open to the Turbine Building. However, Rooms 3702 and 3703 are separated from all of the adjacent rooms within the Communication Corridor and Turbine Building by fire rated barriers; floor, walls and ceiling. The floor of the Rooms (3702, 3703) are at EL. 2061'-6" and the ceiling is at EL. 2074'-2".
CC.1.4    Combustible Loading The cumulative combustible loading classification for Fire Area CC-1 is Low. This includes the combustible gas cylinder rack in Room 3102 that is necessary for laboratory analysis activities in the Health Physics Hot Laboratory.
The combustible loading associated with Rooms 3702 and 3703 is not considered to contribute to a fire in this Fire Area due to the fire barriers provided for each of these rooms.
CC.1.5    Fire Protection Automatic smoke detectors are installed in areas which contain appreciable quantities of combustibles. Attachment A identifies the specific rooms in this Fire Area that contain detection. Manual-pull fire alarm stations are located near the exit doorways from each elevation of this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
At the floor elevations below the turbine operating floor where the Communications Corridor opens into the Turbine Building, an automatic pre-action sprinkler system is provided in the Turbine Building to protect this area from a fire in the Turbine Building.
Access to this area is from the Control Building through doors at each elevation, from the Turbine Building, and from the exterior through doors in the north wall of the building.
Adequate drainage is provided to handle maximum hose station discharge. The drains discharge to the Control Building oily waste sump in Room 3102. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
CC.1.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
CC.1.7    Analysis CC.1.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In all areas, the fire can be extinguished, using hose stations and/or portable extinguishers.
 
Wolf Creek Nuclear Operating Corporation                                              Page 208 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 179 of 250)
CC.1.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an CC-1 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area CC-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in CC-1.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 209 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 180 of 250)
Fire Area D-1 (Reference A-1802 through A-1804)
D.1.1      Fire Area Description Diesel Generator Room 5203 (east).
D.1.2      Major Equipment Standby diesel generator package, associated auxiliaries, and fuel oil day tank.
D.1.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table D.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area. (Reference 3.1, Section F.9)
Table D.1.3-1 Fire Area D-1, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts To minimize property damage, the 18 concrete slab roof is also a fire rated boundary, with the exception of the ventilation openings. No safety-related equipment is located above the buildings ceiling. (Reference 3.1, Section F.9)
A curb is provided at the interconnecting door between this area and the ESF Switchgear Room (Fire Area C-10) to prevent the sprinkler system discharge from passing into Fire Area C-10.
 
Wolf Creek Nuclear Operating Corporation                                                Page 210 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 181 of 250)
The trench between the two Diesel Generator Rooms (P511W0018) is sealed with full depth grout at the communicating wall (column line DB). This seal configuration provides at least a 3-hour fire resistance rating.
D.1.4      Combustible Loading The cumulative combustible loading classification for Fire Area D-1 is Moderate.
The diesel fuel oil day tank has a nominal capacity of 550 gallons. The dike around the base of the tank will hold at least 110 percent of the tank contents. The dike area is drained by gravity to a 900-gallon, covered sump in the same Diesel Generator Room.
The oil can be pumped outdoors to a truck connection for removal from the building.
Each diesel fuel oil tank is provided with protection features to preclude the uncontrolled leakage of diesel fuel. The design features provided for the day tank were reviewed and accepted by the NRC at the Wolf Creek Fire Protection Audit of February 6 to 9, 1984.
(Reference 3.1, Section F.9)
Diesel fuel is stored in underground tanks. The diesel fuel storage tanks are buried approximately 23 feet from the Diesel Generator Building wall. The storage tanks are set on a firm foundation, backfilled with noncorrosive sand surrounding the tank (6 inches minimum) and provided with a covering of 2 feet (minimum) of earth. This bulk storage of flammable liquids is remote from PFSSD SSCs. (Reference 3.1, Section F.10)
D.1.5      Fire Protection Automatic thermal detectors and infrared detectors are provided in this area. Manual-pull fire alarm stations are located near the exit doorways from this area. Detector or pull station activation alarms locally and in the Control Room. The Control Room annunciation is zoned for quick identification of the specific area in alarm. (Reference 3.1, Section F.9)
An automatic preaction sprinkler system is provided for this area. The system is charged by thermal detector alarm or by manual activation of the suppression release station located in Room 3302, (outside the north exit from Fire Area D-1). Thermal detector or suppression release station activation will also lockout the emergency diesel generator fuel oil transfer pump, unless the pump is running. This configuration is provided to preclude a spurious fire protection system trip under accident conditions that would present a negative consequence to emergency diesel generator performance.
(Reference 3.1, Section F.9)
A hose station and portable extinguishers are provided just outside this Fire Area, and portable extinguishers are located within the area, as indicated on drawing A-1802. The hose station is equipped with 100 feet of hose for effective coverage of this Fire Area.
The area is accessible for manual fire fighting from the south ESF Switchgear Room 3302.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 211 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 182 of 250)
Adequate floor drains are provided in the area to remove sprinkler and hose station discharge without appreciable accumulation. The drainage is collected in a sump within the area. The sump is emptied by sump pumps. The sump pump discharge lines from the two Diesel Generator Room sumps are connected outside of the Diesel Generator Building. It is not possible for a flame to spread through the pumps, valves, and piping from one sump to another. Refer to drawing series M-12LE for further information on the oily waste drain system. (Reference 3.1, Section F.9)
D.1.6      Isolation and Smoke Removal A fire in this area will be contained by the fire barriers. Heat and smoke venting for each Diesel Generator Room is provided by utilizing the exhaust air flow path. The free area of the exhaust air flow path provides at least 1.0 square feet of venting area for each 200 square feet of floor area. Smoke exhaust fans per se are not employed. Normal ventilation exhaust systems are utilized throughout for smoke removal. (Reference 3.1, Section F.9)
D.1.7      Analysis D.1.7.1          Fire Suppression Early warning fire detection is by infrared detectors, which will readily detect the type of fire caused by the burning of fuel and lube oils. In the event of a large fire, thermal detectors will charge the sprinkler system and the fusible link heads will open to extinguish the fire.
In the event the automatic system fails (identified by Control Room annunciation), the hose stream available will control the fire. As previously discussed, a thermal fire detection signal stops the emergency diesel generator fuel oil transfer pump, unless it is running. Depending upon the quantity of oil involved in the fire at this point, manual extinguishment with portable extinguishers and/or the hose station may be possible. If additional hose streams are required, the room is accessible from the yard hose hydrant system.
D.1.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an D-1 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area D-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in D-1.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 212 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 183 of 250)
Fire Area D-2 (Reference A-1802 through A-1804)
D.2.1      Fire Area Description Diesel Generator Room 5201 (west).
D.2.2      Major Equipment Standby diesel generator package, associated auxiliaries, and fuel oil day tank.
D.2.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table D.2.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area. (Reference 3.1, Section F.9)
Table D.2.3-1 Fire Area D-2, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts To minimize property damage , the 18 concrete slab roof is also a fire rated boundary, with the exception of the ventilation openings. No safety-related equipment is located above the buildings ceiling. (Reference 3.1, Section F.9)
A curb is provided at the interconnecting door between this area and the ESF Switchgear Room (Fire Area C-10) to prevent the sprinkler system discharge from passing into Fire Area C-10.
 
Wolf Creek Nuclear Operating Corporation                                                Page 213 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 184 of 250)
The trench between the two Diesel Generator Rooms (P511W0018) is sealed with full depth grout at the communicating wall (column line DB). This seal configuration provides at least a 3-hour fire resistance rating.
D.2.4      Combustible Loading The cumulative combustible loading classification for Fire Area D-2 is Moderate.
The diesel fuel oil day tank has a nominal capacity of 550 gallons. The dike around the base of the tank will hold at least 110 percent of the tank contents. The dike area is drained by gravity to a 900-gallon, covered sump in the same Diesel Generator Room.
The oil can be pumped outdoors to a truck connection for removal from the building.
Each diesel fuel oil tank is provided with protection features to preclude the uncontrolled leakage of diesel fuel. The design features provided for the day tank were reviewed and accepted by the NRC at the Wolf Creek Fire Protection Audit of February 6 to 9, 1984.
(Reference 3.1, Section F.9)
Diesel fuel is stored in underground tanks. The diesel fuel storage tanks are buried approximately 23 feet from the Diesel Generator Building wall. The storage tanks are set on a firm foundation, backfilled with noncorrosive sand surrounding the tank (6 inches minimum) and provided with a covering of 2 feet (minimum) of earth. This bulk storage of flammable liquids is remote from PFSSD SSCs. (Reference 3.1, Section F.10)
D.2.5      Fire Protection Automatic thermal detectors and infrared detectors are provided in this area. Manual-pull fire alarm stations are located near the exit doorways from this area. Detector or pull station activation alarms locally and in the Control Room. The Control Room annunciation is zoned for quick identification of the specific area in alarm. (Reference 3.1, Section F.9)
An automatic preaction sprinkler system is provided for this area. The system is charged by thermal detector alarm or by manual activation of the suppression release station located in Room 3302, (outside the north exit from Fire Area D-2). Thermal detector or suppression release station activation will also lockout the emergency diesel generator fuel oil transfer pump, unless the pump is running. This configuration is provided to preclude a spurious fire protection system trip under accident conditions that would present a negative consequence to emergency diesel generator performance.
(Reference 3.1, Section F.9)
A hose station and portable extinguishers are provided just outside this Fire Area, and portable extinguishers are located within the area, as indicated on drawing A-1802. The hose station is equipped with 100 feet of hose for effective coverage of this Fire Area.
The area is accessible for manual fire fighting from the south ESF Switchgear Room 3302.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 214 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 185 of 250)
Adequate floor drains are provided in the area to remove sprinkler and hose station discharge without appreciable accumulation. The drainage is collected in a sump within the area. The sump is emptied by sump pumps. The sump pump discharge lines from the two Diesel Generator Room sumps are connected outside of the Diesel Generator Building. It is not possible for a flame to spread through the pumps, valves, and piping from one sump to another. Refer to drawing series M-12LE for further information on the oily waste drain system. (Reference 3.1, Section F.9)
D.2.6      Isolation and Smoke Removal A fire in this area will be contained by the fire barriers. Heat and smoke venting for each Diesel Generator Room is provided by utilizing the exhaust air flow path. The free area of the exhaust air flow path provides at least 1.0 square feet of venting area for each 200 square feet of floor area. Smoke exhaust fans per se are not employed. Normal ventilation exhaust systems are utilized throughout for smoke removal. (Reference 3.1, Section F.9)
D.2.7      Analysis D.2.7.1          Fire Suppression Early warning fire detection is by infrared detectors, which will readily detect the type of fire caused by the burning of fuel and lube oils. In the event of a large fire, thermal detectors will charge the sprinkler system and the fusible link heads will open to extinguish the fire.
In the event the automatic system fails (identified by Control Room annunciation), the hose stream available will control the fire. As previously discussed, a thermal fire detection signal stops the emergency diesel generator fuel oil transfer pump, unless it is running. Depending upon the quantity of oil involved in the fire at this point, manual extinguishment with portable extinguishers and/or the hose station may be possible. If additional hose streams are required, the room is accessible from the yard hose hydrant system.
D.2.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an D-2 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area D-2 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in D-2.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 215 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 186 of 250)
Fire Area ESWA (Reference M-KG080, E-KF0231 and E-KR0231)
ESWA.1    Fire Area Description Essential Service Water Pumphouse Room K105, Access Vaults MHE1 through MHE5 and Train A ESW Electrical Duct Banks Room K105A.
ESWA.2    Major Equipment Essential Service Water Pumps, Traveling Screens, Strainers, Pre-Lube Storage Tank, Ventilation Fans, Electric Cable and ESW Electrical Duct Banks and Access Vaults.
ESWA.3    Design Features This Fire Area is separated from adjacent Fire Area ESWB by a common concrete wall and penetration closure assemblies that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, UL-555, or IEEE-634) for the respective barrier assembly protective feature. No door is present in this fire boundary.
Buried raceways containing electrical cabling associated with the Essential Service Water System are routed from the ESW Pump House to the Control Building. The raceways are embedded below grade except where they transition through a total of five access vaults.
At these locations a buried concrete vault containing two cells is provided to separate the redundant raceways. Each cell within a vault physically separates redundant train cable by a minimum of 18 concrete construction on all sides. The vault equipment hatches have an 18 overlap with vault interior walls and the manway hatches have at least an 11 overlap. All penetrations into the vaults are adequately sealed to minimize in leakage of air or water.
ESWA.4    Combustible Loading The cumulative combustible loading classification for Fire Area ESWA is Low. This combustible loading applies to Room K105 only. Combustible loading for the access vaults and electrical duct banks (Room K105A) is not quantified.
The ESW system is manually treated for organic fouling with a microbial control agent (biocide) that is a combustible liquid. The liquid is piped within the ESWA where it taps into the ESW system piping.
ESWA.5    Fire Protection Room K105 (Train A ESW Pumphouse)
Automatic smoke detectors are installed at the ceiling of the area. A manual-pull fire alarm station is located at the exit from this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.11)
 
Wolf Creek Nuclear Operating Corporation                                                  Page 216 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 187 of 250)
Portable extinguishers and hose stations are provided for manual fire suppression. Water for the hose stations is taken from the ESW piping, however these stations are pressurized by the service water system from the Circulating Water Screen House unless a low suction pressure signal in the Auxiliary Feedwater System, an SIS or loss of off-site power signal has caused the ESW pumps to start. Under these conditions water is taken from the ESW System. Any water used in this area for fire suppression would flow to the ultimate heat sink. Refer to Figure ESWA.5-1 for the ESW Pump House hose station configuration. (Reference 3.1, Section F.11)
Access for manual firefighting is via exterior access through door K1051.
Figure ESWA.5-1, ESW Hose Stations Room K105A (Train A ESW Duct Banks and Access Vaults)
Fire hydrants are located in the vicinity of the vaults for manual firefighting. The cooling lake is also in the vicinity for manual firefighting.
ESWA.6    Isolation and Smoke Removal Room K105 - The fire barrier will contain a fire within the Fire Area until extinguished.
Refer to Section 4.3.7.2 for smoke removal discussion.
Room K105A - A fire in any one of the cells within a vault will be contained to the cell of origin and will not propagate to the adjacent cell within a vault. The 18 thick concrete walls and ceilings, along with the hatch cover overlap, will help to prevent a fire from propagating into another vault or the surrounding area. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                Page 217 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 188 of 250)
ESWA.7    Analysis ESWA.7.1      Fire Suppression Room K105 The fire hazard associated with the injection process for ESW chemical treatment is the undiluted combustible liquid filled piping located in ESWA.
Leakage from the pipe containing concentrated biocide within the ESWA is not anticipated, as the material is compatible with the pipe type, and the piping stresses are within ANSI B31.1 allowable values considering an operation basis earthquake and safe shutdown earthquake loads.
Additionally, the piping will only contain the combustible liquid concentration under pressure during periods of chemical injection. During periods of chemical injection inactivity, only residual biocide will remain in the distribution piping to ESW. In the unlikely event of a leak within the piping containing concentrated biocide, only Fire Area ESWA would be affected, as the fire barrier between the pump rooms prevent the same fire from damaging redundant ESW trains.
Due to the complete solubility of the biocide product in water and the very small concentrations of product in ESW system, there is no fire hazard concern associated with the product after it is diluted with ESW water in Fire Area ESWA.
Manual fire suppression equipment is available to extinguish a fire in this area. (Reference 3.1, Section F.11)
Room K105A Manual fire protection equipment is available to control and extinguish any postulated vault fire.
ESWA.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an ESWA fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area ESWA will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 218 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 189 of 250)
Fire Area ESWB (Reference M-KG080, E-KF0231 and E-KR0231)
ESWB.1    Fire Area Description Essential Service Water Pumphouse Room K104, Access Vaults MHE1 through MHE5 and Train B ESW Electrical Duct Banks Room K104A.
ESWB.2    Major Equipment Essential Service Water Pumps, Traveling Screens, Strainers, Pre-Lube Storage Tank, Ventilation Fans, Electric Cable and ESW Electrical Duct Banks and Access Vaults.
ESWB.3    Design Features This Fire Area is separated from adjacent Fire Area ESWA by a common concrete wall and penetration closure assemblies that are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, UL-555, or IEEE-634) for the respective barrier assembly protective feature. No door is present in this fire boundary.
Buried raceways containing electrical cabling associated with the Essential Service Water System are routed from the ESW Pump House to the Control Building. The raceways are embedded below grade except where they transition through a total of five access vaults.
At these locations a buried concrete vault containing two cells is provided to separate the redundant raceways. Each cell within a vault physically separates redundant train cable by a minimum of 18 concrete construction on all sides. The vault equipment hatches have an 18 overlap with vault interior walls and the manway hatches have at least an 11 overlap. All penetrations into the vaults are adequately sealed to minimize in leakage of air or water.
ESWB.4    Combustible Loading The cumulative combustible loading classification for Fire Area ESWB is Low. This combustible loading applies to Room K104 only. Combustible loading for the access vaults and electrical duct banks (Room K104A) is not quantified.
The ESW system is manually treated for organic fouling with a microbial control agent (biocide) that is a combustible liquid. The liquid is piped within the ESWA where it taps into the ESW system piping.
ESWB.5    Fire Protection Room K104 (Train B ESW Pumphouse)
Automatic smoke detectors are installed at the ceiling of the area. A manual-pull fire alarm station is located at the exit from this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.11)
 
Wolf Creek Nuclear Operating Corporation                                                  Page 219 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 190 of 250)
Portable extinguishers and hose stations are provided for manual fire suppression. Water for the hose stations is taken from the ESW piping, however these stations are pressurized by the service water system from the Circulating Water Screen House unless a low suction pressure signal in the Auxiliary Feedwater System, an SIS or loss of off-site power signal has caused the ESW pumps to start. Under these conditions water is taken from the ESW System. Any water used in this area for fire suppression would flow to the ultimate heat sink. Refer to Figure ESWB.5-1 for the ESW Pump House hose station configuration. (Reference 3.1, Section F.11)
Access for manual firefighting is via exterior access through door K1041.
Figure ESWB.5-1, ESW Hose Stations Room K104A (Train B ESW Duct Banks and Access Vaults)
Fire hydrants are located in the vicinity of the vaults for manual firefighting. The cooling lake is also in the vicinity for manual firefighting.
ESWB.6    Isolation and Smoke Removal Room K104 - The fire barriers will contain a fire within the Fire Area until extinguished.
Refer to Section 4.3.7.2 for smoke removal discussion.
Room K104A - A fire in any one of the cells within a vault will be contained to the cell of origin and will not propagate to the adjacent cell within a vault. The 18 thick concrete walls and ceilings, along with the hatch cover overlap, will help to prevent a fire from propagating into another vault or the surrounding area. Refer to Section 4.3.7.2 for smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                                Page 220 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 191 of 250)
ESWB.7    Analysis ESWB.7.1      Fire Suppression Room K104 The fire hazard associated with the injection process for ESW chemical treatment is the undiluted combustible liquid filled piping located in ESWA.
Due to the complete solubility of the biocide product in water and the very small concentrations of product in ESW system, there is no fire hazard concern associated with the product after it is diluted with ESW water in Fire Area ESWA. ESWB only contains diluted biocide.
In the unlikely event of a leak within the piping containing concentrated biocide, only Fire Area ESWA would be affected, as the fire barrier between the pump rooms prevent the same fire from damaging redundant ESW trains.
As discussed above, the fire barrier between the pump rooms prevents a single fire from damaging ESW trains. Therefore, a fire originating in ESWB will not impact ESWA. Manual fire suppression equipment is available to extinguish a fire in this area. (Reference 3.1, Section F.11)
Room K104A Manual fire protection equipment is available to control and extinguish any postulated vault fire.
ESWB.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an ESWB fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area ESWB will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                              Page 221 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 192 of 250)
Fire Area ESWV (Reference M-KX9002, C-K230, C-K231, C-K232, C-K233, C-K234)
ESWV.1    Fire Area Description Essential Service Water Yard Pipe Access Vaults AV1 (Z118A), AV2 (Z118B), AV3 (Z118C), AV4 (Z118D), AV5 (Z118E), and AV6 (Z118F).
ESWV.2    Major Equipment ESW Piping Access Vaults.
ESWV.3    Design Features Each of the two redundant trains of Essential Service Water System, supply and return piping, pass through buried vaults located in the yard. The vaults are physically independent structures, recessed at grade elevation. All penetrations into the vaults are adequately sealed to minimize in leakage of air or water.
ESW Access Vault AV1 (Z118A) is broken up into two chambers separated by a 2 foot thick concrete wall. Each chamber is 19 feet-3 inches by 24 feet and the access vault has a vault height of 10 feet-9 inches. Details for AV1 are shown on drawing C-K230.
ESW Access Vaults AV2 (Z118B) and AV5 (Z118E) measure approximately 10 feet-6 inches by 24 feet and have a vault height of 11 feet-3 inches. Details for AV2 and AV5 are shown on drawing C-K231.
ESW Access Vault AV3 (Z118C) has a main vault area that measures 44 feet by 12 feet-3 inches and has a vault height of 11 feet-6 inches. There is a small 6 foot by 5 foot valve operations compartment separated from the main AV3 vault chamber by a 2 foot thick concrete wall. Details for vault AV3 are shown on drawing C-K232.
ESW Access vault AV4 (Z118D) has a main vault area that measures 46 feet by 17 feet-9 inches and has a vault height of 10 feet-6 inches. There is a small 6 foot by 5 foot valve operations compartment from the main AV4 vault chamber by a 2 foot thick concrete wall.
Details for vault AV4 are shown on drawing C-K233.
ESW Access Vault AV6 (Z118F) is broken up into two chambers separated by a 2 foot thick concrete wall. Each chamber is 14 feet-3 inches by 27 feet and the access vault has a vault height of 10 feet. Details for AV6 are shown on drawing C-K234.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 222 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 193 of 250)
For all of the ESW access vaults the roof panels have a 2 foot overlap and lineup flush with the vault walls. The man-way access cover panels have a 5 foot - 6 inch overlap.
Vault AV1 has two instrument penetrations in the roof panel. The instruments are used for indication only, no control functions. Vault AV5 has one instrument penetration in the roof panel. The instrument is used for indication only, no control function. Vault AV3, Train B only, has one instrument penetration in the roof panel that is used for indication only, no control functions. Vault AV3 has another instrument penetration that is used for access to instruments in the pipe area, no control functions. Vault AV4, Train A only, has one instrument penetration in the roof panel that is used for indication only, no control functions. Vault AV4 has another instrument penetration that is used for access to instruments in the pipe area, no control functions. Vaults AV3 and AV4 have 120VAC routed into the vault that is used for flow and temperature instrumentation, indication only, no control functions.
ESWV.4    Combustible Loading The cumulative combustible loading classification for each vault is Low.
ESWV.5    Fire Protection Fire hydrants are located in the vicinity of the vaults for manual firefighting. The cooling lake is also in the vicinity for manual firefighting.
ESWV.6    Isolation and Smoke Removal A fire in any one of the pipe access vaults will be contained to the vault and will not propagate to the surrounding area. The two foot thick concrete walls and ceilings, along with the hatch cover overlap, will help to prevent a fire from propagating into another vault or the surrounding area. Refer to Section 4.3.7.2 for smoke removal discussion.
ESWV.7    Analysis ESWV.7.1        Fire Suppression There are no ignition sources located within vaults AV1, AV2, AV5, and AV6. The vaults are unheated. Vaults AV3 and AV4 have 120VAC routed into the vault that is used for flow and temperature instrumentation, indication only with no control functions. Manual fire protection equipment is available to control and extinguish any postulated vault fires.
ESWV.7.2        Safe Shutdown Capability A vault fire will not impact safe shutdown capability. There are no electrically powered safe shutdown components or circuits located in any of the vaults to be damaged by fire. Redundant trains of the Essential Service Water System will not be affected by a single fire in any one of the vaults. Physical separation of the vaults precludes the possibility of a single fire in any one of the vaults from affecting the redundant train vault.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 223 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 194 of 250)
Fire Area F-1 (Reference A-1802 through A-1804)
F.1.1      Fire Area Description Fuel Building General Area all elevations, Rooms 6101, 6102, 6103, 6106, 6201, 6204, 6205, 6210, 6301, and 6302.
F.1.2      Major Equipment Fuel storage pool bridge crane and cask handling crane.
F.1.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table F.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table F.1.3-1 Fire Area F-1, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category No structural steel fireproofing                  Structural Steel Fireproofing Fuel transfer tube penetration                    Penetration Seal Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017 The bottom floor of this area is on soil and, consequently, is not rated. The structural steel of the Fuel Building is not structurally tied into the Auxiliary Building.
New fuel storage is designed for optimum moderation conditions. Refer to USAR Section 9.1 for further discussion. (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                  Page 224 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 195 of 250)
F.1.4      Combustible Loading The cumulative combustible loading classification for Fire Area F-1 is Low.
F.1.5      Fire Protection Thermal detectors are installed in the Railroad bay area, while infrared flame detectors are also provided for Refueling Floor El 2047 feet 6 inches. The detection system alarms locally and in the Control Room. The Control Room annunciation is zoned for quick identification of the area in alarm. Manual-pull fire alarm stations are located near the exit doorways from this area. The pull stations also alarm locally and in the Control Room.
(Reference 3.1, Section F.12 and F.13)
An automatic preaction sprinkler system is provided for Room 6102, Railroad Bay/Laydown area.
Hose stations and portable extinguishers are provided throughout this fire area, as indicated on drawings A-1802 and A-1804. (Reference 3.1, Section F.12 and F.13)
This area is accessible through one personnel door and one railroad door from the exterior and through a personnel door at each floor elevation at the northwest corner of the building from the Auxiliary Building.
Adequate floor drains (21 total) are provided in the area to remove sprinkler and hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
(Reference 3.1, Section F.12)
F.1.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
F.1.7      Analysis F.1.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers. The preaction sprinkler system in Room 6102, is activated by thermal detection. It does not protect safe shutdown equipment. Consequently, failure of this system to operate will not prevent safe shutdown.
 
Wolf Creek Nuclear Operating Corporation                                              Page 225 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 196 of 250)
F.1.7.2      Safe Shutdown Capability No fire could cause structural damage to the fuel storage racks in the Fuel Storage Pool. A fire during fuel handling operations could cause damage to either of the fuel handling cranes; however, both cranes are designed to fail safe.
As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an F-1 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area F-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-1.
 
Wolf Creek Nuclear Operating Corporation                                                Page 226 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 197 of 250)
Fire Area F-2 (Reference A-1802)
F.2.1      Fire Area Description Fuel Pool Cooling Heat Exchanger Room 6104 (west), El. 2000-0.
F.2.2      Major Equipment Fuel pool cooling heat exchanger B, fuel pool cooling pump B, room cooler, and fuel pool cleanup pumps.
F.2.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table F.2.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table F.2.3-1 Fire Area F-2, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Trench cover panels                                Fire Barrier Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts F.2.4      Combustible Loading The cumulative combustible loading classification for Fire Area F-2 is Low. (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                  Page 227 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 198 of 250)
F.2.5      Fire Protection An automatic smoke detection system is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.12)
Hose stations and portable extinguishers are provided just outside this Fire Area, as indicated on drawing A-1802. (Reference 3.1, Section F.12)
This area is accessible through a door at the south end of the room and a door at the northwest corner.
Adequate floor drains (3 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in the room. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system. (Reference 3.1, Section F.12)
F.2.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
F.2.7      Analysis F.2.7.1          Fire Suppression A fire in the area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
F.2.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an F-2 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area F-2 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-2.
 
Wolf Creek Nuclear Operating Corporation                                                Page 228 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 199 of 250)
Fire Area F-3 (Reference A-1802)
F.3.1      Fire Area Description Fuel Pool Cooling Heat Exchanger Room 6105 (east), ), El. 2000-0.
F.3.2      Major Equipment Fuel pool cooling heat exchanger A, fuel pool cooling pump A, and room cooler.
F.3.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table F.3.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table F.3.3-1 Fire Area F-3, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts F.3.4      Combustible Loading The cumulative combustible loading classification for Fire Area F-3 is Low. (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                  Page 229 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 200 of 250)
F.3.5      Fire Protection An automatic smoke detection system is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.12)
Hose stations and portable extinguishers are provided just outside this Fire Area, as indicated on drawing A-1802. (Reference 3.1, Section F.12)
This area is accessible through a door at the south end of the room.
Adequate floor drains (3 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system. (Reference 3.1, Section F.12)
F.3.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
F.3.7      Analysis F.3.7.1          Fire Suppression A fire in the area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
F.3.7.2          Safe Shutdown Capability There are no PFSSD equipment or circuits in this area, therefore fire damage to this area will not prevent safe shutdown. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-3.
 
Wolf Creek Nuclear Operating Corporation                                                Page 230 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 201 of 250)
Fire Area F-4 (Reference A-1803)
F.4.1      Fire Area Description Air Handling Equipment Room 6203, El. 2026.
F.4.2      Major Equipment Fuel Building supply air units, Fuel Building heating coil unit, fuel handling area cooling coil.
F.4.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table F.4.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table F.4.3-1 Fire Area F-4, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts F.4.4      Combustible Loading The cumulative combustible loading classification for Fire Area F-4 is Low. (Reference 3.1, Section F.12)
F.4.5      Fire Protection
 
Wolf Creek Nuclear Operating Corporation                                                  Page 231 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 202 of 250)
An automatic smoke detection system is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.12)
A hose station and portable extinguishers are provided within this Fire Area. If access to these is blocked by a fire within the area, the hose station and portable extinguishers in Room 1408 of the Auxiliary Building can be used. (Reference 3.1, Section F.12)
This area is accessible through doors from the adjacent room and from the Auxiliary Building (Room 1408).
Adequate floor drains (3 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system. (Reference 3.1, Section F.12)
F.4.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
F.4.7      Analysis F.4.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
F.4.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an F-4 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area F-4 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-4.
 
Wolf Creek Nuclear Operating Corporation                                                Page 232 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 203 of 250)
Fire Area F-5 (Reference A-1803)
F.5.1      Fire Area Description Electrical Equipment Room 6202, El. 2026.
F.5.2      Major Equipment Load centers and motor control centers.
F.5.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table F.5.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table F.5.3-1 Fire Area F-5, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts F.5.4      Combustible Loading The cumulative combustible loading classification for Fire Area F-5 is Low. (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                  Page 233 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 204 of 250)
F.5.5      Fire Protection An automatic smoke detection system is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.12)
A portable extinguisher is provided in this Fire Area and hose stations and portable extinguishers are provided just outside this Fire Area, as indicated on drawing A-1803.
(Reference 3.1, Section F.12)
The area is accessible through double doors in the north and south walls of the area.
Adequate floor drains (2 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system. (Reference 3.1, Section F.12)
F.5.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
F.5.7      Analysis F.5.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
F.5.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an F-5 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area F-5 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-5.
 
Wolf Creek Nuclear Operating Corporation                                                Page 234 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 205 of 250)
Fire Area F-6 (Reference A-1804)
F.6.1      Fire Area Description Emergency Exhaust Equipment Room 6304 (east), El. 2047-6.
F.6.2      Major Equipment Emergency exhaust filter/adsorber unit and emergency exhaust fan.
F.6.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table F.6.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table F.6.3-1 Fire Area F-6, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts F.6.4      Combustible Loading The cumulative combustible loading classification for Fire Area F-6 is Low. (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                  Page 235 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 206 of 250)
F.6.5      Fire Protection An automatic smoke detection system is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.12)
Hose stations and portable extinguishers are provided just outside this Fire Area, as indicated on drawing A-1804. (Reference 3.1, Section F.12)
The emergency exhaust filter adsorber unit does not normally operate. Downstream of the charcoal bed is a thermistor-type continuous thermal detector, which alarms in the Control Room at high air stream temperature. This unit is equipped with a hose connection to provide manual water spray protection.
Access to this area is through a door at the south end of the room.
Adequate floor drains (3 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system. (Reference 3.1, Section F.12)
F.6.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
F.6.7      Analysis F.6.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
F.6.7.2          Safe Shutdown Capability This area contains no PFSSD equipment or circuits and is separated from adjoining Fire Areas by fire barrier construction. Therefore, a fire within Fire Area F-6 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-6.
 
Wolf Creek Nuclear Operating Corporation                                                Page 236 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 207 of 250)
Fire Area F-7 (Reference A-1804)
F.7.1      Fire Area Description Emergency Exhaust Equipment Room 6303 (west), El. 2047-6.
F.7.2      Major Equipment Emergency exhaust filter/adsorber unit and emergency exhaust fan.
F.7.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table F.7.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table F.7.3-1 Fire Area F-7, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding          Penetration Seal limitations of M-663-00017 Structural Steel Fireproofing with unprotected Structural Steel Fireproofing thermal shorts F.7.4      Combustible Loading The cumulative combustible loading classification for Fire Area F-7 is Low. (Reference 3.1, Section F.12)
 
Wolf Creek Nuclear Operating Corporation                                                  Page 237 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 208 of 250)
F.7.5      Fire Protection An automatic smoke detection system is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from the Fuel Building. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. (Reference 3.1, Section F.12)
Hose stations and portable extinguishers are provided just outside this Fire Area, as indicated on drawing A-1804. (Reference 3.1, Section F.12)
The emergency exhaust filter adsorber unit does not normally operate. Downstream of the charcoal bed is a thermistor-type continuous thermal detector, which alarms in the Control Room at high air stream temperature. This unit is equipped with a hose connection to provide manual water spray protection.
Access to this area is through a door at the south end of the room.
Adequate floor drains (3 total) are provided in the area to remove hose station discharge without appreciable accumulation. The drains discharge to the Fuel Building sump in Room 6104. The sump is emptied by sump pumps. Refer to drawing series M-12LF for further information on the floor and equipment drain system. (Reference 3.1, Section F.12)
F.7.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
F.7.7      Analysis F.7.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
F.7.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an F-7 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Therefore, a fire within Fire Area F-7 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance
 
Wolf Creek Nuclear Operating Corporation                                            Page 238 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 209 of 250) that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in F-7.
 
Wolf Creek Nuclear Operating Corporation                                                Page 239 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 210 of 250)
Fire Area HMS-1 (Reference A-1802)
HMS.1.1    Fire Area Description Hot Machine Shop Rooms 1332, 1333, and 1334.
HMS.1.2    Major Equipment Decontamination equipment, laboratory equipment, and machine tools.
HMS.1.3    Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire door, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table HMS.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table HMS.1.3-1 Fire Area HMS-1, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Missile door 13331                                Fire Door Trench cover panels                              Fire Barrier The structural steel of the Hot Machine Shop is not structurally tied into the Auxiliary Building. The ceiling of this area is the building roof, and the building floor is on grade with the exception of the pipe chase communicating with Fire Area F-2. Consequently, only the building walls and the concrete trench cover plugs provide fire boundary protection.
HMS.1.4    Combustible Loading The cumulative combustible loading classification for Fire Area HMS-1 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 240 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 211 of 250)
HMS.1.5    Fire Protection An automatic smoke detection system is installed in this area. Manual-pull fire alarm stations are located near the exit doorways from this area. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
The combustible loading in the Hot Machine Shop is low. The Hot Machine Shop is not a safety-related area and is separated from adjacent safety-related areas by fire barrier construction. Therefore, an automatic sprinkler system is not provided for the Hot Machine Shop.
A hose station and portable extinguishers are provided within this Fire Area, as indicated on drawing A-1802.
Access to this area is through the exterior door in the west wall or through the interior doors at the north wall.
Adequate floor drains are provided in the area to remove hose station discharge without appreciable accumulation. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
HMS.1.6    Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Fire dampers will isolate HVAC openings in the fire barriers. Refer to Section 4.3.7.2 for smoke removal discussion.
HMS.1.7    Analysis HMS.1.7.1        Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using the hose station and/or portable extinguishers.
HMS.1.7.2        Safe Shutdown Capability This area contains no PFSSD equipment or circuits and is separated from adjoining Fire Areas by fire barrier construction. Therefore, a fire within Fire Area HMS-1 will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in HMS-1.
 
Wolf Creek Nuclear Operating Corporation                                                Page 241 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 212 of 250)
Fire Area RB (Reference A-1801 through A-1804)
RB.1      Fire Area Description Reactor Building (Containment).
RB.2      Major Equipment Reactor coolant pumps, steam generators, reactor, pressurizer, regenerative heat exchanger, reactor coolant drain tank and pumps, pressurizer relief tank, accumulator tanks excess letdown heat exchanger, cavity cooling fans, rod positioning indicator cabinets, incore instrumentation drive units, hydrogen recombiners, CRDM cooling fans, hydrogen mixing fans, dry waste compactor, polar crane, RCP lube oil drain tanks, containment coolers RB.3      Design Features This Fire Area is separated from all other Fire Areas by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table RB.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table RB.3-1 Fire Area RB, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Flanges for encapsulated valve                    Fire Barrier tanks Reactor Building personnel hatch                  Hatch Radiant energy shield fire wrap                  Fire Wrap Electrical penetrations                          Penetration Seal Mechanical penetrations                          Penetration Seal Fuel transfer tube penetration                    Penetration Seal
 
Wolf Creek Nuclear Operating Corporation                                                Page 242 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 213 of 250)
The 4-foot-thick Reactor Building walls serve as the fire barrier separation from adjacent buildings. There are no physical boundaries enclosing localized fire hazards within the Reactor Building. However, for purposes of this analysis, the Reactor Building is divided in the following zones as delineated on drawings A-1801 through A-1804.
Zone No.          Area RB-1              Area within the secondary shield wall RB-2              Area outside the secondary shield wall - El. 2000 RB-3              North electrical penetration area - El. 2026 RB-4              South electrical penetration area - El. 2026 RB-5              Cable tray area - El. 2047'-6" RB-6              Reactor building - El. 2068'-8" RB-7              West area - El. 2026 RB-8              East area - El. 2026 RB-9              Tendon access gallery area RB-10              Reactor building - El. 2047'-6" areas, except cable tray area RB-11              Area within primary shield wall RB.4      Combustible Loading The cumulative combustible loading classification for Fire Area RB is Low.
RB.5      Fire Protection Linear heat detection is installed above each reactor coolant pump and in areas where cable trays are concentrated. Duct smoke detection is provided for each containment cooler. Manual-pull fire alarm stations are located near hose stations. Detector or pull activation alarms locally and in the Control Room. The Control Room alarms are zoned for quick identification of the area in alarm. (Reference 3.1, Section F.1a))
Portable extinguishers and manual hose stations are permanently installed inside the Reactor Building as shown on drawings A-1801 through A-1804. The hose stations are spaced at no more than 100-foot intervals. The hose station locations are such that all accessible areas of the Reactor Building are adequately covered by at least one hose stream. A fire at any hose station may be extinguished by using an adjacent hose station. An extra length of hose can be added, if required, to the adjacent hose station.
(Reference 3.1, Section F.1b))
A fixed, manually charged, closed head sprinkler system is provided over the cable trays in Zones RB-3 and RB-4. A manual system is installed to prevent an inadvertent actuation of the sprinklers during normal plant operation. To protect the chloride sensitive piping and equipment from fire protection system leakage, the standpipes inside the Reactor Building are also normally dry. (Reference 3.1, Section F.1.a))
 
Wolf Creek Nuclear Operating Corporation                                                Page 243 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 214 of 250)
All fire water system piping within the Reactor Building is maintained dry by two normally closed isolation valves located in series on the same supply line. The motor operated isolation valve (KCHV0253) can be operated from the Control Room while the manual valve (KCV0427) can be manipulated locally in Room 1322. Opening both of these valves will charge fire water system piping within the Reactor Building, including the two sprinkler systems. All the isolation valves associated with the standpipe and sprinkler system are electrically supervised.
The fire protection supply piping to the Reactor Building is protected from the effects of a single active failure. The inside Containment isolation valve is a check valve which is highly reliable by design and considered exempt from active failures due to the lack of any external electrical signals which may be disabled due to a fire inside the containment.
Refer to USAR Section 3.1.1 for a discussion of the single failure criteria. Even though a fire inside the Containment would not disable the outside isolation valve, a random failure of the outside valve may be postulated with a fire inside the Containment. In this case, the accessibility of the outside isolation valve is not impaired, and the valve may be operated manually.
The Containment atmospheric control filter-adsorber units are provided with a thermistor-type continuous detector which alarms in the Control Room on high airstream temperature downstream of the charcoal bed. The charcoal beds are equipped with a hose connection to provide manual water spray protection.
A system is provided to collect and contain lubricating oil for each reactor coolant pump (RCP). The RCP oil spillage protection and control system consists of a package of splash guards, catch basins, and enclosure assemblies as attachments to the RCP motors at strategic locations to preclude the possibility of oil making contact with hot components and pipe. High pressure portions of the lube oil system are totally enclosed with low point drain connections. Low pressure portions of the system are provided with drip pans with low point connections. Remote lube oil fill lines for the upper and lower bearing reservoirs on each reactor coolant pump motor are not protected by drip pans.
Due to the design of the fill lines, no lube oil leakage is postulated. The RTD Conduit Boxes (3 per motor) are not provided with drip pans, however, conduit seals and leak tight fittings are used to minimize lube oil leakage. Oil leakage at the RDT Conduit Box does not represent a fire hazard. (Reference 3.1, Section F.1.a) and Reference 3.2, Section III.O)
Low points of the collection systems are piped to two collection tanks (each tank serves two RCPs) located in the Reactor Building as shown on Figure RB.5-1. Each of the two oil collection tanks has a capacity of 311 gallons (usable), compared to 265 gallons of oil in the lube oil system of each pump. It is unlikely that common failure would occur that would cause the entire inventory of oil in two RCP motors to leak out. The collection tanks are provided with level indication and high level alarm in the Control Room.
Therefore, the plant operators would have an early indication of a significant oil leak and could initiate corrective action. The tanks are manually drained as required. Should leakage exceed collection tank capacity before corrective actions are completed, the tank would overflow onto the Containment floor. Any such leakage would flow to the containment normal sumps via the drainage trenches located adjacent to the tanks (see drawing M-1G022). This oil would not come into contact with hot surfaces and create a fire hazard. (Reference 3.1, Section F.1.a) and Reference 3.2, Section III.O)
 
Wolf Creek Nuclear Operating Corporation                                                  Page 244 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 215 of 250)
The tanks are constructed to the requirements of ASME Section VIII and have flame arrestors on the vents. The drain piping is ANSI B31.1. The tanks and piping are seismically supported in accordance with the requirements of Paragraph C.2 of Regulatory Guide 1.29. Additionally, the oil collection tanks were sized to accommodate any reasonable amount of leakage that might result from an SSE. The oil collection devices mounted on the RCPs have been seismically analyzed and qualified in accordance with the requirements of Paragraph C.2 of Regulatory Guide 1.29.
(Reference 3.1, Section F.1.a) and Reference 3.2, Section III.O)
Refer to drawing M-12LF09 for a piping and instrument diagram of the RCP lube oil collection system. The location of cable trays in the vicinity of the reactor coolant pumps is identified in Figure RB.5-1. (Reference 3.1, Section F.1.a) and Reference 3.2, Section III.O)
Access to the Containment is via the personnel hatch at El. 2047 feet 6 inches. This hatch opens to Room 1507 of the Auxiliary building. For access to Room 1507, see Fire Area A-20. An emergency personnel hatch for evacuation purposes is located at El. 2013 feet 5 inches. The hatch opens to a stairway leading to the outside grade elevation. The tendon access gallery can be reached from a hatch at the outside grade at El. 2000 leading to the tendon gallery access shaft, and through door 21011 at El. 1974 of Fire Area A-1. Stairways and one elevator are located at Zone RB-2, as shown on drawing A-1802, and provide access to all elevations up to 2068 feet 8 inches.
Self-contained breathing apparatus are available for use inside Containment. They are stored near the entrance to the RCA. (Reference 3.1, Section F.1.b)
Adequate drainage capability exists in the Reactor Building to prevent the accumulation of fire-fighting water. Refer to drawing series M-12LE and M-12LF and for further information on the drain systems applicable to the Reactor Building.
RB.6      Isolation and Smoke Removal A fire within the reactor building will be contained by the fire barriers until extinguished.
Smoke may be removed by the containment purge system. Refer to Section 4.3.7.2 for smoke removal discussion.
RB.7      Analysis RB.7.1            Fire Suppression The automatic detection system, above the reactor coolant pumps, over areas where cable trays are concentrated and in the containment cooling system ducts, will alarm in the Control Room upon detection of a fire. The standpipes and sprinkler systems are manually charged by a combination of Control Room and local action to open the two normally closed isolation valves for Containment fire water supply. A fire in the cable trays at zones RB-3 or RB-4 would be suppressed by the respective sprinkler system. A fire can be extinguished manually, using the portable extinguishers and/or the hose stations.
 
Wolf Creek Nuclear Operating Corporation                                              Page 245 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 216 of 250)
The reactor coolant pumps are approximately 50 feet apart and a totally enclosed system to collect and contain the lube oil is provided for each pump. An oil fire is not postulated since this would require a failure in the pump lube oil system and another failure in the lube oil collection system in combination with the presence of an ignition source. Any major maintenance work on the pumps will require a plant shutdown. Therefore, an introduction of transient combustibles into this zone during normal plant operation is not postulated. The reactor coolant pumps are not required for a safe shutdown. For these reasons, an automatic suppression system is not provided to extinguish an oil fire in this zone.
The probability of a fire occurrence is greater during refueling and maintenance operations, when transient combustibles could be in the Reactor Building. However, the area would be occupied, and any potential fire would be quickly detected. Again, fire fighting could be performed manually using the hose stations and extinguishers shown on drawings A-1801 through 1804.
RB.7.2        Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an RB fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
Additionally, PFSSD manual actions for a fire in this area were evaluated as feasible within E-1F9900. Therefore, a fire within Fire Area RB will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in RB.
 
Wolf Creek Nuclear Operating Corporation                                Page 246 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 217 of 250)
Figure RB.5-1, RCP Cable Trays in Proximity to RCPs
 
Wolf Creek Nuclear Operating Corporation                                      Page 247 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 218 of 250)
Figure RB.5-1 (Contd), RCP Cable Trays in Proximity to RCPs
 
Wolf Creek Nuclear Operating Corporation                                              Page 248 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 219 of 250)
Fire Area RW (Reference A-1801 through A-1804, A-1347 through A-1350, and Z007A-M-0008)
Note:
The RW FHA encompasses the Fire Areas identified as RW A, RW B, and RW C in E-15000.
RW.1      Fire Area Description Entire Radwaste Building and Radwaste Storage Building - Rooms 7101, 7102, 7103, 7104, 7105, 7106, 7107, 7108, 7109, 7110, 7111, 7112, 7113, 7114, 7115, 7116, 7117, 7118, 7119, 7120, 7121, 7122, 7123, 7124, 7125, 7126, 7127, 7128, 7129, 7130, 7131, 7132, 7135, 7201, 7202, 7203, 7204, 7205, 7206, 7207, 7208, 7209, 7210, 7211, 7212, 7213, 7214, 7215, 7216, 7217, 7218, 7219, 7220, 7221, 7222, 7223, 7224, 7225, 7226, 7227, 7228, 7229, 7230, 7231, 7232, 7233, 7301, 7302, 7303, 7304, 73057401, 7402, 7403, 7404, 7405, 7406, 7407, 7408, 7409, 7410, 7411, 7413, 7501, 7502, 7503, and 7504.
RW.2      Major Equipment SG blowdown surge tank, SG blowdown surge pumps, aux steam condensate recovery tank, Aux steam condensate transfer pumps, gas decay tanks, catalytic hydrogen recombiner, waste gas compressors, floor drain tanks, floor drain pumps, waste hold-up tank, waste evaporator feed pump, thb04, chemical drain tank, chemical drain pump, waste evaporator condensate tank, waste evaporator condensate pump, waste monitor tank, waste monitor pump, re-cycle hold-up tanks, recycle evaporator feed pumps, primary waste evaporator bottoms tank, gas analyzer racks, oil water separator, radiation monitors, oil water separator pumps, load centers, motor control centers, solidification control cabinet, SLWS monitor tanks, spent resin storage tanks, control room control panels, hold-up tanks, evaporators, fan coil units, equipment hoist radwaste, Radwaste Building exhaust fans, Radwaste Building exhaust filter adsorber unit, SLWS monitor tanks.
RW.3      Design Features Fire Area RW to RW-1 is not separated by a physical fire barrier boundary. The south end of the Radwaste Tunnel at Column R1 has been established as a theoretical zone boundary between RW and RW-1 for analysis purpose only. For life safety purposes, fire barriers are provided for the stairwell enclosures within the Radwaste Building. The Radwaste Building is a concrete structure, while the Radwaste Storage Building is constructed of sheet metal siding over unprotected structural steel. The drum storage building is a combination of concrete and sheet metal construction. Although the majority of the barriers within the Radwaste Building are not credited as fire barriers, they do present a substantial impediment to fire propagation within the structure.
RW.4      Combustible Loading Calculation XX-X-004 does not maintain a combustible loading classification for Fire Area RW. The predominate combustible hazards associated with this area is that presented by Class A and B radwaste materials that a stored for ultimate processing or disposal.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 249 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 220 of 250)
RW.5      Fire Protection Automatic smoke detectors are installed in the area, except as noted in Attachment A.
Manual-pull fire alarm stations are located near exit doorways. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
An automatic wet pipe sprinkler system is provided for the Radwaste Storage Building and the Dry Waste Compactor area (Room 7228) of the Radwaste Building.
The charcoal filter adsorber unit is provided with a thermistor-type continuous detector which alarms in the Control Room at high airstream temperature. The adsorber unit is equipped with a hose connection to provide manual water spray protection.
Hose stations and fire extinguishers are strategically located throughout the area.
The area is accessible for firefighting from the exterior and the Radwaste Tunnel.
Floor drains that discharge to the Radwaste Building sump are provided for removal of firefighting water. Refer to drawing series M-12LF for further information on the floor and equipment drain system.
RW.6      Isolation and Smoke Removal A fire in this area is isolated from the Auxiliary Building by fire barrier construction. Refer to Section 4.3.7.2 for smoke removal discussion.
RW.7      Analysis RW.7.1            Fire Suppression A fire in the Radwaste Building will be detected and alarmed by the automatic detection system. A fire in the Radwaste Storage Building will be alarmed following sprinkler system water flow. Fire in the Radwaste Storage Building or Dry Waste Compactor area will be suppressed by the respective automatic sprinkler system. A fire can be extinguished manually, using hose stations and/or portable extinguishers in the event automatic suppression fails, or the fire is located in an area where automatic suppression is not provided.
A filter fire in the charcoal adsorber unit will be extinguished utilizing the manual spray system.
 
Wolf Creek Nuclear Operating Corporation                                              Page 250 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 221 of 250)
RW.7.2        Safe Shutdown Capability Four hand switches and associated cables are located in fire areas RW and RW-1 that are used to close the Steam Generator blowdown valves BMHV0001 through BMHV0004 in the case of a fire that renders the primary circuit incapable of controlling the valves. In the case of a fire in Fire Area RW or RW-1, the primary circuit will be available to control these valves. Therefore, a fire in this area will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in RW.
 
Wolf Creek Nuclear Operating Corporation                                                Page 251 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 222 of 250)
Fire Area RW-1 (Reference A-1801)
RW.1.1    Fire Area Description Radwaste Pipe Tunnel and Cable Chase to Auxiliary Building (below grade) Rooms 7133 and 7134.
RW.1.2    Major Equipment Electric cable.
RW.1.3    Design Features This Fire Area is separated from the Auxiliary Building by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table RW.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table RW.1.3-1 Fire Area RW-1, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017 The ceiling, floor, and east west side walls of this area are against soil. The fire area is divided into two rooms by a 2-foot-thick concrete wall. Room 7133 is the Nonradioactive Tunnel, while Room 7134 contains radioactive piping.
Ventilation air for the tunnel is provided by transferring air from the Radwaste and Auxiliary Buildings by means of transfer fans. The tunnel is exhausted by Radwaste and Auxiliary Building exhaust systems. More air is exhausted than supplied to prevent exfiltration from the tunnel. Air is supplied to the nonradioactive portion of the tunnel and exhausted from the radioactive side of the tunnel.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 252 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 223 of 250)
RW.1.4    Combustible Loading The cumulative combustible loading classification for Fire Area RW-1 is Low.
RW.1.5    Fire Protection An automatic smoke detection system is installed in Room 7133. Manual-pull fire alarm stations are located near the exit doorways from adjacent areas. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm. Detection is not installed in the Radioactive Pipe Tunnel (Room 7134) due to low installed combustibles.
Hose stations are not located inside the tunnel since a fire in the tunnel may render them inaccessible. Hose stations, located approximately 30 feet away from either end of the tunnel in the Auxiliary and Radwaste Buildings, are available for manual firefighting.
Each hose rack has 75 feet of hose, and the tunnel is approximately 140 feet along.
Therefore, all areas of the tunnel are within reach of these hose stations. Portable extinguishers are provided inside and outside of the tunnel. Refer to drawing A-1801 for hose stations and extinguisher locations.
The area is accessible for firefighting from both the north and south ends of the tunnel.
A 4 foot x 4 foot x 4 foot sump with two 50 gpm submersible pumps is located in the Nonradioactive Tunnel midway between the Auxiliary and Radwaste Buildings. The sump pumps discharge to the floor drain tank located in the Radwaste building. The Radioactive Pipe Tunnel has a 3 foot x 3 foot x 3 foot sump, which is connected to the Nonradioactive Tunnel sump by a 4-inch embedded pipe.
RW.1.6    Isolation and Smoke Removal A fire in this area is isolated from the Auxiliary Building by fire barrier construction. Fire dampers will isolate HVAC openings in the fire barrier communicating with the Auxiliary Building. Refer to Section 4.3.7.2 for smoke removal discussion.
RW.1.7    Analysis RW.1.7.1          Fire Suppression Due to the low installed combustibles in the Radioactive Pipe Tunnel and limited credible ignition sources, a fire in this area is not postulated.
A fire in the Nonradioactive Tunnel area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
 
Wolf Creek Nuclear Operating Corporation                                              Page 253 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 224 of 250)
RW.1.7.2      Safe Shutdown Capability Four hand switches and associated cables are located in fire areas RW and RW-1 that are used to close the Steam Generator blowdown valves BMHV0001 through BMHV0004 in the case of a fire that renders the primary circuit incapable of controlling the valves. In the case of a fire in Fire Area RW or RW-1, the primary circuit will be available to control these valves. Therefore, a fire in this area will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in RW-1.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 254 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 225 of 250)
Fire Area SBO (Reference M-1G074)
SBO.1      Fire Area Description Station Blackout (SBO) diesel generator missile shield structure. The concrete structure has four (4) bays. The North and South ends of the bays are open to atmosphere and enclosed with steel grating.
SBO.2      Major Equipment Three 3250 kW/4063 kVA diesel generator enclosures and one Power Equipment Center (PEC) enclosure. The PEC enclosure contains the switchgear (PB005) for the generator sets and power output to the plant.
SBO.3      Design Features This Fire Area is outside the protected area and is remote to the power block structures.
Due to the spatial separation, there is no exposure hazard to this Fire Area. The missile shield structure is constructed with non-combustible, fire resistive, materials. The structure is comprised of 1-foot thick concrete walls on the ends with 1-foot thick separation walls between the bays. The North and South sides of the building is enclosed with steel grating. The roof has removable concrete shield plugs that are 1-foot thick. The building is lightning protected per NFPA 780. The doors between the bays are 3-hour fire rated. The PEC has 2-hour fire rated walls between the switchgear room and the control room. The wall surrounding the battery room within the PEC is 2-hour fire rated. The diesel driven generator sets and PEC are each housed within an enclosure designed to withstand 150 mph winds. UL Listed double walled fuel tanks are provided with the generator sets. The fuel tanks are equipped with overfill protection. The PEC battery compartment is equipped with redundant hydrogen ventilation fans. The vent fan is started on detection of a 1% hydrogen concentration. An alarm is initiated on detection of a 2% hydrogen level.
SBO.4      Combustible Loading The cumulative combustible loading classification for Fire Area SBO is High. This area is not a safety related area nor is it adjacent to a safety related area so it is not included in Calculation XX-X-004, Combustible Fire Loading For Each Room In The Various Fire Areas At WCNOC. The following is included for information.
Each individual fuel oil tank for the SBO diesels has a nominal capacity of 6512 gallons.
The tank is a UL #142 listed double walled fuel tank. Each Diesel engine contains 104 gallons of lube oil. The PEC has 60 lead acid batteries (LSe450). The overall square footage of the fire area is 6500 sqft. Each individual bay has a square footage of 1625 sqft.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 255 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 226 of 250)
Room      Combustible              Heat Rate      Quantity    Room Area    Load (Btu/sqft)
Material              (Btu/lb)        (gal)      (sqft)
SBO-A      Diesel Fuel
* 20000          6187*      1625          523896 Lube Oil **              20000          104**      1625            9114 SBO-B      Diesel Fuel
* 20000          6187*      1625          523896 Lube Oil **              20000          104**      1625            9114 SBO-      Diesel Fuel
* 20000          6187*      1625          523896 C          Lube Oil **              20000          104**      1625            9114 SBO-E    Batteries Class A            18000          650 lbs      1625            7200 Misc Class A              18000        ~150 lbs      1625            1662
* Specific Gravity of Diesel Fuel - 0.86
          ** Specific Gravity of lube oil - 0.89 Fire      Combustible            Heat Rate      Quantity    Room Area    Load (Btu/sqft)
Area        Material              (Btu/lb)        (gal)      (sqft)
SBO        Diesel Fuel
* 20000          18561        6500          392922 Lube Oil **            20000            312        6500            6836 Misc Class A            18000          750 lbs      6500            2077 Total          401835
* Specific Gravity of Diesel Fuel - 0.86
          ** Specific Gravity of lube oil - 0.89 SBO.5      Fire Protection An automatic heat detection system is installed in the separate diesel enclosures in this fire area. Automatic smoke detection is installed in the PEC enclosure in this fire area.
Manual-pull stations are located at exit doors from the three Diesel Generator and PEC enclosures. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the WCNOC Control Room.
Attachment A summarizes the automatic detection and suppression coverage provided for this fire area. Specifically, automatic detection coverage is only provided within the three Diesel Generator and PEC enclosures.
Portable extinguishers are located within the three Diesel Generator and PEC enclosures.
Access to this area for manual firefighting is available from outside of the structure at ground level. A fire hydrant and hose house will be installed in the future adjacent to the structure.
The structure is open to the outside on the North and South side through steel grating on each of the four bays of the structure, which will facilitate drainage of firewater.
SBO.6      Isolation and Smoke Removal There are no mechanical smoke isolation or smoke removal features within the fire area.
The structure is open to the outside on the North and South side through steel grating on each of the four bays of the structure, which will facilitate smoke removal due to natural ventilation.
 
Wolf Creek Nuclear Operating Corporation                                              Page 256 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 227 of 250)
SBO.7      Analysis SBO.7.1      Fire Suppression The automatic detection system installed in the Diesel Generator and PEC enclosures will provide an early warning of a fire in this area. The fire can be extinguished manually, using hose lines and/or portable extinguishers.
Adequate drainage is provided to remove the fire suppression water discharge.
SBO.7.2      Safe Shutdown Capability There are no cables or components within the SBO fire area that are credited for Post Fire Safe Shutdown (PFSSD).
 
Wolf Creek Nuclear Operating Corporation                                                Page 257 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 228 of 250)
Fire Area T-1 (Reference A-1801 through A-1804, A-1806, A-1807, and A-1812 )
T.1.1      Fire Area Description Turbine Building Stairway Room 4101.
T.1.2      Major Equipment Electric cable.
T.1.3      Design Features This Fire Area is separated from the Auxiliary Building by fire barrier construction and penetration closure assemblies (fire doors and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table T.1.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table T.1.3-1 Fire Area T-1, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Missile door 41015                                Fire Door Missile door 41017                                Fire Door Remaining walls of the stairwell enclosure are 2-hour rated.
T.1.4      Combustible Loading The cumulative combustible loading classification for Fire Area T-1 is Low.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 258 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 229 of 250)
T.1.5      Fire Protection Automatic smoke detection is provided at the top of the stairwell. Manual-pull fire alarm stations are located just outside the doorway at each floor elevation. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are provided just outside this fire area at each floor elevation.
The area is accessible for fire fighting from each communicating elevation with the Auxiliary Building and Turbine Building.
No drains are provided for this Fire Area, as manual fire water suppression efforts will be minimal, considering the limited combustible loading and equipment in the Fire Area.
There are no PFSSD equipment or circuits in this area. There is no PFSSD equipment susceptible to water damage in this area. Therefore, water accumulation in the area would not affect safe shutdown capability.
T.1.6      Isolation and Smoke Removal The fire barriers will contain a fire within the Fire Area until extinguished. Refer to Section 4.3.7.2 for smoke removal discussion.
T.1.7      Analysis T.1.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The fire can be extinguished manually, using hose stations and/or portable extinguishers.
T.1.7.2          Safe Shutdown Capability One cable for the trip circuit for the main feedwater pump turbine runs through this Fire Area. This cable needs to function when the MSIV's are rendered incapable of closing due to a fire. For a fire in this area, the MSIV's will function normally. Therefore, a fire in any portion of Fire Area T-1 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                Page 259 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 230 of 250)
Fire Area T-2 (Reference A-1806 through A-0808)
T.2.1      Fire Area Description Turbine Building - 50 feet north of Auxiliary Building wall. Rooms 4301, 4302, 4303, 4304, 4305, 4306, 4322, 4351, 4401, 4501, and 4504.
T.2.2      Major Equipment Condenser vacuum pumps, air compressors feedwater heaters, turbine building supply air units, S.G. blowdown flash tank, S.G. blowdown non-regenerative heat exchanger, load centers and motor control centers.
T.2.3      Design Features This Fire Area is separated from the Auxiliary Building and Fire Areas T-4 and T-10 by fire barrier construction and penetration closure assemblies (fire doors, fire dampers, and penetration seals) that satisfy at least one of the following criteria:
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
Table T.2.3-1 identifies fire barrier features within the Fire Area that are unique or not directly bounded by fire endurance testing. These features are evaluated within M 663-00017A or an appropriate document referenced within M 663-00017A. These evaluations determined that each unique or unbounded fire barrier feature will prevent fire propagation from one Fire Area to another, and will not adversely impact PFSSD equipment or circuits within an adjacent Fire Area.
Table T.2.3-1 Fire Area T-2, Unique or Unbounded Fire Barrier Features M-663-00017A Closure Unique or Unbounded Feature Component Category Blowout panel                                    Hatch Emergency escape hatch                            Hatch Missile Shield                                    Fire Barrier 20 unsealed floor drains from A-23              Fire Barrier Penetration seals that exceed the bounding Penetration Seal limitations of M-663-00017
 
Wolf Creek Nuclear Operating Corporation                                              Page 260 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 231 of 250)
The Communication Corridor (Fire Area CC-1) is open to this area at El. 2000 and 2016, but separated from the adjacent Control Building by a fire boundary wall. The turbine lube oil area located approximately 38 feet north of the Auxiliary Building wall consists of two rooms (4308 and 4403), one above the other, which are both enclosed by fire barriers. Due to the fire boundaries for each of these rooms the areas are not considered part of Fire Area T-2. The FHA for Room 4308 is provided in Section T.4.1 (Fire Area T-4), while the FHA for 4403 (Fire Area T-10) is provided in Section T.10.1.
Fire Area T-2 to TURB is not separated by a physical boundary. The 50 point north of the Auxiliary Building wall has been established as a theoretical zone boundary between T-2 and TURB for fire hazard analysis purpose only.
A pipe trench extends from the Auxiliary Building wall to the Condenser Pit area. The trench is sloped away from the Auxiliary building.
T.2.4      Combustible Loading The cumulative combustible loading classification for Fire Area T-2 is Low.
T.2.5      Fire Protection The T-2 areas below the turbine operating floor (El. 2065) are protected by an automatic detection system, using rate compensated thermal detectors. The detection system alarms locally and in the Control Room and also charges the preaction sprinkler system in the area. The Control Room detection annunciation is zoned for quick identification of the specific area in alarm. Manual-pull fire alarm stations are located near the emergency exit doorways from this area. The pull stations alarm locally and in the Control Room.
Control Room annunciation of a pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Hose stations and portable extinguishers are provided throughout this area. Adjacent hose stations are separated by no more than 100 feet.
Automatic preaction sprinkler protection is provided for T-2 areas below the operating floor, El. 2065. Each of the two systems is charged by actuation of any one of the thermal detectors located in the area protected by that system.
The entire area is readily accessible through several interior and exterior doors and fire-rated stairways.
Adequate floor drains are provided in the Turbine Building area to remove sprinkler and hose station discharge without appreciable accumulation. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 261 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 232 of 250)
T.2.6      Isolation and Smoke Removal A fire in this area will be isolated from the Auxiliary Building and Fire Areas T-4 and T-10 by fire barrier construction. Fire dampers will isolate the HVAC ducts from the Auxiliary Building, and Fire Areas T-4 and T-10. The roof of the Turbine Building is fitted with spring loaded vents which are held closed by fusible links. In the event of a fire in the Turbine Building, these vents will open to relieve smoke and heat. The vents are sized to provide 1 square foot of vent area for each 100 square feet of floor area. Refer to Section 4.3.7.2 for additional smoke removal discussion.
T.2.7      Analysis T.2.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. The automatic suppression systems will discharge shortly after the automatic alarm signal occurs. In the event of failure of the automatic suppression system or a delay in discharge, the fire can be manually extinguished, using the portable extinguishers, manual hose stations, and/or the manual water spray systems, where provided.
Collapse of the Turbine Building roof or even a Turbine Building roof truss is not credible and is not postulated because of the fire protection provided, low fire loadings above the operating deck of the Turbine Building, and the construction of the roof which meets FM Class I UL Class A requirements. Even though the roof trusses will not collapse, it has been verified that a free-falling roof truss has less energy than tornado missiles considered in the design of safety-related buildings.
Fires on or above the operating deck within the T-2 area would be extinguished manually. The combustible loading above the operating floor is low and administrative controls limit the introduction and storage of transient combustibles on the operating floor. Fires starting on or above the operating floor will not damage the roof or roof trusses. The resultant heat and smoke will be vented through the roof vents.
Fire starting below the operating deck in an open area will be automatically detected and extinguished by an automatic preaction sprinkler system. Therefore, fires below the operating deck within the T-2 area will not damage the roof or the roof trusses. Failure of the automatic extinguishing system is alarmed in the Control Room.
T.2.7.2          Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by an T-2 fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary.
 
Wolf Creek Nuclear Operating Corporation                                              Page 262 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 233 of 250)
Therefore, a fire within Fire Area T-2 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                Page 263 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 234 of 250)
Fire Area T-4 (Reference A-1806)
T.4.1      Fire Area Description Turbine Building 2000, Lube Oil Storage Tanks Room 4308.
T.4.2      Major Equipment Main lube oil storage tanks, oily waste sumps, main lube oil conditioner, and main lube oil transfer pump.
T.4.3      Design Features This Fire Area is separated from other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, fire damper, and penetration seals) that satisfy at least one of the following criteria: (Reference 3.1, Section F.8)
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
The doorway of the room has an 8-inch curb to contain oil spillage in the room.
T.4.4      Combustible Loading Calculation XX-X-004 does not maintain a combustible loading classification for Fire Area T-4. The combustible hazard associated with this area is that presented by stored lubrication oil. The maximum capacity of each tank (TCF01A and TCF01B) is approximately 15,122 gallons.
T.4.5      Fire Protection An automatic infrared flame detector is installed in this Fire Area. Manual-pull stations are located at Turbine Building Exits. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
The area is protected by an automatic wet pipe sprinkler system. (Reference 3.1, Section F.8)
Hose stations and portable extinguishers are located outside the area to ensure accessibility. Refer to drawing A-1806 for specific hose station and fire extinguisher locations.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 264 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 235 of 250)
The area is accessible for fire fighting efforts via Turbine Building Room 4322.
An 8 curb and sump are provided within the area to contain and remove sprinkler and hose station discharge without appreciable accumulation. Refer to drawing series M-12LE for further information on the oily waste drain system.
T.4.6      Isolation and Smoke Removal A fire in this area will be isolated from adjacent safe shutdown areas of the plant by fire barriers. Fire dampers will isolate the HVAC ducts from the adjacent safe shutdown areas. Refer to Section 4.3.7.2 for smoke removal discussion.
T.4.7      Analysis T.4.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers and suppressed by the wet pipe system. Should the automatic suppression system fail, manual hose streams and extinguishers can be used to extinguish the fire.
T.4.7.2          Safe Shutdown Capability There are no PFSSD equipment or circuits in this area. Therefore fire damage to this area will not prevent safe shutdown.
 
Wolf Creek Nuclear Operating Corporation                                                Page 265 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 236 of 250)
Fire Area T-10 (Reference A-1807)
T.10.1    Fire Area Description Turbine Building 2033, Lube Oil Reservoir Room 4403.
T.10.2    Major Equipment Lube oil reservoir.
T.10.3    Design Features This Fire Area is separated from other Fire Areas by fire barrier construction and penetration closure assemblies (structural steel fireproofing, fire door, fire dampers, and penetration seals) that satisfy at least one of the following criteria: (Reference 3.1, Section F.8)
Are directly qualified by 3-hour fire endurance testing in accordance with criteria of the applicable controlling standard (ASTM E-119, ASTM E-152, UL-10B, UL-555, or IEEE-634) for the respective barrier assembly protective feature.
Have been evaluated as providing an equivalent level of protection.
Have been evaluated as providing protection commensurate with the fire hazards present.
T.10.4    Combustible Loading Calculation XX-X-004 does not maintain a combustible loading classification for Fire Area T-10. The combustible hazard associated with this area is that presented by lubrication oil within the main turbine lube oil tank (TCB01). The tank has a maximum capacity of approximately 12,450 gallons.
T.10.5    Fire Protection An automatic infrared flame detector is installed in this Fire Area. Manual-pull stations are located at Turbine Building Exits. Detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a detection or pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
The area is protected by an automatic wet pipe sprinkler system. (Reference 3.1, Section F.8)
Hose stations and portable extinguishers are located outside the area to ensure accessibility. Refer to drawing A-1807 for specific hose station and fire extinguisher locations.
The area is accessible for firefighting efforts via Turbine Building Room 4401.
 
Wolf Creek Nuclear Operating Corporation                                                    Page 266 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 237 of 250)
Floor drains are provided within the area to contain and remove sprinkler and hose station discharge without appreciable accumulation. The drains discharge to the oily waste sump located in Room 4308. Refer to drawing series M-12LE for further information on the oily waste drain system.
T.10.6    Isolation and Smoke Removal A fire in this area will be isolated from adjacent safe shutdown areas of the plant by fire barriers. Fire dampers will isolate the HVAC ducts from the adjacent safe shutdown areas. Refer to Section 4.3.7.2 for smoke removal discussion.
T.10.7    Analysis T.10.7.1          Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In the event that a fire develops, it will be contained by the fire barriers, with the exception of the potential fire communication path to Fire Area T-4 via the floor drain system. The automatic sprinkler system will suppress a fire in the area. Should the automatic suppression system fail, manual hose streams and extinguishers can be used to extinguish the fire.
As identified in Section T.10.5, floor drains in the area discharge to the oily waste sump located in Room 4308 (Fire Area T-4). This presents a potential combustible liquid communication path between the two Fire Areas. However, each Fire Area is protected from other Fire Areas by fire barrier construction and a wet pipe sprinkler system ensuring that a fire originating in T-10 and communicating to T-4 through the drainage system, would be maintained within the fire barrier confines of T-4.
Additionally, Fire Area T-4 does not contain any PFSSD equipment or circuits. Therefore, a fire involving both T-10 and T-4 will have the same overall impact on plant safe shutdown capability.
T.10.7.2          Safe Shutdown Capability One cable for the control of valve ABHV031 runs through this Fire Area.
This cable needs to function when the MSIV's are rendered incapable of closing due to a fire. For a fire in this area, the MSIV's will function normally. Therefore, a fire in any portion of Fire Area T-10 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                Page 267 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 238 of 250)
Fire Area TURB (Reference A-1806 through A-0808)
Note:
The TURB FHA encompasses Fire Zones T-3, T-5, T-6, T-7, T-8, and T-9 identified in AP 10-106, Fire Preplans.
TURB.1      Fire Area Description Entire Turbine Building north of Fire Area T-2. Rooms 4201, 4203, 4204, 4205, 4309, 4310, 4312, 4313, 4314, 4316, 4317, 4318, 4319, 4320, 4321, 4323, 4324, 4325, 4326, 4402, 4404, 4405, 4502, 4503, 4505, 4601, 4301E, 4301W, 4401E, 4401W, 4501E,4501W, OP-1, OP-2, and OP-7.
TURB.2      Major Equipment Condensate pumps, heater drain pumps, low, intermediate and high pressure condensers, steam generator feedwater pump lube oil pumps and conditioners, lube oil filter pump, process sample rack, condenser drain pump, auxiliary steam boiler blowdown flash tank, demineralized water transfer pump, low TDS transfer pumps, high TDS transfer pumps, SLW oil interceptor transfer pumps, SLW oil interceptor, oily waste sump pumps, miscellaneous condensate drain pump and tank, condensate demineralizer hot water tank, condensate demineralizer control panel, steam generator feedwater pump and turbine, acid day tank, caustic day tank, condensate demineralizers, high TDS tanks, high TDS collection pumps, hydrazine chemical addition skid, ammonia chemical addition skid, high pressure feedwater heaters, motor control centers, moister separator/reheater drain tank, reheater drain tank, 125 volt dc electrical busses, 125 volt batteries, 125 volt battery chargers, 13.8 kv electrical busses, 4.16 kv electrical busses, 480 volt load centers, isophase bus duct cooling system, exciter control panel, main generator relay panels \ main generator potential relay cabinets, waterbox vent tank, waterbox venting pumps, moister separator/reheater drain tank, reheater drain tanks, main turbine generator, alternator, intercept and control valves, and closed cooling water surge tank.
TURB.3      Design Features Fire Area TURB to T-2 is not separated by a physical fire barrier boundary. The 50 mark north of the Auxiliary Building wall has been established as a theoretical zone boundary between T-2 and TURB for analysis purpose only. Fire barriers are provided for Battery Rooms 4402 and 4404 for commercial property protection.
The Communication Corridor (Fire Area CC-1) is open to this area via T-2. However, CC-1 is separated from the adjacent Control Building by a fire boundary wall.
TURB.4      Combustible Loading Calculation XX-X-004 does not maintain a combustible loading classification for Fire Area TURB. The predominate combustible hazards associated with this area is that presented by lubrication oil and hydrogen within the main generator.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 268 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 239 of 250)
TURB.5    Fire Protection Battery Rooms 4402 and 4404 are protected by automatic smoke detectors. Remaining TURB areas below the turbine operating floor (El. 2065), with the exception of the Condenser Pit and Observation Posts are protected by an automatic detection system, using rate compensated thermal detectors. The detection system alarms locally and in the Control Room. Thermal detection activation and also charges the preaction sprinkler system in the area. The Control Room thermal detector alarm annunciation is zoned for quick identification of the specific area in alarm. Manual-pull fire alarm stations are located near the emergency exit doorways from this area. The pull stations alarm locally and in the Control Room. Control Room annunciation of a smoke detector and pull station alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
Automatic preaction sprinkler systems are provided to protect TURB areas below the turbine operating floor (excluding room enclosures and the Condenser Pit area). Each system is charged by actuation of any one of the thermal detectors located in the area protected by that system. Each floor elevation in the Turbine Building with the exception of 1983 and 2065 is protected by two independent sprinkler systems with each system serving approximately one-half of the floor area. A preaction sprinkler system, actuated by thermal detection, is also provided for the main turbine generator bearings The area under the condenser in the Condenser Pit is protected by an automatic wet pipe sprinkler system. The steam generator feedwater pump turbines are protected by a manually actuated water spray system. Detection is by thermal detectors which alarm locally and in the Control Room. A manual system is installed to prevent damage due to inadvertent operation. The hydrogen seal oil unit and is protected by an automatic water spray system actuated by thermal detectors, which alarm locally and in the Control Room.
An automatic wet pipe sprinkler system is provided for the Outage office and storage area located in the northwest corner of the turbine operating floor.
The entire area is readily accessible through several interior and exterior doors and fire-rated stairways.
Adequate floor drains are provided in the Turbine Building area to remove sprinkler and hose station discharge without appreciable accumulation. Refer to drawing series M-12LE for further information on the oily waste drain system.
TURB.6    Isolation and Smoke Removal A fire in this area will be isolated from the Auxiliary Building, Control Building, Fire Area T-4, and Fire Area T-10 by fire barriers. Fire dampers will isolate the HVAC ducts from the these areas. The roof of the Turbine Building is fitted with spring loaded vents which are held closed by fusible links. In the event of a fire in the Turbine Building, these vents will open to relieve smoke and heat. The vents are sized to provide 1 square foot of vent area for each 100 square feet of floor area. Refer to Section 4.3.7.2 for additional smoke removal discussion.
 
Wolf Creek Nuclear Operating Corporation                                              Page 269 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 240 of 250)
TURB.7    Analysis TURB.7.1      Fire Suppression A fire in this area will be detected and alarmed by the automatic detection system. In areas where preaction suppression systems are installed, the design is such that the system will discharge shortly after the automatic alarm signal occurs. The wet pipe sprinkler systems will automatically activate as sprinklers heads are opened by the fire. In the event of an automatic suppression system failure, complete extinguishment is not achieved by the automatic systems, or there is a delay in discharge, the fire can be manually extinguished, using the portable extinguishers, manual hose stations, and/or the manual water spray systems, where provided.
Collapse of the Turbine Building roof or even a Turbine Building roof truss is not credible and is not postulated because of the fire protection provided, low fire loadings above the operating deck of the Turbine Building, and the construction of the roof which meets FM Class I UL Class A requirements. Even though the roof trusses will not collapse, it has been verified that a free-falling roof truss has less energy than tornado missiles considered in the design of safety-related buildings.
A fire involving the Outage Office or storage area on the operating floor would be suppressed by the sprinkler system. All other fires on or above the operating deck would be extinguished manually. The combustible loading above the operating floor is low and administrative controls limit the introduction and storage of transient combustibles on the operating floor. Fires starting on or above the operating floor will not damage the roof or roof trusses. The resultant heat and smoke will be vented through the roof vents.
Fire starting below the operating deck in an open area will be automatically detected and suppressed by an automatic sprinkler system.
Should an automatic fire extinguishing system fail to operate or is not entirely successful, manual fire fighting could still be accomplished to extinguish the fire. The resultant heat and smoke would be vented through the roof vents. Therefore, fires below the operating deck will not damage the roof or the roof trusses. Failure of the automatic extinguishing system is alarmed in the Control Room.
TURB.7.2      Safe Shutdown Capability There are several components located in Fire Area TURB that are needed for a fire that renders the MSIVs incapable of closing. For a fire in this area, the MSIV's will function normally. Cables for several components that are needed for a fire that renders the MSIVs incapable of closing are located in Fire Area T-2 and CC-1. For a fire in these areas, the MSIV's will function normally.
 
Wolf Creek Nuclear Operating Corporation                                              Page 270 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 241 of 250)
The main turbine stop valves and steam bypass valves are located in Fire Area TURB. In addition to a fire that renders the MSIVs incapable of closing, these valves are needed in the case of a fire in the Control Room.
The procedure that governs the safe shutdown of the plant in the case of a fire in the Control Room assures that these valves will close.
Fire in this area and CC-1 can cause loss of off site power. However, redundant on-site power sources are available.
In summary, a fire in any portion of Fire Area TURB will not prevent safe shutdown of the plant, even in the unlikely event that fire propagation to T-2 and/or CC-1 occurs.
 
Wolf Creek Nuclear Operating Corporation                                              Page 271 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 242 of 250)
Fire Area CST & RWST (Reference A-1802)
CST/RWST.1      Fire Area Description Yard Areas around Condensate Storage Tank and Refueling Water Storage Tank (areas are identified as Fire Areas Y-01 and Y-02 in XX-X-004).
CST/RWST.2      Major Equipment Condensate Storage Tank, Refueling Water Storage Tank, Demineralized Water Tank, Reactor Makeup Water Tank, and Emergency Fuel Oil Storage Tanks.
CST/RWST.3      Design Features The water storage tanks are located in areas containing low combustible loading.
The walls of the two buildings adjacent to the Refueling Water Storage Tank are of concrete for the Fuel Building and metal siding for the Hot Machine Shop. The walls of the buildings adjacent to the Condensate Storage Tank are concrete for the Reactor Building and metal siding for the Auxiliary Boiler Room. Neither the below grade emergency fuel oil storage tanks or the diked heating oil storage tank present an exposure hazard to the CST or RWST.
CST/RWST.4      Combustible Loading The cumulative combustible loading classification for Fire Area CST/RWST is Low.
CST/RWST.5      Fire Protection Yard hydrants and hose houses are located throughout the Power Block area.
CST/RWST.6      Isolation and Smoke Removal Smoke will be removed by natural means for these outdoor structures.
CST/RWST.7      Analysis CST/RWST.7.1          Fire Suppression Manual fire suppression equipment is available to extinguish a fire in this area.
 
Wolf Creek Nuclear Operating Corporation                                            Page 272 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 243 of 250)
CST/RWST.7.2      Safe Shutdown Capability As applicable, XX-E-013 identifies electrical PFSSD equipment located within the Fire Area, while E-15000 identifies PFSSD circuits. The detailed PFSSD analysis for the Fire Area is provided in E-1F9910. The analysis demonstrates that a success path of PFSSD equipment, unaffected by a CST/RWST fire, remains available for achieving and maintaining hot standby and ultimately, transition to cold shutdown, if necessary. Therefore, a fire within Fire Area CST/RWST will not prevent safe shutdown of the plant. This, coupled with the defense in depth fire protection features and administrative controls for the Fire Area, provides reasonable assurance that 10 CFR Part 20 radiation limits will not be exceeded due to a fire in CST/RWST.
 
Wolf Creek Nuclear Operating Corporation                                                Page 273 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 244 of 250)
Fire Area YARD-ESF (Reference E-0F0221)
Note:
Fire Area YARD-ESF is identified as YARD1 in E-15000.
YARD-ESF.1      Fire Area Description ESF Transformers XNB01, XNB02, and surrounding yard area YARD-ESF.2      Major Equipment ESF Transformers XNB01 and XNB02.
YARD-ESF.3      Design Features The two ESF Transformers are located outdoors west of the Turbine Building and north of the Communications Corridor. The units set approximately 9-6 apart with an 13-3 tall by 20-8 long by 12 thick concrete barrier provided between the 11 transformers for fire exposure protection. Overhead cable raceways exiting the transformers into the Communications Corridor are separated by a horizontal distance of approximately 20 ft.
Due to spatial separation, the Communications Corridor, Turbine Building, and Station Service Transformers, do not present an exposure hazard to XNB01 or XNB02.
YARD-ESF.4      Combustible Loading The predominate combustible material is the transformer oil (approximately 2,170 gallons for XNB01 and approximately 4,205 gallons for XNB02). The oil is a Class        11 IIIB combustible liquid.
YARD-ESF.5      Fire Protection Each transformer is provided with automatic thermal detectors that upon activation will trip the open spray head deluge sprinkler system protecting the corresponding unit. The system may also be manually actuated by an electrical manual pull station in the area or by activation of a pneumatic manual release station on the deluge system riser. Detector or pull station activation will annunciate locally and in the Control Room. The Control Room annunciation of a detection or release station alarm is zoned for a quick and easy means to identify the location associated with the device in alarm.
Hydrants and hose hoses are accessible in the area for manual firefighting efforts.
The transformers area accessible from the yard area of the Power Block for firefighting efforts.
 
Wolf Creek Nuclear Operating Corporation                                                Page 274 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 245 of 250)
A curbed gravel pit is located beneath the transformers. The pit is sized to contain the oil from a transformer as well as water from both ESF transformer deluge sprinkler systems operating for approximately 10 minutes. Drainage is provided by a manual valve controlled 6 drain that discharges to the Turbine Building drainage system. Refer to drawing series M-12LE for further information on the oily waste drain system.
YARD-ESF.6      Isolation and Smoke Removal The concrete barrier between the two transformers provides exposure protection from a fire originating in either transformer. Smoke will be removed by natural means for the outdoor transformers.
YARD-ESF.7      Analysis YARD-ESF.7.1          Fire Suppression A fire in either transformer unit would be detected by the automatic heat detectors, which would automatically actuate the open head spray deluge system to suppress the fire. In the event that the deluge system does not extinguish the fire or the system fails to operate, the fire can be extinguished manually by utilizing an area fire hydrant.
YARD-ESF.7.2          Safe Shutdown Capability The ESF transformers have been included as PFSSD equipment because they are the normal power supplies to the emergency busses. An analysis has been performed that shows the areas where these transformers can be lost and is included in calculation XX-E-013. In all areas where fire can cause the loss of these transformers, the emergency diesel generators will be available. Therefore, a fire in that causes the loss of ESF transformers XNB01 and XNB02 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                Page 275 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 246 of 250)
Fire Area YARD-SU (Reference E-0F0221)
Note:
Fire Area YARD-SU is identified as YARD3 in E-15000.
YARD-SU.1        Fire Area Description Startup Transformers XMR01 and surrounding yard area.
YARD-SU.2        Major Equipment Startup Transformer XMR01.
YARD-SU.3        Design Features The Startup Transformer is located outdoors west of the Turbine Building.
Overhead cable raceways exiting the transformers into the Communications Due to spatial separation, the Turbine Building and Station Service Transformers, do not present an exposure hazard to XMR01.
YARD-SU.4        Combustible Loading The predominate combustible material is the transformer oil (approximately 10,850 gallons). The oil is a Class IIIB combustible liquid.
YARD-SU.5        Fire Protection The transformer is provided with cross zoned automatic thermal detectors.
Detection by either zone will alarm locally and in the Control Room. Activation by both zones will trip the open spray head deluge sprinkler system protecting the transformer. A deluge system trip signal also deenergizes XMR01. Activation of the electrical manual pull station in the area results in an single zone only alarm. It will not trip the deluge system. Manual deluge system actuation may be accomplished by activation of the pneumatic manual release station on the deluge system riser or key activated switch at the control panel. The Control Room annunciation of a detection or manual pull station alarm is zoned for a quick and easy means to identify the location associated with the device in alarm.
Hydrants and hose hoses are accessible in the area for manual firefighting efforts.
The transformer area accessible from the yard area of the Power Block for firefighting efforts.
A curbed gravel pit is located beneath the transformer. The pit is sized to contain the oil from the transformer as well as water from the deluge sprinkler system operating for approximately 10 minutes. Drainage is provided by a manual valve controlled 6 drain that discharges to the Turbine Building drainage system. Refer to drawing series M-12LE for further information on the oily waste drain system.
 
Wolf Creek Nuclear Operating Corporation                                              Page 276 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 247 of 250)
YARD-SU.6        Isolation and Smoke Removal Smoke will be removed by natural means for the outdoor transformer.
YARD-SU.7        Analysis YARD-SU.7.1        Fire Suppression A fire in the transformer unit would be detected by the automatic heat detectors, which would automatically actuate the open head spray deluge system to suppress the fire. In the event that the deluge system does not extinguish the fire or the system fails to operate, the fire can be extinguished manually by utilizing an area fire hydrant.
YARD-SU.7.2        Safe Shutdown Capability The startup transformer XMR01 is required to provide power to equipment in the Turbine Building that is needed when a fire renders the MSIVs incapable of closing. Any fire that can cause the loss of the startup transformer will not cause the MSIVs to be incapable of closing. Therefore, a fire in that causes the loss of startup transformer XMR01 will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                                Page 277 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 248 of 250)
Fire Area ESWC (Reference A-1324 through A-1327)
ESWC.1    Fire Area Description ESW Vertical Loop Chase, West of Control Building, Elevations 1974 to 2087-2, Room 8000.
ESWC.2    Major Equipment A and B train essential service water (ESW) piping and vacuum breakers.
ESWC.3    Design Features The ESW Vertical Loop Chase is a Seismic Category I structure that is attached to the west exterior wall of the Control Building. The exterior walls of the Chase below grade are concrete. Above grade, the walls are 1/2 thick steel plate with the exception of the east wall, which is the Control Building concrete wall at column line CF. The approximate area footprint of the Chase is 23 x 13. The Chase extends from 1974 to the top of the Control Building (2087-2). Access/egress is provided by an exterior door at 2000 (grade) and a personnel hatch on the Chase roof.
This fire area is separated from all other fire Areas by 3-hour rated fire barrier construction and penetration closure assemblies. No structural steel fireproofing is provided for the Chase due to low combustible loading. An additional consideration for not providing fireproofing was thermal expansion/contraction of the steel enclosure, from seasonal temperature changes, which would challenge fireproofing bond integrity. The exterior walls of the Chase are not fire rated, as there are no significant exterior fire exposure hazards in close proximity to the Chase.
ESWC.4    Combustible Loading The cumulative combustible loading classification for Fire Area ESWC is Low, with minimal fixed combustibles and no combustible continuity. As an added defense in depth feature, the fire area is maintained as a Combustible Control Zone. This administrative control requires that transient combustibles be constantly attended, or a transient combustible materials (TCM) permit is required. The TCM will specify required compensatory measures commensurate with the hazard presented by the transient combustible material package.
 
Wolf Creek Nuclear Operating Corporation                                                  Page 278 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 249 of 250)
ESWC.5    Fire Protection Area smoke detection is provided for the Chase. A manual-pull fire alarm station is located at each exit. Smoke detector or pull station activation results in local fire alarm notification appliance operation and annunciation within the Control Room. The Control Room annunciation of a fire alarm is point addressable for a quick and easy means to identify the location associated with the device in alarm.
A dry standpipe connection is provided south of the Chase at grade level. The standpipe feeds open head spray nozzles located below the Chase roof. Fire water is provided to the system by connecting the standpipe to an area fire hydrant with fire hose located in the hydrant hose house. The nozzles provide water spray protection for the Chase footprint, including the structural steel vertical columns.
Manual fire water suppression capability also includes hose stream application via area fire hydrants that are provided with fire hose and nozzle stored within the fire hydrant hose house.
Portable fire extinguishers are provided within the Chase for incipient fire response.
Drainage for the Chase is by a sump located on the 1974 elevation. Fire water discharge into the chase will not impact safe shutdown capability, as there are no electrical safe shutdown components within the Chase.
ESWC.6    Isolation and Smoke Removal The fire barrier separating the Chase from the Control Building will prevent fire propagation to a communicating fire area. No ventilation ductwork penetrates the fire barrier separating the Chase from the Control Building. Louvered vents are provided in the exterior walls of the chase to provide natural ventilation.
Refer to Section 4.3.7.2 for smoke removal discussion.
ESWC.7    Analysis ESWC.7.1        Fire Suppression In the event that a fire occurs within the Chase, it will be detected by area smoke detection. Fire severity will be low considering the limited amount of fixed combustibles and the administratively controlled transient combustibles within the Chase. Fire suppression will be via portable fire extinguishers, manual operation of the water spray system, or hose stream from an area yard fire hydrant. This protection approach
 
Wolf Creek Nuclear Operating Corporation                                              Page 279 of 281 Fire Hazard Analysis ATTACHMENT B FIRE HAZARD ANALYSIS (Page 250 of 250) ensures that Chase structural integrity will not be challenged by an ESW Vertical Loop Chase fire.
ESWC.7.2      Safe Shutdown Capability As previously identified, there is no electrical safe shutdown equipment within the fire area. Protection of the Chase and vertical structural steel with the manual water spray system ensures that the building structure will not impact the performance of the ESW piping internal to the Chase. Per the section 3.2.1.2 assumption from NEI 00-01, Guidance for Post-Fire Safe Shutdown Circuit Analysis, (Rev. 2), exposure fire damage to manual valves and piping does not adversely impact their ability to perform their pressure boundary or safe shutdown function. Therefore, a fire within ESWC will not prevent safe shutdown of the plant.
 
Wolf Creek Nuclear Operating Corporation                                  Page 280 of 281 Fire Hazard Analysis ATTACHMENT C NON-SAFETY RELATED SITE STRUCTURES (Page 1 of 2)
Nearest Structure Containing PFSSD Approximate Structures & Equipment Equipment/Circuits                Distance (ft) 345 KV Switchyard and 69 KVA          Turbine Building                  1155 Substation Concentrate Acid Storage Tank Area    ESW Mechanical Vault              675 Unit Aux. Transformer XMA02          Turbine Building                  20 Main Phase A Transformer XMA01A      Turbine Building                  62 Main Phase B Transformer XMA01B      Turbine Building                  62 Main Phase C Transformer XMA01B      Turbine Building                  62 Spare Transformer                    Turbine Building                  62 Station Service Transformer XPB03    Turbine Building                  63 Station Service Transformer XPB04    Turbine Building                  63 Admin. Services Shop                  ESW Mechanical Vault              354 Cable Reel Shop                      Start-Up Transformer XMR01        744 Walter P. Chrysler Support Complex    Turbine Building                  112 Charles Curtis Development Center    ESW Mechanical Vault              477 Circulating Water Screen House        ESW Pump House                    849 Dosimetry Building                    Start-Up Transformer XMR01        58 Dimineralized Water Storage          CST & Valve House                  21 Dwight D. Eisenhower Learning Center  Turbine Building                  14070 (Emergency Operations Center)
Ron Evans Outage Processing Center    Turbine Building                  1041 Fire Training Building                ESW Pumphouse                      645 Clyde Cessna Administration Building  CST                                277 High Ammonia Chemistry Building      Turbine Building                  504 Hazardous Waste Storage              Radwaste Storage Building          507 Hydrogen Storage                      Turbine Building                  747 Kelly Building #7                    Start-Up Transformer XMR01        1080 Edward P. Macabe Support Building    Turbine Building                  448 NDE/Civil Test Center                ESW Mechanical Vault              234 North Storage Building                Turbine Building                  1245 Olive Ann Beech - Ops Admin. Building CST                                128 Arthur Capper OJT Center              ESW Mechanical Vault              531 Outage Support Building              Start-Up Transformer XMR01        52 Owens Corning Warehouse              Radwaste Building                  513 Nitrogen / Oxygen Storage            Diesel Generator Building          255 Pump House Northeast                  ESW Pumphouse                      1506 Paint Shop                            Radwaste Building                  945 Paint Storage                        Radwaste Building                  1092 Pole Barns East, Middle, & West      Start-Up Transformer XMR01        1348 Charles Evans Whittaker Security      Reactor Building                  192 Building Security Diesel Generator Building    Fuel Building                      197 Secondary Access                      Turbine Building                  1290 Badge Check Point to Owner            Turbine Building                  2994 Controlled Area Vehicle Inspection Building          Turbine Building                  2970 William Allen White Skills Training  Turbine Building                  909 Center Technical Support Center              Turbine Building                  183 Vehicle Maintenance Shop              ESW Mechanical Vault              513 Amelia Earhart Warehouse              ESW Pumphouse                      882
 
Wolf Creek Nuclear Operating Corporation                                Page 281 of 281 Fire Hazard Analysis ATTACHMENT C NON-SAFETY RELATED SITE STRUCTURES (Page 2 of 2)
Nearest Structure Containing PFSSD Approximate Structures & Equipment Equipment/Circuits                Distance (ft)
Amelia Earhart Warehouse (West)    Control Building                  822 Waste Oil Storage                  Radwaste Building                  216 Heating Oil Pumphouse and Storage  Radwaste Building                  417 Tank Area Sewage Lagoon                      Turbine Building                  3444 Circ. Water Discharge              Start-Up Transformer XMR01        984 Waste Water Treatment              Turbine Building                  885 SBO Diesel Generator Structure      Control Building                  240
                                              -END-}}

Latest revision as of 23:44, 17 November 2024

E-1F9905, Revision 11, Fire Hazard Analysis