- 05000348/LER-1980-002, Forwards LER 80-002/03L-0 & 80-004/03L-0 + (17:25:02, 3 January 2025)
- 05000346/LER-1980-005-03, /03L-0:on 800110,Tech Spec Late Date Passed W/O Performance of Boric Acid Flowpath Heat Tracing Weekly Test. Caused by Known Deficiency in Design of Sys Resulting in Inability to Maintain Min Temp Necessary During Startup + (17:25:05, 3 January 2025)
- 05000317/LER-1980-003-03, /03L-0:on 800108,during Routine Containment Air Lock Surveillance,Emergency Escape Lock Leakage Found Greater than Allowed.Caused by Excessive Leaking of Packing Glands for Doors Handwheels.Packing Tightened + (17:25:09, 3 January 2025)
- 05000267/LER-1980-003, Forwards LER 80-003/03L-0 + (17:25:11, 3 January 2025)
- 05000346/LER-1980-005, Forwards LER 80-005/03L-0 + (17:25:15, 3 January 2025)
- ML19260D990 + (17:25:16, 3 January 2025)
- 05000317/LER-1980-003, Forwards LER 80-003/03L-0 + (17:25:19, 3 January 2025)
- 05000338/LER-1980-012-03, /03L-0:on 800111,during Testing in Mode 3 to Verify Main Steam Trip Valve Closure Time,Trip Valve Failed to Close Fully within Required Five Seconds.Cause Unknown. Valve Was Retested.Closure Time within Acceptable Limits + (17:25:21, 3 January 2025)
- 05000295/LER-1980-001-03, /03L-0:on 800103,while in Cold Shutdown,Spent Fuel Bldg Area Monitor ORE-0005 Failed full-scale High.Failure Due to Normal End of Life.Tube Replaced & Monitor Functionally Tested & Returned to Svc + (17:25:24, 3 January 2025)
- ML19260D984 + (17:25:25, 3 January 2025)
- 05000338/LER-1980-012, Forwards LER 80-012/03L-0 + (17:25:27, 3 January 2025)
- 05000295/LER-1980-001, Forwards LER 80-001/03L-0 + (17:25:29, 3 January 2025)
- ML19260D979 + (17:25:32, 3 January 2025)
- 05000272/LER-1980-002-03, /03L-0:on 800104,discovered That Functional Tests of Power Range Neutron Flux Low Trip Setpoint When Greater than 25% Power Had Not Been Performed Since 1976.Caused by Lack of Procedures for Tests + (17:25:34, 3 January 2025)
- 05000285/LER-1980-004-01, /01T-0:on 800126,while Fire Barrier Inside Empty Breaker Cubicle Was Degraded to Pull in New Cabling,Fire Watch Was Not Maintained Continuously.Caused by Fire Watch Not Receiving Accurate Info on Status of Barrier + (17:25:36, 3 January 2025)
- ML19260D976 + (17:25:38, 3 January 2025)
- 05000318/LER-1980-002-03, /03L-0:on 800107,refueling Water Tank Narrow Range Level Indicator Was in Alarm W/Low Level,But Instrument Did Not Indicate Alarm Conditions.Caused by Faulty Indicator Alarm light-emitting Diode.Diode Replaced + (17:25:40, 3 January 2025)
- ML19260D974 + (17:25:42, 3 January 2025)
- 05000267/LER-1980-005-03, /03L-0:on 800111,during Release from Gaseous Waste Holdup Sys,Recorder Did Not Function Properly.Caused by Bad Bull Drive Gear & Clutch Assembly.Parts Replaced & Recorder Returned to Operation + (17:25:44, 3 January 2025)
- 05000318/LER-1980-002, Forwards LER 80-002/03L-0 + (17:25:49, 3 January 2025)
- ML19260D970 + (17:25:51, 3 January 2025)
- 05000338/LER-1980-015-03, /03L-0:on 800116,during Reactor Physics Testing Following Refueling Outage,Reactor Was Critical W/Rcs Tavg Under 541 F.Caused by Cooldown While Attempting to Maintain RCS Temp During Testing.Heat Release Valve Closed + (17:25:53, 3 January 2025)
- ML19260D967 + (17:25:54, 3 January 2025)
- ML19260D966 + (17:25:55, 3 January 2025)
- 05000338/LER-1980-015, Forwards LER 80-015/03L-0 + (17:25:57, 3 January 2025)
- 05000267/LER-1980-005, Forwards LER 80-005/03L-0 + (17:25:59, 3 January 2025)
- 05000280/LER-1980-007-03, /03L-0:on 800116,during Normal Operation,Heat Tracing Circuit 4 on Line 1-CH-56-152,boric Acid Supply to Blender Failed.Caused by Water Penetration of Heat Tracing Tape.Tape Replaced W/Higher Water Resistant Tape + (17:26:01, 3 January 2025)
- ML19260D959 + (17:26:03, 3 January 2025)
- ML19260D960 + (17:26:03, 3 January 2025)
- ML19260D958 + (17:26:05, 3 January 2025)
- 05000280/LER-1980-006-03, /03L-0:on 800115,during Routine Surveillance of Liquid Waste Release,Discovered That Unsampled Waste from Tank 5A Was Being Pumped to Tank 5B.Caused by Inadvertent Operation of Transfer Pump.Waste Release Terminated + (17:26:06, 3 January 2025)
- ML19260D956 + (17:26:08, 3 January 2025)
- 05000309/LER-1980-002-03, /03L-0:on 800108,during Surveillance Testing of Containment Personnel hatch,O-ring Seal on Inner Door Found Leaking excessively.O-rings Replaced + (17:26:10, 3 January 2025)
- 05000309/LER-1980-002, Forwards LER 80-002/03L-0 + (17:26:13, 3 January 2025)
- 05000280/LER-1980-005-03, /03L-0:on 800120,while Conducting PT 27D Heat Tracing Sys,Discovered That Circuit 17A Panel 9 Was Inoperative.Caused by Thermostat Failure.Maint Rept Initiated.Defective Thermostat Replaced + (17:26:15, 3 January 2025)
- ML19260D942 + (17:26:17, 3 January 2025)
- ML19260D945 + (17:26:17, 3 January 2025)
- ML19260D941 + (17:26:18, 3 January 2025)
- ML19260D940 + (17:26:19, 3 January 2025)
- ML19260D939 + (17:26:20, 3 January 2025)
- ML19260D938 + (17:26:21, 3 January 2025)
- ML19260D935 + (17:26:22, 3 January 2025)
- ML19260D937 + (17:26:22, 3 January 2025)
- ML19260D934 + (17:26:23, 3 January 2025)
- ML19260D932 + (17:26:25, 3 January 2025)
- 05000285/LER-1980-004, Forwards LER 80-004/01T-0 + (17:26:27, 3 January 2025)
- ML19260D930 + (17:26:28, 3 January 2025)
- ML19260D927 + (17:26:32, 3 January 2025)
- ML19260D925 + (17:26:37, 3 January 2025)
- ML19260D923 + (17:26:37, 3 January 2025)
- ML19260D922 + (17:26:40, 3 January 2025)