{{#Wiki_filter:.r consumers Energy A CMS Energy Company February 23, 1998 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 DOCKET 50-255 -LICENSE DPR-20 -PALISADES PLANT Tlloma* t:. Bordhw Manager Licensing SUPPLEMENTAL INFORMATION  
{{#Wiki_filter:consumers Energy
-GENERIC LETTER 95-07, "PRESSURE LOCKING AND THERMAL BINDING OF SAFETY-RELATED POWER-OPERATED GATE VALVES" This letter provides the supplemental information requested by the NRC to support the Palisades Safety Evaluation Report for NRC Generic Letter (GL) 95-07, "Pressure*
.r A CMS Energy Company                                                                                     Tlloma* t:. Bordhw Manager Licensing February 23, 1998 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT SUPPLEMENTAL INFORMATION - GENERIC LETTER 95-07, "PRESSURE LOCKING AND THERMAL BINDING OF SAFETY-RELATED POWER-OPERATED GATE VALVES" This letter provides the supplemental information requested by the NRC to support the Palisades Safety Evaluation Report for NRC Generic Letter (GL) 95-07, "Pressure*
Locking and Thermal Binding of Power-Operated Gate Valves." Two attachments provide the necessary information.
Locking and Thermal Binding of Power-Operated Gate Valves."
Attachment 1 is a table which summarizes the safety function and the pressure locking and thermal binding susceptibility bases for each of the valves covered in the 180-day response to GL 95-07, dated February 13, 1996. The table also provides the corrective actions that have been or will be taken to address the pressure locking or thermal binding concerns.
Two attachments provide the necessary information. Attachment 1 is a table which summarizes the safety function and the pressure locking and thermal binding susceptibility bases for each of the valves covered in the 180-day response to GL 95-07, dated February 13, 1996. The table also provides the corrective actions that have been or will be taken to address the pressure locking or thermal binding concerns. This table lists valves in the same order as presented to the NRC in the 180-day submittal.
This table lists valves in the same order as presented to the NRC in the 180-day submittal.
Attachment 2 addresses power-operated gate valves that were susceptible to pressure locking and for which analytical models were used to determine the unseating forces.
Attachment 2 addresses power-operated gate valves that were susceptible to pressure locking and for which analytical models were used to determine the unseating forces. This attachment provides the necessary information to quantify the margins available to overcome pressure_locking _ I/ ( . .* 9803040016 900223 L PDR ADOCK 05000255 P PDR :'. * ----------
This attachment provides the necessary information to quantify the margins available to overcome pressure_locking                         -~-- _                                                                                       ~                  I/
------------------J 1111111111111111111111111111111111111111 i Palisades Nuclear Plant
( .   .* 9803040016 900223                           ~.
L         PDR P
    ---------- --- --
ADOCK 05000255
                          -- -   --- -- -     -- -PDR :'. *
                                                        -                       J                                           1111111111111111111111111111111111111111 i Palisades Nuclear Plant
* 27780 Blue Star Memorial Highway
* 27780 Blue Star Memorial Highway
* CovtJi/, Ml 49043
* CovtJi/, Ml 49043
* Tel: 616 764 2913
* Tel: 616 764 2913
* Fax: 616 764 2490
* Fax: 616 764 2490
-. -
 
2
                      - . -


==SUMMARY==
==SUMMARY==
OF COMMITMENTS This letter contains no new commitments and no revisions to existing commitments. Thomas C. Berdine Manager, Licensing CC Administrator, Region Ill, USNRC Project Manager, NRR, USNRC NRC Resident Inspector  
OF COMMITMENTS This letter contains no new commitments and no revisions to existing commitments.
-Palisades 2 Attachments 2
~~
CONSUMERS ENERGY COMPANY To the best of my knowledge, the contents of this supplemental information supporting GL 95-07 response, are truthful and complete. Thomas C. Sardine Manager, Licensing Sworn and subscribed to before me this cJ 3-' day of 1998.
Thomas C. Berdine Manager, Licensing CC     Administrator, Region Ill, USNRC Project Manager, NRR, USNRC NRC Resident Inspector - Palisades 2 Attachments
Alora M. Davis, Notary Public Berrien County, Michigan (Acting in Buren County, Michigan)
 
My commission expires August 26, 1999 t ATTACHMENT 1 CONSUMERSENERGYCOMPANY PALISADES PLANT DOCKET 50-255 SUPPLEMENTAL INFORMATION  
CONSUMERS ENERGY COMPANY To the best of my knowledge, the contents of this supplemental information supporting GL 95-07 response, are truthful and complete.
-GENERIC LETTER 95-07 "PRESSURE LOCKING AND THERMAL BINDING OF SAFETY-RELATED POWER-OPERA TED GATE VALVES" TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PLTB SUSCEPTIBILITY 7 Pages ATTACHMENT 1 TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Descr!ption Susceptible Pressure Locking Thermal Binding to PL or TB J ustifi ca ti on/ Ac ti on Justification/Action
~~~  Thomas C. Sardine Manager, Licensing Sworn and subscribed to before me this cJ 3-' day of ~              1998.
: CV-0521 Alternate Steam Supply to AFW N/A Valve was removed from the plant in Valve was removed from the plant in Pump P-8B 1996 as part of modification FC-966. 1996 as part of modification FC-966. M0-1042A PORV Block Valve PL& TB Drilled hole in upstream disc. Converting from torque seating to limit e Completed 12/96 seating in 98 REFOUT. M0-1043A PORV Block Valve PL& TB Drilled hole in upstream disc. Converting from torque seating to limit , Completed 12/96 seating in 98 REFOUT. CV-3055 Shutdown Cooling Inlet to N/A Excluded from scope of NRC GL 95-Excluded from scope of NRC GL 95-Shutdown Cooling Heat 07 based on Palisades being a Hot 07 based on Palisades being a Hot Exchanger Shutdown Plant. Shutdown Plant. CV-3070 HPSI $ub Cooling Valve PL& TB Bonnet vent path to upstream side of Valve lff of 32° Fis below.the valve will be installed prior to threshold for thermal binding of conclusion of 98REFOUT.
t
double disc gate valves. CV-3071 HPSI Sub Cooling Valve PL& TB Bonnet vent path to upstream side of Valve 6. T of 32° F is below the valve will be installed prior to threshold for thermal binding of conclusion of 98REFOUT.
~'VY\-~~
double disc gate valves. CV-3027 SIRW Tank Recirculation N/A Valve is normally open and only has Valve is normally open and only has to close to perform its safety function.
Alora M. Davis, Notary Public Berrien County, Michigan (Acting in V~n Buren County, Michigan)
to close to perform its safety function.
My commission expires August 26, 1999
It does not have to reopen. It does not have to reopen. CV-3031 SIRW Tank Outlet N/A Valve is normally open and only has Valve is normally open and only has to close to perform its safety function.-
 
to close to perform its safety function.
ATTACHMENT 1 CONSUMERSENERGYCOMPANY PALISADES PLANT DOCKET 50-255 SUPPLEMENTAL INFORMATION - GENERIC LETTER 95-07 "PRESSURE LOCKING AND THERMAL BINDING OF SAFETY-RELATED POWER-OPERATED GATE VALVES" TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PLTB SUSCEPTIBILITY 7 Pages
It does not have to reopen. It does not have to reopen. CV-3056 SIRW Tank Recirculation N/A Valve is normally open and only has Valve is normally open and only has to close to perform its safety function.
 
to close to perform its safety function.
ATTACHMENT 1 TABLE- VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Descr!ption                     Susceptible Pressure Locking                         Thermal Binding to PL or TB J ustifi ca ti on/Ac ti on               Justification/Action
It does not have to reopen. It does not have to reopen. -1 ATTACHMENT 1 TABLE-VAL VE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding I to PL or TB Justification/Action Justification/Action CV-3057 SIRW Tank Outlet N/A Valve is normally open and only has Valve is normally open and only has Jo close to perform its safety function.
:
to close to perform its safety function.
CV-0521   Alternate Steam Supply to AFW   N/A         Valve was removed from the plant in       Valve was removed from the plant in Pump P-8B                                   1996 as part of modification FC-966.     1996 as part of modification FC-966.
It does not have to reopen. It does not have to reopen. CV-0704 Slowdown Tank Discharge to N/A Valve has no active safety function to Valve has no active safety function to e Condensate Discharge reposition.
M0-1042A PORV Block Valve               PL& TB     Drilled hole in upstream disc.
reposition.
Completed 12/96 Converting from torque seating to limit seating in 98 REFOUT.                   e M0-1043A PORV Block Valve               PL& TB     Drilled hole in upstream disc.           Converting from torque seating to limit
-CV-0733 Hotwell 12" Makeup Valve N/A Valve has no active safety function to Valve has no active safety function to reposition.
                                        ,             Completed 12/96                           seating in 98 REFOUT.
reposition.
CV-3055   Shutdown Cooling Inlet to       N/A         Excluded from scope of NRC GL 95-         Excluded from scope of NRC GL 95-Shutdown Cooling Heat                       07 based on Palisades being a Hot         07 based on Palisades being a Hot Exchanger                                   Shutdown Plant.                           Shutdown Plant.
M0-0501 MSIV Bypass Valve N/A Valve has no safety function to Valve has no active safety function to ' open. open. M0-0510 MSIV'Bypass Valve N/A Valve has rio active safety function to Valve has no active safety function to open. open. CV-3212 Shutdown Cooling Hx Inlet N/A Valve is normally open and has no Valve is normally open and has no Valve active safety function to open. active safety function to open.
CV-3070   HPSI $ub Cooling Valve         PL& TB     Bonnet vent path to upstream side of     Valve lff of 32° Fis below.the valve will be installed prior to         threshold for thermal binding of conclusion of 98REFOUT.                   double disc gate valves.
Shutdown Cooling Hx Outlet N/A Valve is normally open and has no Valve is normally open and has no Valve active safety function to open. active safety function to open. CV-3223 Shutdown Cooling Hx Inlet N/A Valve is normally open and has no Valve is normally open and has no Valve active safety function to open. active safety function to open. CV-3224 Shutdown Cooling Hx Outlet N/A Valve is normally open and has no Valve is normally open and has no Valve* active safety function to open. active safety function to open. M0-0798 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in,place and valve. Valve retired in place and locked open. locked open.
CV-3071   HPSI Sub Cooling Valve         PL& TB     Bonnet vent path to upstream side of     Valve 6.T of 32° F is below the valve will be installed prior to         threshold for thermal binding of conclusion of 98REFOUT.                   double disc gate valves.
ATTACHMENT 1 TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding to PL or TB Justification/Action Justification/Action M0-3041 Safety Injection Tank T-82A N/A Valve is normally open and has no Valve is normally open and has no Outlet Isolation active safety function to reopen if active safety function to reopen if closed. closed. M0-3045 Safety Injection Tank T-828 N/A Valve is normally open and*has no Valve is normally open and has no Outlet Isolation active safety function to reopen if active safety function to reopen if closed. closed. M0-3049 Safety Injection Tank T-82C N/A Valve is normally open and has no Valve is normally open and has no Outlet Isolation active safety function to reopen if active safety function to reopen if I closed. closed. M0-3052 Safety Injection Tank T-820 N/A Valve is normally open and has no Valve is normally open and has no Outlet Isolation active safety function to reopen if active safety function to reopen if closed. closed. CV-3036 HPSI Pump P-66A to HPSI N/A Valve is normally open and has no Valve is normally open and has no Train 2 Isolation active safety function to open. active safety function to open. CV-3037 HPSI Pump P-66A to HPSI NIA Valve is normally closed and has no Valve is normally closed and has no Train 1 Isolation active safety function to.open.
CV-3027   SIRW Tank Recirculation         N/A         Valve is normally open and only has       Valve is normally open and only has to close to perform its safety function. to close to perform its safety function.
active safety function to open. CV-3059 HPSI Pump P-668 to HPSI N/A Valve is normally open and has no Valve is normally open and has no Train 1 Isolation.
It does not have to reopen.               It does not have to reopen.
active safety function to open. active safety function to open. M0-0743 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve retired in place and locked open. locked open. M0-0748 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve retired in place and locked open. locked open. 3 ATTACHMENT 1 TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding ; to PL or TB Justification/Action Justification/
CV-3031   SIRW Tank Outlet               N/A         Valve is normally open and only has       Valve is normally open and only has to close to perform its safety function.- to close to perform its safety function.
Action ' M0-0753 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve retired in place and locked open. locked open. M0-0754 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve retired in place and locked open. locked open. M0-0755 Aux Fe'edwater Isolation Valve N/A -SC 95-041 disc!onnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and. valve. Valve retired in place and locked open. locked open. M0-0759 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve retired in place and locked open. locked open. M0-0760 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve *retired in place and locked open. locked open. M0-3080 HPSI Hot Leg Injection Mode N/A Valve is normally open and has no Valve is normally open and has no Select active safety function to reopen after it active safety function'to reopen after it is closed. is closed. M0-3081 HPSI Hot Leg Injection Mode NIA Valve is normally open and has no Valve is normally open and has no Select active safety function to reopen after it active safety function to reopen after it is closed. is closed. M0-3189 LPSI Pump P-678 Inlet from N/A Valve is normally open and has no Valve is normally open and has no SIRWTank active safety function to open. active safety function to open. 4 ATTACHMENT 1 TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PLTB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding to PL or TB Justification/
It does not have to reopen.               It does not have to reopen.
Action J ustifi ca ti on/ Ac ti on M0-3198 LPSI Pump P-67 A Inlet from N/A Valve is normally open and has no Valve is normally open and has no SIRWTank active safety function to open. active safety function to open. CV-0939 MZ-11 Shield Cooling Surge N/A This valve is excluded from further GL This valve is excluded from further GL Tank 95-07 consideration because it is a 95-07 consideration because it is a globe valve. See. Note 1 globe valve. See Note 1 M0-2087 Volume Control Tank Outlet N/A Valve is normally open and does not Valve is normally open and does not have an active safety function to have an active safety function to reopen after it closes. reopen after it closes. CV-0437A Iodine Removal Tank Outlet N/A The valve was retired in place as part The valve was retired in place as part of FC 949. It currently has no safety of FC 949. It currently has ho safety : function.
CV-3056   SIRW Tank Recirculation         N/A         Valve is normally open and only has       Valve is normally open and only has to close to perform its safety function. to close to perform its safety function.
function.
It does not have to reopen.               It does not have to reopen.
CV-04378 Iodine Removal Tank Outlet N/A The valve was retired in place as part The valve was retired in place as part of FC 949 .. it currently has no safety of FC 949. It currently has no safety function.
                                                                          -
function.
1
CV-0438A Iodine Removal Tank Outlet NIA The valve was retired in place as part The valve was retired in place as part of FC 949. It currently has no safety of FC 949. It currently has no safety function.
 
function.
ATTACHMENT 1 TABLE- VAL VE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description                   Susceptible Pressure Locking                         Thermal Binding I
CV-04388 Iodine Removal Tank Outlet N/A The valve was retired in place as part The valve was retired in place as part of FC 949. It currently has no safety of FC 949. It currently has no safety function.
to PL or TB Justification/Action                     Justification/Action CV-3057   SIRW Tank Outlet             N/A         Valve is normally open and only has       Valve is normally open and only has Jo close to perform its safety function. to close to perform its safety function.
function.
It does not have to reopen.               It does not have to reopen.
M0-2160 SIRW Tank to CVCS Isolation PL&T8 Valve has 81% margin based on Valve lff of 45° Fis below.the COMED Anplysis Method. See threshold for thermal binding of flex Attachment 2 for Inputs. wedge gate valves. There is no heat trace on this eves valve. 5 ATTACHMENT 1 TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PLTB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding to PL or TB Justification/Action J ustifi ca ti on/Action
CV-0704   Slowdown Tank Discharge to Condensate Discharge N/A         Valve has no active safety function to reposition.
: M0-2169 Boric Acid Gravity Feed PL & TB Valve has 4% margin .based on Valve .6T of 25° Fis below the lsolatiori COMED Analysis Method. See threshold for thermal binding of flex I Attachment 2 for Inputs. wedge gate valves. The valve is heat : ' " traced and maintains a temperature of 165 ° F +/-5 °. Low alarm set point is 145° F. M0-2170 Boric Acid Gravity Feed PL'& TB Valve has 21 % margin based on Valve .6 T of 25° F is below the Isolation COMED Analysis Method. See threshold for thermal binding of flex Attachment 2 for Inputs. wedge gate valves. The valve is heat traced and maintains a temperature of 165° F +/-5°. Low alarm set point is 145° F. M0-2140 Boric Acid Gravity Feed PL&TB Valve has 31% margin based.on Valve .6T of 25° Fis below the Isolation COMED Analysis Method. See threshold for thermal binding of flex Attachment 2 for Inputs. wedge gate valves. The valve is heat ' traced and maintains a temperature of 165° F +/-5°. Low alarm set point is 145° F. CV-3018 HPSI T;rain Cross Connect N/A Valve is normally closed and has no Valve is normally closed and has no Isolation active safety function to open. active safety function to open. M0-3190 LPSI Pump P-678 Shutdown N/A Excluded from scope of NRC GL 95-Excluded from scope of NRC GL 95-Cooling Inlet Isolation 07 based on Palisades being a Hot 07 based on Palisades being a Hot Shutdown Plant. Shutdown Plant. M0-3199 LPSI Pump P-67 A Shutdown N/A Excluded from scope of NRC GL 95-Excluded from scope of NRC GL 95-Cooling Inlet Isolation 07 based on Palisades being a Hot 07 based on Palisades being a Hot Shutdown Plant. Shutdown Plant. 6 ATTACHMENT 1
Valve has no active safety function to reposition.
VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding ' to PL or TB Justification/Action Justification/Action
e
: ' M0-3015 PCS to Shutdown Cooling N/A Excluded from scope of NRC GL 95-Excluded from scope of NRC GL 95-Isolation 07 based on Palisades being a Hot 07 based on Palisades being a Hot Shutdown Plant. Shutdown Plant. M0-3016 PCS to Shutdown Cooling N/A Excluded from scope of NRC GL 95-Excluded from scope of NRC GL 95-Isolation 07 based on Palisades being a Hot 07 based on Palisades being a Hot : Shutdown Plant. Shutdown Plant. CV-3029 Containment Sump Isolation N/A Valve does have an active safety The. Containment Sump Valves are function to open. However, the valve only opened for surveillance testing disc is a solid wedge design which is during cold shutdown and then not susceptible to an occurrence of reclosed.
                          -
The valves are not closed pressure IOc_king.
CV-0733   Hotwell 12" Makeup Valve     N/A         Valve has no active safety function to   Valve has no active safety function to reposition.                               reposition.
hot. Additionally, the valves are insulated by a column of water between the valves and the Containment Sump so they will not experience large thermal transients.
M0-0501   MSIV Bypass Valve             N/A         Valve has no   ~ctive safety function to Valve has no active safety function to
CV-3030 Sump Isolation N/A Valve does have an active safety The Containment Sump Valves are function to open. However, the valve only opened for surveillance testing disc is a solid wedge design which is during cold shutdown and then not susceptible to an occurrence of . reclosed.
                '                                 open.                                     open.
The valves are not closed pressure locking. hot. Additionally, the valves are insulated by a c_olumn of water between the valves and the Containment Sump so they will not experience large thermal transients.
M0-0510   MSIV'Bypass Valve             N/A         Valve has rio active safety function to   Valve has no active safety function to open.                                     open.
Note 1: During implementation of the Palisades AOV Program, CV-0939, Shield Cooling Surge Tank Inlet Valve, was verified as a globe valve. The Plant Equipment Data Base has been updated to reflect the proper valve type. The original submittal included this valve in the scope of safety related power operated gate valves. Additionally, the Palisades AOV Program has not found any other valves that were classified as globe valves that should have been gate valves. 7 ATTACHMENT 2 CONSUMERS ENERGY COMPANY PALISADES PLANT DOCKET 50-255 SUPPLEMENTAL INFORMATION-GENERIC LETTER 95-07 "PRESSURE LOCKING AND THERMAL BINDING OFSAFETY-RELATED POWER-OPERATED GATE VALVES" INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS 3 Pages
CV-3212   Shutdown Cooling Hx Inlet     N/A         Valve is normally open and has no         Valve is normally open and has no Valve                                     active safety function to open.         active safety function to open.
.. ATTACHMENT 2 INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS The following inputs and assumptions were used in the COMED methodology calculations for determining the additional forces needed to unwedge a pressure locked valve (Reference Palisades Engineering Analysis EA-PL TB-00). These calculations form the basis for determining the available MOV margin as reported in Attachment
CV~3213  Shutdown Cooling Hx Outlet   N/A         Valve is normally open and has no         Valve is normally open and has no Valve                                     active safety function to open.         active safety function to open.
: 1. The differences between the available margin reported in this submittal and the margir(in the original 180 day submittal are as follows: 1. The original calculation used the Entergy Methodology and now the COMED Methodology is used. The methodology change reflects industry feedback on the validity .of the two calculational methods. 2. There is an additional 20% margin added to the disc pullout forces to account for future changes in this force. The original calculations included the appropriate VOTES diagnostic accuracy assumptions, but this additional 20% is added to assure that future changes due to different torque switch trip settings do not create a need to revise the PL TB Calculations.
CV-3223   Shutdown Cooling Hx Inlet     N/A         Valve is normally open and has no         Valve is normally open and has no Valve                                     active safety function to open.         active safety function to open.
: 3. The original calculations used a generic 0.5 valve factor. This was revised to be consistent with the valve factor assumption used for NRC Generic Letter 89-10. The new valve factors for M0-2140, 2160, 2169 and 2170 are 0.8. M0-2140, MO-2160 Assumptions:
CV-3224   Shutdown Cooling Hx Outlet   N/A         Valve is normally open and has no         Valve is normally open and has no Valve*                                     active safety function to open.         active safety function to open.
M0-0798   Aux Feedwater Isolation Valve N/A         SC 95-041 disconnected power to this     SC 95-041 disconnected power to this valve. Valve retired in,place and       valve. Valve retired in place and locked open.                             locked open.
 
ATTACHMENT 1 TABLE- VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description                   Susceptible Pressure Locking                     Thermal Binding to PL or TB Justification/Action                 Justification/Action M0-3041   Safety Injection Tank T-82A   N/A         Valve is normally open and has no   Valve is normally open and has no Outlet Isolation                         active safety function to reopen if active safety function to reopen if closed.                             closed.
M0-3045   Safety Injection Tank T-828   N/A         Valve is normally open and*has no   Valve is normally open and has no Outlet Isolation                         active safety function to reopen if active safety function to reopen if closed.                             closed.
M0-3049   Safety Injection Tank T-82C   N/A         Valve is normally open and has no   Valve is normally open and has no Outlet Isolation                         active safety function to reopen if active safety function to reopen if I
closed.                             closed.
M0-3052   Safety Injection Tank T-820   N/A         Valve is normally open and has no   Valve is normally open and has no Outlet Isolation                         active safety function to reopen if active safety function to reopen if closed.                             closed.
CV-3036   HPSI Pump P-66A to HPSI       N/A         Valve is normally open and has no   Valve is normally open and has no Train 2 Isolation                         active safety function to open.     active safety function to open.
CV-3037   HPSI Pump P-66A to HPSI       NIA         Valve is normally closed and has no Valve is normally closed and has no Train 1 Isolation                         active safety function to.open.     active safety function to open.
CV-3059   HPSI Pump P-668 to HPSI       N/A         Valve is normally open and has no   Valve is normally open and has no Train 1 Isolation.                       active safety function to open.     active safety function to open.
M0-0743   Aux Feedwater Isolation Valve N/A         SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and   valve. Valve retired in place and locked open.                         locked open.
M0-0748   Aux Feedwater Isolation Valve N/A         SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and   valve. Valve retired in place and locked open.                         locked open.
3
 
ATTACHMENT 1 TABLE- VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description                   Susceptible Pressure Locking                         Thermal Binding
                ;                       to PL or TB Justification/Action                     Justification/Action
                '
M0-0753   Aux Feedwater Isolation Valve N/A         SC 95-041 disconnected power to this     SC 95-041 disconnected power to this valve. Valve retired in place and         valve. Valve retired in place and locked open.                             locked open.
M0-0754   Aux Feedwater Isolation Valve N/A         SC 95-041 disconnected power to this     SC 95-041 disconnected power to this valve. Valve retired in place and         valve. Valve retired in place and locked open.                             locked open.
M0-0755   Aux Fe'edwater Isolation Valve N/A -     SC 95-041 disc!onnected power to this     SC 95-041 disconnected power to this valve. Valve retired in place and.       valve. Valve retired in place and locked open.                             locked open.
M0-0759   Aux Feedwater Isolation Valve N/A         SC 95-041 disconnected power to this     SC 95-041 disconnected power to this valve. Valve retired in place and         valve. Valve retired in place and locked open.                             locked open.
M0-0760   Aux Feedwater Isolation Valve N/A         SC 95-041 disconnected power to this     SC 95-041 disconnected power to this valve. Valve retired in place and         valve. Valve *retired in place and locked open.                             locked open.
M0-3080   HPSI Hot Leg Injection Mode   N/A         Valve is normally open and has no         Valve is normally open and has no Select                                     active safety function to reopen after it active safety function'to reopen after it is closed.                               is closed.
M0-3081   HPSI Hot Leg Injection Mode   NIA         Valve is normally open and has no         Valve is normally open and has no Select                                     active safety function to reopen after it active safety function to reopen after it is closed.                               is closed.
M0-3189   LPSI Pump P-678 Inlet from     N/A         Valve is normally open and has no         Valve is normally open and has no SIRWTank                                   active safety function to open.           active safety function to open.
4
 
ATTACHMENT 1 TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PLTB SUSCEPTIBILITY Tag No. Description                   Susceptible Pressure Locking                       Thermal Binding to PL or TB Justification/Action                   J ustifi ca ti on/Ac ti on M0-3198   LPSI Pump P-67 A Inlet from   N/A         Valve is normally open and has no       Valve is normally open and has no SIRWTank                                 active safety function to open.         active safety function to open.
CV-0939   MZ-11 Shield Cooling Surge   N/A         This valve is excluded from further GL This valve is excluded from further GL Tank                                     95-07 consideration because it is a     95-07 consideration because it is a globe valve. See. Note 1               globe valve. See Note 1 M0-2087   Volume Control Tank Outlet   N/A         Valve is normally open and does not     Valve is normally open and does not have an active safety function to       have an active safety function to reopen after it closes.                 reopen after it closes.
CV-0437A Iodine Removal Tank Outlet   N/A         The valve was retired in place as part The valve was retired in place as part of FC 949. It currently has no safety   of FC 949. It currently has ho safety
:             function.                               function.
CV-04378 Iodine Removal Tank Outlet   N/A         The valve was retired in place as part The valve was retired in place as part of FC 949 .. it currently has no safety of FC 949. It currently has no safety function.                               function.
CV-0438A Iodine Removal Tank Outlet   NIA         The valve was retired in place as part The valve was retired in place as part of FC 949. It currently has no safety   of FC 949. It currently has no safety function.                               function.
CV-04388 Iodine Removal Tank Outlet   N/A         The valve was retired in place as part The valve was retired in place as part of FC 949. It currently has no safety   of FC 949. It currently has no safety function.                               function.
M0-2160   SIRW Tank to CVCS Isolation   PL&T8       Valve has 81% margin based on           Valve lff of 45° Fis below.the COMED Anplysis Method. See             threshold for thermal binding of flex Attachment 2 for Inputs.               wedge gate valves. There is no heat trace on this eves valve.
5
 
ATTACHMENT 1 TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PLTB SUSCEPTIBILITY Tag No. Description               Susceptible Pressure Locking                   Thermal Binding to PL or TB Justification/Action               J ustifi ca ti on/Action
:
M0-2169   Boric Acid Gravity Feed   PL & TB     Valve has 4% margin .based on       Valve .6T of 25° Fis below the lsolatiori                             COMED Analysis Method. See         threshold for thermal binding of flex I
:
Attachment 2 for Inputs.           wedge gate valves. The valve is heat
                    '                                       "
traced and maintains a temperature of 165 ° F +/-5 °. Low alarm set point is 145° F.
M0-2170   Boric Acid Gravity Feed   PL'& TB     Valve has 21 % margin based on     Valve .6T of 25° F is below the Isolation                             COMED Analysis Method. See         threshold for thermal binding of flex Attachment 2 for Inputs.           wedge gate valves. The valve is heat traced and maintains a temperature of 165° F +/-5°. Low alarm set point is 145° F.
M0-2140   Boric Acid Gravity Feed   PL&TB       Valve has 31% margin based.on       Valve .6T of 25° Fis below the Isolation                             COMED Analysis Method. See         threshold for thermal binding of flex Attachment 2 for Inputs.           wedge gate valves. The valve is heat traced and maintains a temperature of
                  '
165° F +/-5°. Low alarm set point is 145° F.
CV-3018   HPSI T;rain Cross Connect N/A         Valve is normally closed and has no Valve is normally closed and has no Isolation                             active safety function to open. active safety function to open.
M0-3190   LPSI Pump P-678 Shutdown N/A         Excluded from scope of NRC GL 95-   Excluded from scope of NRC GL 95-Cooling Inlet Isolation               07 based on Palisades being a Hot   07 based on Palisades being a Hot Shutdown Plant.                     Shutdown Plant.
M0-3199   LPSI Pump P-67 A Shutdown N/A         Excluded from scope of NRC GL 95-   Excluded from scope of NRC GL 95-Cooling Inlet Isolation               07 based on Palisades being a Hot   07 based on Palisades being a Hot Shutdown Plant.                     Shutdown Plant.
6
 
ATTACHMENT 1 TABLE~        VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No.       Description                         Susceptible     Pressure Locking                             Thermal Binding
                        '
to PL or TB     Justification/Action                         Justification/Action
:
                                                                                                                                              '
M0-3015       PCS to Shutdown Cooling             N/A             Excluded from scope of NRC GL 95-           Excluded from scope of NRC GL 95-Isolation                                           07 based on Palisades being a Hot           07 based on Palisades being a Hot Shutdown Plant.                             Shutdown Plant.
M0-3016       PCS to Shutdown Cooling             N/A             Excluded from scope of NRC GL 95-           Excluded from scope of NRC GL 95-Isolation                                           07 based on Palisades being a Hot           07 based on Palisades being a Hot
:                                           Shutdown Plant.                             Shutdown Plant.
CV-3029       Containment Sump Isolation           N/A             Valve does have an active safety             The. Containment Sump Valves are function to open. However, the valve         only opened for surveillance testing disc is a solid wedge design which is       during cold shutdown and then not susceptible to an occurrence of         reclosed. The valves are not closed pressure IOc_king.                           hot. Additionally, the valves are insulated by a column of water between the valves and the Containment Sump so they will not experience large thermal transients.
CV-3030       Contai~ment  Sump Isolation         N/A             Valve does have an active safety             The Containment Sump Valves are function to open. However, the valve         only opened for surveillance testing disc is a solid wedge design which is       during cold shutdown and then not susceptible to an occurrence of .       reclosed. The valves are not closed pressure locking.                           hot. Additionally, the valves are insulated by a c_olumn of water between the valves and the Containment Sump so they will not experience large thermal transients.
Note 1: During implementation of the Palisades AOV Program, CV-0939, Shield Cooling Surge Tank Inlet Valve, was verified as a globe valve. The Plant Equipment Data Base has been updated to reflect the proper valve type. The original submittal included this valve in the scope of safety related power operated gate valves. Additionally, the Palisades AOV Program has not found any other valves that were classified as globe valves that should have been gate valves.
7
 
ATTACHMENT 2 CONSUMERS ENERGY COMPANY PALISADES PLANT DOCKET 50-255 SUPPLEMENTAL INFORMATION- GENERIC LETTER 95-07 "PRESSURE LOCKING AND THERMAL BINDING OFSAFETY-RELATED POWER-OPERATED GATE VALVES" INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS 3 Pages
 
..
ATTACHMENT 2 INPUT   AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS The following inputs and assumptions were used in the COMED methodology calculations for determining the additional forces needed to unwedge a pressure locked valve (Reference Palisades Engineering Analysis EA-PLTB-00). These calculations form the basis for determining the available MOV margin as reported in Attachment 1. The differences between the available margin reported in this submittal and the margir(in the original 180 day submittal are as follows:
: 1. The original calculation used the Entergy Methodology and now the COMED Methodology is used. The methodology change reflects industry feedback on the validity
      .of the two calculational methods.
: 2. There is an additional 20% margin added to the disc pullout forces to account for future changes in this force. The original calculations included the appropriate VOTES diagnostic accuracy assumptions, but this additional 20% is added to assure that future changes due to different torque switch trip settings do not create a need to revise the PL TB Calculations.
: 3. The original calculations used a generic 0.5 valve factor. This was revised to be consistent with the valve factor assumption used for NRC Generic Letter 89-10. The new valve factors for M0-2140, 2160, 2169 and 2170 are 0.8.
M0-2140, MO- 2160 Assumptions:
: 1. The maximum pressure in the bonnet is assumed to be the highest pressure seen from upstream and downstream sources. The upstream and downstream pressures are conservatively set equal to 0.0 psi at the time of valve opening. This represents the worst possible scenario.
: 1. The maximum pressure in the bonnet is assumed to be the highest pressure seen from upstream and downstream sources. The upstream and downstream pressures are conservatively set equal to 0.0 psi at the time of valve opening. This represents the worst possible scenario.
: 2. An additional 20% margin (on top of diagnostic accuracy) is conservatively included for the measured pullout thrust values to provide for future variances in actual pullout values.
: 2. An additional 20% margin (on top of diagnostic accuracy) is conservatively included for the measured pullout thrust values to provide for future variances in actual pullout values.                                       *
* 3. The valves are 3", 150#, Velan flex wedge gate valves. Conversations with Velan revealed that Velan uses a 1500# class valve body for all pressure classes. As such, it is expected that the valve body/disc are indeed stiff and there is not a concern of the valve body stretching due to the bonnet pressure and the disc traveling further into the seat. As such, additional pinching_of the disc due to this phenomena is not considered in the pressure locking calculations.
: 3. The valves are 3", 150#, Velan flex wedge gate valves. Conversations with Velan revealed that Velan uses a 1500# class valve body for all pressure classes. As such, it is expected that the valve body/disc are indeed stiff and there is not a concern of the valve body stretching due to the bonnet pressure and the disc traveling further into the seat.
These are forged valves and typically*
As such, additional pinching_of the v~lve disc due to this phenomena is not considered in the pressure locking calculations. These are forged valves and typically* the forging process results in a thicker (and therefore more stiff) material than a cast valve. The stiffness of the valve body and disc should preclude any significant pinching effect.
the forging process results in a thicker (and therefore more stiff) material than a cast valve. The stiffness of the valve body and disc should preclude any significant pinching effect. I 1
I 1
, . . ATTACHMENT 2 INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS Inputs: Upstream Pressure Downstream Pressure Bonnet Pressure Valve Disc Wedge 8° Structural Thrust Limit Mean Seat Radius Stem Diameter 0 psi 0 psi 120 psi 50 22,894 lbf 1.281 in. 1.121 in. Required Unseating Forces: Pressure Locking Force: 441.7 lbf Piston Effect: -118.4 lbf Reverse Piston Effect: 107.8 lbf Pullout Thrust (M0-2140):
 
4800 lbf Pullout Thrust (M0-2160):
.
3000 lbf Total Required Force: M0-2140 M0-2160 Margin: M0-2140 M0-2160 M0-2169, M0-2170 Assumptions:
,.
5231.1 lbf 3431.1 lbf 31.4% 81.2% Modulus of Elasticity 29X10 6 psi Disc Center to Hub Edge 0. 736 Disc Thickness Valve Factor Hub Length Disc Coefficient of Friction 0.761 in. 0.8 1 in. 0.857 Poisson's ratio (disc) 0.27 Motor Gearing Capability:
ATTACHMENT 2 INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS Inputs:
M0-2140 M0-2160 6877 lbf 6218 lbf 1. The maximum pressure in the bonnet is assumed to be the highest pressure seen from upstream and downstream sources. The upstream and downstream pressures are conservatively set equal to 0.0 psi at the time of valve opening. This represents the worst possible-scenario.
Upstream Pressure           0 psi                  Modulus of Elasticity        29X10 6 psi Downstream Pressure         0 psi                  Disc Center to Hub Edge      0. 736 Bonnet Pressure             120 psi                Disc Thickness              0.761 in.
: 2. An additional 20% margin (on top of diagnostic accuracy) is conservatively included for the measured pullout thrust values to provide for future variances in actual pullout values. ' 3. The valves are 4", 150#, Velan flex wedge gate valves. Conversations with Velan revealed that Velan uses a 1500# class valve body for all pressure classes. As such, it is expected that the valve body/disc are indeed stiff and there is not a concern of the valve body stretching due to the bonnet pressure and the disc traveling further into the seat. 2 i ATTACHMENT 2 INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS As such, additional pinching of the valve disc due to this phenomena is not con.sidered in the pressure locking calculations.
Valve Disc Wedge 8°         50                      Valve Factor                0.8 Structural Thrust Limit     22,894 lbf             Hub Length                  1 in.
These are forged valves and typically the forging process results in a thi_cker (and therefore more stiff) material than a cast valve. The stiffness of the valve body and disc should preclude any significant pinching effect. Inputs: Upstream Pressure Downstream Pressure Bonnet Pressure Valve Disc Wedge 8° Structural Thrust Limit Mean Seat Radius Stem Diameter 0 psi 0 psi 120 psi 50 31,566 lbf 1.859 in. 1.37 in. Required Unseating Forces: Pressure Locking Force: 698.5 lbf Piston Effect: -176.8 lbf Reverse Piston Effect: 227.1 lbf Pullout Thrust (M0-2169):
Mean Seat Radius            1.281 in.               Disc Coefficient of Friction        0.857 Stem Diameter              1.121 in.               Poisson's ratio (disc)      0.27 Required Unseating Forces:
5025 lbf Pullout Thrust (M0-2170):
Pressure Locking Force: 441.7 lbf Piston Effect:             -118.4 lbf Reverse Piston Effect:     107.8 lbf Pullout Thrust (M0-2140): 4800 lbf Pullout Thrust (M0-2160): 3000 lbf Total Required Force:                               Motor Gearing Capability:
4570 lbf Total Required Force: M0-2169 M0-2170 *Margin: M0-2169 M0-2170 5773.8 lbf 5318.8 lbf 4.3% 21.1% Modulus of Elasticity 29X10 6 psi
M0-2140                     5231.1 lbf              M0-2140                     6877 lbf M0-2160                     3431.1 lbf              M0-2160                      6218 lbf Margin:
* Disc Center to Hub Edge 1.25 Disc Thickness 0.941 in." Valve Factor 0.8 Hub Length 1 in. Disc Coefficient of Friction 0.857 Poisson's ratio (disc)
M0-2140                    31.4%
* 0.27 Motor Gearing Capability:
M0-2160                    81.2%
M0-2169 M0-2170 6022 lbf 6444 lbf As noted earlier, the apparent low margin in M0-2169 is largely a function of the additional 20% margin that was added to the pullout forces. If the additional 20% conservatism is-neglected,-then the actualmargin for M0-2169 is 21. 9%.
M0-2169, M0-2170 Assumptions:
: 1. The maximum pressure in the bonnet is assumed to be the highest pressure seen from upstream and downstream sources. The upstream and downstream pressures are conservatively set equal to 0.0 psi at the time of valve opening. This represents the worst possible-scenario.
: 2. An additional 20% margin (on top of diagnostic accuracy) is conservatively included for the measured pullout thrust values to provide for future variances in actual pullout values.                                               '
: 3. The valves are 4", 150#, Velan flex wedge gate valves. Conversations with Velan revealed that Velan uses a 1500# class valve body for all pressure classes. As such, it is expected that the valve body/disc are indeed stiff and there is not a concern of the valve body stretching due to the bonnet pressure and the disc traveling further into the seat.
2
 
i ATTACHMENT 2 INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS As such, additional pinching of the valve disc due to this phenomena is not con.sidered in the pressure locking calculations. These are forged valves and typically the forging process results in a thi_cker (and therefore more stiff) material than a cast valve. The stiffness of the valve body and disc should preclude any significant pinching effect.
Inputs:
Upstream Pressure             0 psi                  Modulus of Elasticity        29X106 psi
* Downstream Pressure           0 psi                  Disc Center to Hub Edge      1.25 Bonnet Pressure               120 psi                Disc Thickness                0.941 in."
Valve Disc Wedge 8°           50                    Valve Factor                  0.8 Structural Thrust Limit       31,566 lbf             Hub Length                    1 in.
Mean Seat Radius              1.859 in.             Disc Coefficient of Friction        0.857 Stem Diameter                1.37 in.               Poisson's ratio (disc)
* 0.27 Required Unseating Forces:
Pressure Locking Force: 698.5 lbf Piston Effect:               -176.8 lbf Reverse Piston Effect:       227.1 lbf Pullout Thrust (M0-2169): 5025 lbf Pullout Thrust (M0-2170): 4570 lbf Total Required Force:                               Motor Gearing Capability:
M0-2169                       5773.8 lbf            M0-2169                       6022 lbf M0-2170                       5318.8 lbf             M0-2170                      6444 lbf
*Margin:
M0-2169                       4.3%
M0-2170                       21.1%
As noted earlier, the apparent low margin in M0-2169 is largely a function of the additional 20% margin that was added to the pullout forces. If the additional 20%
conservatism is-neglected,-then the actualmargin for M0-2169 is 21. 9%.


== Conclusion:==
== Conclusion:==

Revision as of 17:54, 21 October 2019

Forwards Supplemental Info Requested by NRC to Support Plant SER for GL 95-07, Pressure Locking & Thermal Binding of Power-Operated Gate Valves.
ML18065B169
Person / Time
Site: Palisades Entergy icon.png
Issue date: 02/23/1998
From: Bordine T
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
GL-95-07, GL-95-7, NUDOCS 9803040016
Download: ML18065B169 (15)


Text

consumers Energy

.r A CMS Energy Company Tlloma* t:. Bordhw Manager Licensing February 23, 1998 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT SUPPLEMENTAL INFORMATION - GENERIC LETTER 95-07, "PRESSURE LOCKING AND THERMAL BINDING OF SAFETY-RELATED POWER-OPERATED GATE VALVES" This letter provides the supplemental information requested by the NRC to support the Palisades Safety Evaluation Report for NRC Generic Letter (GL) 95-07, "Pressure*

Locking and Thermal Binding of Power-Operated Gate Valves."

Two attachments provide the necessary information. Attachment 1 is a table which summarizes the safety function and the pressure locking and thermal binding susceptibility bases for each of the valves covered in the 180-day response to GL 95-07, dated February 13, 1996. The table also provides the corrective actions that have been or will be taken to address the pressure locking or thermal binding concerns. This table lists valves in the same order as presented to the NRC in the 180-day submittal.

Attachment 2 addresses power-operated gate valves that were susceptible to pressure locking and for which analytical models were used to determine the unseating forces.

This attachment provides the necessary information to quantify the margins available to overcome pressure_locking -~-- _ ~ I/

( . .* 9803040016 900223 ~.

L PDR P


--- --

ADOCK 05000255

-- - --- -- - -- -PDR :'. *

- J 1111111111111111111111111111111111111111 i Palisades Nuclear Plant

  • 27780 Blue Star Memorial Highway
  • CovtJi/, Ml 49043
  • Tel: 616 764 2913
  • Fax: 616 764 2490

2

- . -

SUMMARY

OF COMMITMENTS This letter contains no new commitments and no revisions to existing commitments.

~~

Thomas C. Berdine Manager, Licensing CC Administrator, Region Ill, USNRC Project Manager, NRR, USNRC NRC Resident Inspector - Palisades 2 Attachments

CONSUMERS ENERGY COMPANY To the best of my knowledge, the contents of this supplemental information supporting GL 95-07 response, are truthful and complete.

~~~ Thomas C. Sardine Manager, Licensing Sworn and subscribed to before me this cJ 3-' day of ~ 1998.

t

~'VY\-~~

Alora M. Davis, Notary Public Berrien County, Michigan (Acting in V~n Buren County, Michigan)

My commission expires August 26, 1999

ATTACHMENT 1 CONSUMERSENERGYCOMPANY PALISADES PLANT DOCKET 50-255 SUPPLEMENTAL INFORMATION - GENERIC LETTER 95-07 "PRESSURE LOCKING AND THERMAL BINDING OF SAFETY-RELATED POWER-OPERATED GATE VALVES" TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PLTB SUSCEPTIBILITY 7 Pages

ATTACHMENT 1 TABLE- VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Descr!ption Susceptible Pressure Locking Thermal Binding to PL or TB J ustifi ca ti on/Ac ti on Justification/Action

CV-0521 Alternate Steam Supply to AFW N/A Valve was removed from the plant in Valve was removed from the plant in Pump P-8B 1996 as part of modification FC-966. 1996 as part of modification FC-966.

M0-1042A PORV Block Valve PL& TB Drilled hole in upstream disc.

Completed 12/96 Converting from torque seating to limit seating in 98 REFOUT. e M0-1043A PORV Block Valve PL& TB Drilled hole in upstream disc. Converting from torque seating to limit

, Completed 12/96 seating in 98 REFOUT.

CV-3055 Shutdown Cooling Inlet to N/A Excluded from scope of NRC GL 95- Excluded from scope of NRC GL 95-Shutdown Cooling Heat 07 based on Palisades being a Hot 07 based on Palisades being a Hot Exchanger Shutdown Plant. Shutdown Plant.

CV-3070 HPSI $ub Cooling Valve PL& TB Bonnet vent path to upstream side of Valve lff of 32° Fis below.the valve will be installed prior to threshold for thermal binding of conclusion of 98REFOUT. double disc gate valves.

CV-3071 HPSI Sub Cooling Valve PL& TB Bonnet vent path to upstream side of Valve 6.T of 32° F is below the valve will be installed prior to threshold for thermal binding of conclusion of 98REFOUT. double disc gate valves.

CV-3027 SIRW Tank Recirculation N/A Valve is normally open and only has Valve is normally open and only has to close to perform its safety function. to close to perform its safety function.

It does not have to reopen. It does not have to reopen.

CV-3031 SIRW Tank Outlet N/A Valve is normally open and only has Valve is normally open and only has to close to perform its safety function.- to close to perform its safety function.

It does not have to reopen. It does not have to reopen.

CV-3056 SIRW Tank Recirculation N/A Valve is normally open and only has Valve is normally open and only has to close to perform its safety function. to close to perform its safety function.

It does not have to reopen. It does not have to reopen.

-

1

ATTACHMENT 1 TABLE- VAL VE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding I

to PL or TB Justification/Action Justification/Action CV-3057 SIRW Tank Outlet N/A Valve is normally open and only has Valve is normally open and only has Jo close to perform its safety function. to close to perform its safety function.

It does not have to reopen. It does not have to reopen.

CV-0704 Slowdown Tank Discharge to Condensate Discharge N/A Valve has no active safety function to reposition.

Valve has no active safety function to reposition.

e

-

CV-0733 Hotwell 12" Makeup Valve N/A Valve has no active safety function to Valve has no active safety function to reposition. reposition.

M0-0501 MSIV Bypass Valve N/A Valve has no ~ctive safety function to Valve has no active safety function to

' open. open.

M0-0510 MSIV'Bypass Valve N/A Valve has rio active safety function to Valve has no active safety function to open. open.

CV-3212 Shutdown Cooling Hx Inlet N/A Valve is normally open and has no Valve is normally open and has no Valve active safety function to open. active safety function to open.

CV~3213 Shutdown Cooling Hx Outlet N/A Valve is normally open and has no Valve is normally open and has no Valve active safety function to open. active safety function to open.

CV-3223 Shutdown Cooling Hx Inlet N/A Valve is normally open and has no Valve is normally open and has no Valve active safety function to open. active safety function to open.

CV-3224 Shutdown Cooling Hx Outlet N/A Valve is normally open and has no Valve is normally open and has no Valve* active safety function to open. active safety function to open.

M0-0798 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in,place and valve. Valve retired in place and locked open. locked open.

ATTACHMENT 1 TABLE- VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding to PL or TB Justification/Action Justification/Action M0-3041 Safety Injection Tank T-82A N/A Valve is normally open and has no Valve is normally open and has no Outlet Isolation active safety function to reopen if active safety function to reopen if closed. closed.

M0-3045 Safety Injection Tank T-828 N/A Valve is normally open and*has no Valve is normally open and has no Outlet Isolation active safety function to reopen if active safety function to reopen if closed. closed.

M0-3049 Safety Injection Tank T-82C N/A Valve is normally open and has no Valve is normally open and has no Outlet Isolation active safety function to reopen if active safety function to reopen if I

closed. closed.

M0-3052 Safety Injection Tank T-820 N/A Valve is normally open and has no Valve is normally open and has no Outlet Isolation active safety function to reopen if active safety function to reopen if closed. closed.

CV-3036 HPSI Pump P-66A to HPSI N/A Valve is normally open and has no Valve is normally open and has no Train 2 Isolation active safety function to open. active safety function to open.

CV-3037 HPSI Pump P-66A to HPSI NIA Valve is normally closed and has no Valve is normally closed and has no Train 1 Isolation active safety function to.open. active safety function to open.

CV-3059 HPSI Pump P-668 to HPSI N/A Valve is normally open and has no Valve is normally open and has no Train 1 Isolation. active safety function to open. active safety function to open.

M0-0743 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve retired in place and locked open. locked open.

M0-0748 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve retired in place and locked open. locked open.

3

ATTACHMENT 1 TABLE- VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding

to PL or TB Justification/Action Justification/Action

'

M0-0753 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve retired in place and locked open. locked open.

M0-0754 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve retired in place and locked open. locked open.

M0-0755 Aux Fe'edwater Isolation Valve N/A - SC 95-041 disc!onnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and. valve. Valve retired in place and locked open. locked open.

M0-0759 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve retired in place and locked open. locked open.

M0-0760 Aux Feedwater Isolation Valve N/A SC 95-041 disconnected power to this SC 95-041 disconnected power to this valve. Valve retired in place and valve. Valve *retired in place and locked open. locked open.

M0-3080 HPSI Hot Leg Injection Mode N/A Valve is normally open and has no Valve is normally open and has no Select active safety function to reopen after it active safety function'to reopen after it is closed. is closed.

M0-3081 HPSI Hot Leg Injection Mode NIA Valve is normally open and has no Valve is normally open and has no Select active safety function to reopen after it active safety function to reopen after it is closed. is closed.

M0-3189 LPSI Pump P-678 Inlet from N/A Valve is normally open and has no Valve is normally open and has no SIRWTank active safety function to open. active safety function to open.

4

ATTACHMENT 1 TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PLTB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding to PL or TB Justification/Action J ustifi ca ti on/Ac ti on M0-3198 LPSI Pump P-67 A Inlet from N/A Valve is normally open and has no Valve is normally open and has no SIRWTank active safety function to open. active safety function to open.

CV-0939 MZ-11 Shield Cooling Surge N/A This valve is excluded from further GL This valve is excluded from further GL Tank 95-07 consideration because it is a 95-07 consideration because it is a globe valve. See. Note 1 globe valve. See Note 1 M0-2087 Volume Control Tank Outlet N/A Valve is normally open and does not Valve is normally open and does not have an active safety function to have an active safety function to reopen after it closes. reopen after it closes.

CV-0437A Iodine Removal Tank Outlet N/A The valve was retired in place as part The valve was retired in place as part of FC 949. It currently has no safety of FC 949. It currently has ho safety

function. function.

CV-04378 Iodine Removal Tank Outlet N/A The valve was retired in place as part The valve was retired in place as part of FC 949 .. it currently has no safety of FC 949. It currently has no safety function. function.

CV-0438A Iodine Removal Tank Outlet NIA The valve was retired in place as part The valve was retired in place as part of FC 949. It currently has no safety of FC 949. It currently has no safety function. function.

CV-04388 Iodine Removal Tank Outlet N/A The valve was retired in place as part The valve was retired in place as part of FC 949. It currently has no safety of FC 949. It currently has no safety function. function.

M0-2160 SIRW Tank to CVCS Isolation PL&T8 Valve has 81% margin based on Valve lff of 45° Fis below.the COMED Anplysis Method. See threshold for thermal binding of flex Attachment 2 for Inputs. wedge gate valves. There is no heat trace on this eves valve.

5

ATTACHMENT 1 TABLE-VALVE LIST CONTAINING SAFETY FUNCTION AND PLTB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding to PL or TB Justification/Action J ustifi ca ti on/Action

M0-2169 Boric Acid Gravity Feed PL & TB Valve has 4% margin .based on Valve .6T of 25° Fis below the lsolatiori COMED Analysis Method. See threshold for thermal binding of flex I

Attachment 2 for Inputs. wedge gate valves. The valve is heat

' "

traced and maintains a temperature of 165 ° F +/-5 °. Low alarm set point is 145° F.

M0-2170 Boric Acid Gravity Feed PL'& TB Valve has 21 % margin based on Valve .6T of 25° F is below the Isolation COMED Analysis Method. See threshold for thermal binding of flex Attachment 2 for Inputs. wedge gate valves. The valve is heat traced and maintains a temperature of 165° F +/-5°. Low alarm set point is 145° F.

M0-2140 Boric Acid Gravity Feed PL&TB Valve has 31% margin based.on Valve .6T of 25° Fis below the Isolation COMED Analysis Method. See threshold for thermal binding of flex Attachment 2 for Inputs. wedge gate valves. The valve is heat traced and maintains a temperature of

'

165° F +/-5°. Low alarm set point is 145° F.

CV-3018 HPSI T;rain Cross Connect N/A Valve is normally closed and has no Valve is normally closed and has no Isolation active safety function to open. active safety function to open.

M0-3190 LPSI Pump P-678 Shutdown N/A Excluded from scope of NRC GL 95- Excluded from scope of NRC GL 95-Cooling Inlet Isolation 07 based on Palisades being a Hot 07 based on Palisades being a Hot Shutdown Plant. Shutdown Plant.

M0-3199 LPSI Pump P-67 A Shutdown N/A Excluded from scope of NRC GL 95- Excluded from scope of NRC GL 95-Cooling Inlet Isolation 07 based on Palisades being a Hot 07 based on Palisades being a Hot Shutdown Plant. Shutdown Plant.

6

ATTACHMENT 1 TABLE~ VALVE LIST CONTAINING SAFETY FUNCTION AND PL TB SUSCEPTIBILITY Tag No. Description Susceptible Pressure Locking Thermal Binding

'

to PL or TB Justification/Action Justification/Action

'

M0-3015 PCS to Shutdown Cooling N/A Excluded from scope of NRC GL 95- Excluded from scope of NRC GL 95-Isolation 07 based on Palisades being a Hot 07 based on Palisades being a Hot Shutdown Plant. Shutdown Plant.

M0-3016 PCS to Shutdown Cooling N/A Excluded from scope of NRC GL 95- Excluded from scope of NRC GL 95-Isolation 07 based on Palisades being a Hot 07 based on Palisades being a Hot

Shutdown Plant. Shutdown Plant.

CV-3029 Containment Sump Isolation N/A Valve does have an active safety The. Containment Sump Valves are function to open. However, the valve only opened for surveillance testing disc is a solid wedge design which is during cold shutdown and then not susceptible to an occurrence of reclosed. The valves are not closed pressure IOc_king. hot. Additionally, the valves are insulated by a column of water between the valves and the Containment Sump so they will not experience large thermal transients.

CV-3030 Contai~ment Sump Isolation N/A Valve does have an active safety The Containment Sump Valves are function to open. However, the valve only opened for surveillance testing disc is a solid wedge design which is during cold shutdown and then not susceptible to an occurrence of . reclosed. The valves are not closed pressure locking. hot. Additionally, the valves are insulated by a c_olumn of water between the valves and the Containment Sump so they will not experience large thermal transients.

Note 1: During implementation of the Palisades AOV Program, CV-0939, Shield Cooling Surge Tank Inlet Valve, was verified as a globe valve. The Plant Equipment Data Base has been updated to reflect the proper valve type. The original submittal included this valve in the scope of safety related power operated gate valves. Additionally, the Palisades AOV Program has not found any other valves that were classified as globe valves that should have been gate valves.

7

ATTACHMENT 2 CONSUMERS ENERGY COMPANY PALISADES PLANT DOCKET 50-255 SUPPLEMENTAL INFORMATION- GENERIC LETTER 95-07 "PRESSURE LOCKING AND THERMAL BINDING OFSAFETY-RELATED POWER-OPERATED GATE VALVES" INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS 3 Pages

..

ATTACHMENT 2 INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS The following inputs and assumptions were used in the COMED methodology calculations for determining the additional forces needed to unwedge a pressure locked valve (Reference Palisades Engineering Analysis EA-PLTB-00). These calculations form the basis for determining the available MOV margin as reported in Attachment 1. The differences between the available margin reported in this submittal and the margir(in the original 180 day submittal are as follows:

1. The original calculation used the Entergy Methodology and now the COMED Methodology is used. The methodology change reflects industry feedback on the validity

.of the two calculational methods.

2. There is an additional 20% margin added to the disc pullout forces to account for future changes in this force. The original calculations included the appropriate VOTES diagnostic accuracy assumptions, but this additional 20% is added to assure that future changes due to different torque switch trip settings do not create a need to revise the PL TB Calculations.
3. The original calculations used a generic 0.5 valve factor. This was revised to be consistent with the valve factor assumption used for NRC Generic Letter 89-10. The new valve factors for M0-2140, 2160, 2169 and 2170 are 0.8.

M0-2140, MO- 2160 Assumptions:

1. The maximum pressure in the bonnet is assumed to be the highest pressure seen from upstream and downstream sources. The upstream and downstream pressures are conservatively set equal to 0.0 psi at the time of valve opening. This represents the worst possible scenario.
2. An additional 20% margin (on top of diagnostic accuracy) is conservatively included for the measured pullout thrust values to provide for future variances in actual pullout values. *
3. The valves are 3", 150#, Velan flex wedge gate valves. Conversations with Velan revealed that Velan uses a 1500# class valve body for all pressure classes. As such, it is expected that the valve body/disc are indeed stiff and there is not a concern of the valve body stretching due to the bonnet pressure and the disc traveling further into the seat.

As such, additional pinching_of the v~lve disc due to this phenomena is not considered in the pressure locking calculations. These are forged valves and typically* the forging process results in a thicker (and therefore more stiff) material than a cast valve. The stiffness of the valve body and disc should preclude any significant pinching effect.

I 1

.

,.

ATTACHMENT 2 INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS Inputs:

Upstream Pressure 0 psi Modulus of Elasticity 29X10 6 psi Downstream Pressure 0 psi Disc Center to Hub Edge 0. 736 Bonnet Pressure 120 psi Disc Thickness 0.761 in.

Valve Disc Wedge 8° 50 Valve Factor 0.8 Structural Thrust Limit 22,894 lbf Hub Length 1 in.

Mean Seat Radius 1.281 in. Disc Coefficient of Friction 0.857 Stem Diameter 1.121 in. Poisson's ratio (disc) 0.27 Required Unseating Forces:

Pressure Locking Force: 441.7 lbf Piston Effect: -118.4 lbf Reverse Piston Effect: 107.8 lbf Pullout Thrust (M0-2140): 4800 lbf Pullout Thrust (M0-2160): 3000 lbf Total Required Force: Motor Gearing Capability:

M0-2140 5231.1 lbf M0-2140 6877 lbf M0-2160 3431.1 lbf M0-2160 6218 lbf Margin:

M0-2140 31.4%

M0-2160 81.2%

M0-2169, M0-2170 Assumptions:

1. The maximum pressure in the bonnet is assumed to be the highest pressure seen from upstream and downstream sources. The upstream and downstream pressures are conservatively set equal to 0.0 psi at the time of valve opening. This represents the worst possible-scenario.
2. An additional 20% margin (on top of diagnostic accuracy) is conservatively included for the measured pullout thrust values to provide for future variances in actual pullout values. '
3. The valves are 4", 150#, Velan flex wedge gate valves. Conversations with Velan revealed that Velan uses a 1500# class valve body for all pressure classes. As such, it is expected that the valve body/disc are indeed stiff and there is not a concern of the valve body stretching due to the bonnet pressure and the disc traveling further into the seat.

2

i ATTACHMENT 2 INPUT AND ASSUMPTIONS TO PRESSURE LOCKING CALCULATIONS As such, additional pinching of the valve disc due to this phenomena is not con.sidered in the pressure locking calculations. These are forged valves and typically the forging process results in a thi_cker (and therefore more stiff) material than a cast valve. The stiffness of the valve body and disc should preclude any significant pinching effect.

Inputs:

Upstream Pressure 0 psi Modulus of Elasticity 29X106 psi

  • Downstream Pressure 0 psi Disc Center to Hub Edge 1.25 Bonnet Pressure 120 psi Disc Thickness 0.941 in."

Valve Disc Wedge 8° 50 Valve Factor 0.8 Structural Thrust Limit 31,566 lbf Hub Length 1 in.

Mean Seat Radius 1.859 in. Disc Coefficient of Friction 0.857 Stem Diameter 1.37 in. Poisson's ratio (disc)

  • 0.27 Required Unseating Forces:

Pressure Locking Force: 698.5 lbf Piston Effect: -176.8 lbf Reverse Piston Effect: 227.1 lbf Pullout Thrust (M0-2169): 5025 lbf Pullout Thrust (M0-2170): 4570 lbf Total Required Force: Motor Gearing Capability:

M0-2169 5773.8 lbf M0-2169 6022 lbf M0-2170 5318.8 lbf M0-2170 6444 lbf

  • Margin:

M0-2169 4.3%

M0-2170 21.1%

As noted earlier, the apparent low margin in M0-2169 is largely a function of the additional 20% margin that was added to the pullout forces. If the additional 20%

conservatism is-neglected,-then the actualmargin for M0-2169 is 21. 9%.

Conclusion:

All valves have adequate margin to open under the assumed pressure locking conditions.

3