ULNRC-06401, Attachment 4 - Revised Technical Specification Pages

From kanterella
Jump to navigation Jump to search

Attachment 4 - Revised Technical Specification Pages
ML18068A690
Person / Time
Site: Callaway Ameren icon.png
Issue date: 03/09/2018
From:
Ameren Missouri, Union Electric Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML18068A685 List:
References
ULNRC-06401, CAC MF8118, CAC MF8119
Download: ML18068A690 (6)


Text

Attachiient 4 to ULNRC-0640 I Page 1 of 6 ATTACHMENT IV REVISED TECHNICAL SPECIFICATION PAGES to ULNRC-06401 Class IE Electrical Equipment Air Conditioning (A/C) System Page2of6 3.7.20 TABLE OF CONTENTS 3.7 PLANT SYSTEMS 3.7-I 3.7.1 Main Steam Safety Vakes (MSSVs) 3.7-1 3.7.2 Main Steam Isolation Valves (MSIVs) and MSIV Bypass Valves 3.7-5 3.7.3 Main Feedwater Isolation Valves (MFIVs) and Main Feedwater Regulating Valves (MFRVs) and MFRV Bypass Valves 3.7-9 3.7.4 Atmospheric Relief Valves (ARVs) 3.7-13 3.7.5 Atixiliary Feedwater (AFW) System 3.7-15 3.7.6 Condensate Storage Tank (CST) 3.7-1 $

3.7.7 Component Cooling Water (CCW) System 3.7-20 3.7.8 Essential Service Water System (ESW) 3.7-22 3.7.9 Ultimate Heat Sink (UI-IS) 3.7-24 3.7.10 Control Room Emergency Ventilation System (CREVS) 3.7-26 3.7.11 Control Room Air Conditioning System (CRACS) 3.7-29 3.7.12 Emergency Core Cooling System (ECCS) Pump Room Exhaust Air Cleanup System Not Used 3.7-32 3.7.13 Emergency Exhaust System tEES) 3.7-33 3.7.14 Penetration Room Exhaust Air Cleanup System (PREACS)

Not Used 3.7-37 3.7.15 Fuel Storage Pool Water Level 3.7-38 3.7.16 Fuel Storage Pool Boron Concentration 3.7-39 3.7.17 Spent Ftiel Assembk Storage 3.7-41 3.7.18 Secondary Specific Activity 3.7-43 3.7.19 Secondary System Isolation Valves (SSIVs) 3.7-44 3.7.20 Class I E Electrical Eqtiipment Air Conditioning (A/C) System 3.7-46 3.8 ELECTRiCAL POWER SYSTEMS 3.8-1 3.8.1 AC Sources Operating 3.8-I 3.8.2 AC Sources Shutdown 3.8-18 3.8.3 Diesel fuel Oil, Ltibe Oil, and Stailing Air 3.8-21 3.8.4 DC Sotirces Operating 3.8-24 3.8.5 DC Sources Shutdown 3.8-28 3.8.6 Battery Cell Parameters 3.8-30 3.8.7 Inveilers Operating 3.8-34 3.8.8 Inverlers Shutdown 3.8-35 3.8.9 Distribution Systems Operating 3.8-37 3.8.10 Distribution Systems Shutdown 3.8-39 3.9 REFUELING OPERATIONS 3.9-I 3.9.1 Boron Concentration 3.9-1 3.9.2 Unborated Water Source Isolation Valves 3.9-2 3.9.3 Nuclear Instrumentation 3.9-3 3.9.4 Containment Penetrations 3.9-5 3.9.5 Residtial Heat Removal (RHR) and Coolant Circulation High Water Level 3.9-7 3.9.6 Residual Heat Removal (RHR) and Coolant Circulation Low Water Level 3.9-9 to ULNRC-0640 I Class I E Electrical Equipment Air Conditioning (A/C) System Page 3 of 6 3.7.20 3.7 PLANT SYSTEMS 3.7.20 Class IE Electrical Equipment Air Conditioning (A/C) System LCO 3.7.20 Two Class 1 E electrical equipment A/C trains shall be OPERABLE.

APPLICABILITY: MODES 1. 2, 3, and 4.

ACTI ONS CONDITION REQU IRED ACTION COMPLETION TIME A. One Class I E electrical A. I Initiate action to Immediately equipment A/C train implement iii itigating inoperable, actions.

AND A.2 Verify room area I hour temperatures 90°f.

AND Once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> thereafter AND A.3 Restore Class I E electrical 30 days equipment A/C train to OPERABLE status.

B. Required Action and B.l Be in MODE 3. 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition A not AND met.

B.2 Be in MODE 5. 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> C. Two Class IE electrical C.I Enter LCO 3.0.3. Immediately equipment AJC trains inoperable.

(continued) to ULNRC-06401 Class IE Electrical Equipment Air Conditioning (A/C) Sstem Page 4 of 6 3.7.20 SURVEILLANCE_REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.20.1 Verii each Class I E electrical equipment A/C train In accordance with actuates on an actual or simulated actuation signal. the Surveillance Frequency Control Program SR 3.7.20.2 Verify each Class I E electrical equipment A/C train has In accordance with the capability to remove the assumed heat load. the Surei1lance Frequency Control Program to ULNRC-06401 Class I E Electrical Equipment Air Conditioning (A/C) System Page 5 of 6 3.720 Programs and Manuals 5.5 Programs and Manuals 5.5.11 Ventilation filter Testing Program (VFTP) (continued)

e. Demonstrate at least once per 12 months that the heaters for each of the ESF systems dissipate the value specified below when tested in accordance with ANSI 510-1975 and corrected to design nameplate voltage settings.

ESF Ventilation System Wattage Control Room Pressurization 5 + I KW Emergency Exhaust System 37 + 3 1KW The provisions of SR 3.0,2 and SR 3.0.3 are applicable to the VFTP test frequencies.

5.5.12 Explosive Gas and Storage Tank Radioactivity Monitoring Program This program provides controls for potentially explosive gas mixtures contained in the Gaseous Radwaste System. the quantity of radioactivity contained in gas storage tanks and the quantity of radioactivity contained in unprotected outdoor liqtiid storage tanks. The gaseous radioactivity quantities shall be determined following the methodology in Branch Technical Position (BTP) ETSB 11-5.

Postulated Radioactive Release due to Waste Gas System Leak or Failure.

Revision 0. The liquid radwaste quantities shall be determined in accordance with Standard Review Plan. Section 15.7.3. Postulated Radioactive Release due to Tank failures. Revision 2.

The program shall include:

a. The limits for concentrations of hydrogen and oxygen in the Gaseous Radwaste System and a surveillance program to ensure the limits are maintained. ScLch limits shall be appropriate to the systems design criteria (i.e., whether or not the system is designed to withstand a hydrogen explosion);
b. b. A surveillance program to ensure that the quantity of radioactivity contained in each gas storage tank is less than the amount that would result in a whole body exposure of? 0.5 rem to any individual in an unrestricted area.

in the event of an uncontrolled release of the tanks contents; and to ULNRC-06401 Class I E Electrical Equipment Air Conditioning (A/C) System Page6of6 3.7.20

c. A surveillance program to ensure that the quantity of radioactivity contained in the outdoor liquid radwaste tanks listed below that are not (continued)

CALLA WAY PLANT 5.0-16 Amendment No. 215 I