Finding | |
|---|---|
| Title | |
| Description | A self-revealing finding (FIN) was identified for the licensees failure to adequately evaluate historically high vibrations on the Unit 1 Reactor Protection System (RPS) Motor Generator (M-G) Set 1B. Consequently, the impact of high vibrations was not considered in the determination of an adequate preventive maintenance frequency to ensure proper wire and cable terminal tightness in the RPS M-G Set control panel. The failure to ensure proper wire and cable tightness resulted in a loss of all Technical Specifications required reactor coolant system (RCS) leak detection. The licensee replaced the voltage regulator and performed all required tightness checks on RPS M-G Set 1B. In addition, the licensee verified appropriate tightness checks were scheduled in the next component outage window for the remaining M-G sets, and initiated actions to increase the preventive maintenance (PM) frequency to every two years, perform a design review to relocate the control panel, and evaluate the vibration program alert limit evaluation process. This issue was entered into the licensees corrective action program as problem evaluation report (PER) 412934. The finding was determined to be more than minor because it was associated with the Barrier Integrity Cornerstone attribute of RCS Equipment and Barrier Performance, and adversely affected the cornerstone objective to provide reasonable assurance that physical design barriers (reactor coolant system) protect the public from radionuclide releases caused by accidents or events. Specifically, the failure to ensure proper wire and cable tightness resulted in loose connectors and/or cable assemblies that caused the failure of the Unit 1 RPS M-G Set 1B which resulted in a loss of all Unit 1 RCS leakage detection systems and an unplanned power reduction on August 6, 2011. The significance of the finding was evaluated using Phase 1 of the SDP in accordance with the IMC 0609 Attachment 4, and was determined to be of very low safety significance (Green) because the finding did not represent a pressurized thermal shock, fuel barrier, or spent fuel pool issue. The cause of this finding was directly related to the cross-cutting aspect of Long Term Plant Safety Through Proper Maintenance Practices in the Resources component of the Human Performance area, because the vibration issues associated with Unit 1 RPS M-G Set 1B had been a long-standing equipment issue that was not adequately addressed by the vibration program alert limit evaluation process H.2(a). |
| Site: | Browns Ferry |
|---|---|
| Report | IR 05000259/2011005 Section 4OA3 |
| Date counted | Dec 31, 2011 (2011Q4) |
| Type: | Finding: Green |
| cornerstone | Barrier Integrity |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71153 |
| Inspectors (proximate) | C Kontz C Stancil E Guthrie L Pressley P Niebaum R Baldwin T Ross |
| CCA | H.6, Design Margins |
| INPO aspect | WP.2 |
| ' | |
Finding - Browns Ferry - IR 05000259/2011005 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|