Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML17317B093 + (21:59:32, 7 January 2025)
- ML17317B091 + (21:59:33, 7 January 2025)
- ML17317B088 + (21:59:34, 7 January 2025)
- 05000315/LER-1979-018-03, /03L-0 on 790310:root Valve for Lower Containment Pressure Transmitter PPP-300 Was Found in Closed Position. Cause Unknown.Valve Was Immediately Opened,Restoring Loop to Operable Status + (21:59:36, 7 January 2025)
- 05000315/LER-1979-018, Forwards LER 79-018/03L-0 + (21:59:39, 7 January 2025)
- ML17317B083 + (21:59:41, 7 January 2025)
- ML17317B076 + (21:59:42, 7 January 2025)
- ML17317B081 + (21:59:42, 7 January 2025)
- ML17317B075 + (21:59:43, 7 January 2025)
- ML17317B074 + (21:59:44, 7 January 2025)
- ML17317B073 + (21:59:45, 7 January 2025)
- 05000315/LER-1979-017-03, /03L-0 on 790312:spent Fuel Pit Exhaust Ventilation Unit Flow Failed to Meet Acceptance Criteria. Caused by Slight Closing of Intake Grills Due to Sys Vibration.Grill Damper Linkage Securely Fastened + (21:59:46, 7 January 2025)
- 05000315/LER-1979-016-03, /03L-0 on 790304:two Manual Containment Isolation Valves Were Inadvertantly Left Open Following Routine Sample of Instrument Room.Caused by Personnel Oversight.Both Valves Were Returned to Their Normally Closed Positions + (21:59:48, 7 January 2025)
- ML17317B067 + (21:59:49, 7 January 2025)
- 05000316/LER-1979-010-03, /03L-0 on 790306:during Surveillance Test on Turbine Driven Auxiliary Feed Pump,Pump Was Over Max Recommended Temp.Possible Cause Was Foreign Matl in Bearing Oil.Oil Was Changed + (21:59:52, 7 January 2025)
- 05000316/LER-1979-010, Forwards LER 79-010/03L-0 + (21:59:56, 7 January 2025)
- 05000316/LER-1979-009-03, /03L-0 on 790303:2W Svc Water Pump Amp Pegged Meter Stopped,Constituting Inoperable Pump.Caused by Burr Formed Between Impeller Ring & Bowl.Pump Shaft & Bowl Replaced + (22:00:00, 7 January 2025)
- 05000316/LER-1979-009, Forwards LER 79-009/03L-0 + (22:00:01, 7 January 2025)
- ML17317B059 + (22:00:03, 7 January 2025)
- ML17317B054 + (22:00:04, 7 January 2025)
- ML17317B057 + (22:00:04, 7 January 2025)
- ML17317B052 + (22:00:06, 7 January 2025)
- ML17317B053 + (22:00:06, 7 January 2025)
- 05000315/LER-1979-015-03, /03L-0 on 790302:while Operating at Full Power, Pressurizer Relief Tank Rupture Disc Blew Out,Causing Ice Condenser Inlet Doors to Open.Caused by Pressure Fluctuations Resulting in Weakened Rupture Discs + (22:00:08, 7 January 2025)
- 05000315/LER-1979-014-03, /03L-0 on 790301:while in Mode 1,indicated Position of Rod F-6 Discovered to Be Oscillating within 15 Steps of Bank Demand Position.Caused by Signal Conditioning Module Connector.Cleaning & Reinstallation Corrected Limits + (22:00:09, 7 January 2025)
- 05000315/LER-1979-014, Forwards LER 79-014/03L-0 & 79-015/03L-0 + (22:00:11, 7 January 2025)
- 05000316/LER-1979-008-03, /03L-0 on 790303:main Turbine Stop Valve C Closure Limit Switch Failed Conservatively (Closure Indication Received).Cause Unknown.Switch Replaced + (22:00:13, 7 January 2025)
- 05000316/LER-1979-008, Forwards LER 79-008/03L-0 + (22:00:14, 7 January 2025)
- ML17317B043 + (22:00:16, 7 January 2025)
- ML17317B042 + (22:00:17, 7 January 2025)
- ML17317B041 + (22:00:18, 7 January 2025)
- ML17317B039 + (22:00:19, 7 January 2025)
- ML17317B038 + (22:00:20, 7 January 2025)
- ML17317B037 + (22:00:20, 7 January 2025)
- ML17317B035 + (22:00:21, 7 January 2025)
- 05000315/LER-1979-013-03, /03L-0 on 790303:auxiliary Feed Valve FMO-212 Would Not Shut from Control Room.Caused by Broken Wire in Valves Motor Operator.Breakage Is a Result of Vibration & Use of Solid Conductor Wire.Wire Replaced + (22:00:23, 7 January 2025)
- 05000315/LER-1979-012-03, /03L-0 on 790226:containment Air Monitor Pump Overheated.Caused by Worn Rubber Spider in Lovejoy L-100 Coupling.Spider Replaced & Air Sampler Retested + (22:00:24, 7 January 2025)
- 05000315/LER-1979-011-03, /03L-0 on 790223:auxiliary Feedwater Discharge Valve Would Not Close from Control Room.Caused by Loose Connection in Hot Shutdown Panel.Connection Tightened & Correct Valve Operation Verified + (22:00:26, 7 January 2025)
- ML17317B028 + (22:00:28, 7 January 2025)
- ML17317B023 + (22:00:29, 7 January 2025)
- IR 05000315/1979001 + (22:00:30, 7 January 2025)
- ML17317B017 + (22:00:32, 7 January 2025)
- ML17317B014 + (22:00:32, 7 January 2025)
- ML17317B012 + (22:00:33, 7 January 2025)
- ML17317B011 + (22:00:34, 7 January 2025)
- ML17317B009 + (22:00:34, 7 January 2025)
- ML17317B008 + (22:00:35, 7 January 2025)
- 05000315/LER-1979-009-03, /03L-0 on 790223:in Mode 1 Both Emergency Diesel Generators Were Inoperable on Separate Occasions.Caused by AB Diesel Generator Running in Parallel & Other Emergency Generator Out for Maint.Operating Procedures Revised + (22:00:37, 7 January 2025)
- 05000315/LER-1979-008-03, /03L-0 on 790207:containment Atmospheric Air Particulate & Gaseous Radiation Monitoring Sys Pump Was Continuously Tripping.Caused by Misalignment of Pump Bypass Flow Adjustments Due to Normal Pump Wear.Flow Rate Adjusted + (22:00:38, 7 January 2025)
- 05000315/LER-1979-007-03, /03L-0 on 790218:suction Valve of West Centrifugal Charging Pump Found Closed.Caused by Mistaken Closing Following Surveillance Testing.Incident Is Being Reviewed + (22:00:40, 7 January 2025)
- ML17317B003 + (22:00:41, 7 January 2025)