- JPN-92-001, Responds to Diagnostic Evaluation Team Rept,Provided Via NRC .Five Major Initiatives Will Be Undertaken Re Capital Improvements,Mgt Changes,Engineering Organizational Changes & Nuclear Generation Business Plan + (06:46:01, 26 May 2025)
- TXX-9130, Final Deficiency Rept CP-90-07 Re Safeguards Bldg Overtemp Condition.Initially Reported on 900608.Unit 1 Design Mods Incorporated Into Unit 2 Piping Insulation Spec + (06:46:03, 26 May 2025)
- 05000272/LER-1981-059, Supplemental LER 81-059/01X-01:on 810616,during Initial Testing,Auxiliary Feedwater Pump 23 Turbine Steam Supply Check Valves 21MS46 & 23MS46 Found Damaged Internally.Caused by Steam Flow Sys Oscillations + (06:46:42, 26 May 2025)
- L-13-103, Rev 0 to Design Rept for Recirculation Sys Weld Overlay Repairs at Brunswick Steam Electric Plant Unit 1 + (06:47:27, 26 May 2025)
- ML20087A019 + (06:47:30, 26 May 2025)
- ML20086U403 + (06:48:15, 26 May 2025)
- TXX-9106, Advises That Arrangements Made to Conduct full-participation Emergency Field Exercise on 911119 + (06:49:42, 26 May 2025)
- TAC:M80872 + (06:50:08, 26 May 2025)
- 05000482/LER-1989-021, :on 911227,discovered That TS Surveillance Test Procedure STS BM-202 Had Not Been Performed Satisfactorily on 891115 Due to Procedural Inadequacy. Administrative Procedure Adm 02-300 Revised + (06:50:10, 26 May 2025)
- ML20086T483 + (06:50:45, 26 May 2025)
- ML20086T356 + (06:51:10, 26 May 2025)
- ML20086T228 + (06:51:35, 26 May 2025)
- ML20086T209 + (06:51:38, 26 May 2025)
- ML20086T037 + (06:52:00, 26 May 2025)
- ML20086S961 + (06:52:10, 26 May 2025)
- W3P84-0215, Forwards Public Version of Rev 6 to Emergency Plan & Rev 3 to Emergency Plan Implementing Procedures,Including Procedures EP-1-001 Re Recognition & Classification of Emergency Conditions & EP-1-020 Re alert.W/840301 Memo + (06:52:27, 26 May 2025)
- 05000364/LER-1984-002-01, Revised LER 84-002-01:on 840124,hourly Firewatch Patrol in Train B Auxiliary Bldg Battery Charger Room Not Performed at Specified Times.Caused by Personnel Error.Personnel Counseled & Firewatch Patrol Immediately Performed + (06:53:43, 26 May 2025)
- TAC:49741 + (06:54:40, 26 May 2025)
- ML20086R298 + (06:55:58, 26 May 2025)
- ML20086R000 + (06:56:23, 26 May 2025)
- 05000280/LER-1975-005-01, /01T:on 750214,pressurizer Pressure Comparator Found Out of Calibr.Caused by Component Failure of Hagan Computer Sys Model 118 Signal Comparator A56Y 4111082-001. Comparator Replaced + (06:56:37, 26 May 2025)
- 05000280/LER-1975-006-01, /01T:on 750215 & 19,channel 1 Overpower Setpoint Failed High.Caused Under Investigation.Low Level Amplifier TM-1-412A Replaced & Instrument Calibr Performed + (06:56:42, 26 May 2025)
- 05000280/LER-1975-006, Supplemental LER 75-06/010:on 750215,module S/N D401 Failed Due to Capacitor C-37 Being Open Circuit.Capacitors Replaced + (06:56:45, 26 May 2025)
- ML20086Q618 + (06:57:12, 26 May 2025)
- 05000327/LER-1995-009, :on 950624,rod Position Indication Was Out of Step W/Demand Position Indication Sys.Caused by Gap Between Actual Rod Position & RPI Response.Ts Was Entered & Shift Operations Supervisor Was Notified + (06:57:13, 26 May 2025)
- 05000280/LER-1975-008, Supplementary LER 75-08/01L on 750427.Previously Described Event Caused by Apparent Inadequate Implementation of Administrative Controls During Const & Preoperation. Administrative Control of Electrical Wire Changes Increased + (06:57:54, 26 May 2025)
- 05000293/LER-1981-009-03, Inboard Isolation Valve Failed to Open & HPCI Sys Declared Inoperable.Caused by Incorrect Min Torque Switch Setting of Motor Operator & Thermal Binding.Torque Switch Set at Max Value + (06:58:02, 26 May 2025)
- 05000259/LER-1983-029-03, During Standby Gas Treatment Sys Operability Test,Train B Discovered Inoperable.Caused by Erratic Mcdonnel & Miller Model AF-1 Flow Switches.Damper Adjusted.W/Undated Ltr + (06:58:28, 26 May 2025)
- ML20086N963 + (07:00:32, 26 May 2025)
- ML20086N898 + (07:00:36, 26 May 2025)
- A830001, Responds to NRC Re Violations Noted in IE Insp Rept 50-298/83-24.Corrective Actions:Class 350 UL-rated File Cabinets Ordered to Provide Adequate Fire Protection + (07:01:06, 26 May 2025)
- ML20086N234 + (07:01:19, 26 May 2025)
- ML20086M750 + (07:02:42, 26 May 2025)
- TAC:52663 + (07:02:49, 26 May 2025)
- 05000336/LER-1991-009, :on 910821,both EDGs Declared Inoperable.Caused by Load Swings Due to Oxidation Buildup on Relay Contacts. Governor Controls Sys on 12U DG & 13U DG Updated W/New Electronic Governor Actuator Controls + (07:03:00, 26 May 2025)
- TAC:47149 + (07:03:20, 26 May 2025)
- PMNS20200205, Meeting Announcement - Category 1 Public Meeting + (07:03:41, 26 May 2025)
- ML20086M006 + (07:03:44, 26 May 2025)
- ML20086L953 + (07:03:46, 26 May 2025)
- 05000336/LER-1994-020, :on 940722,determined That DG Fuel Oil Supply Less than IEEE Std.New Fuel Oil Consumption Calculation Performed Which Determines Length of Time DG Can Be Operated at Full Rated Capacity & TS Change Submitted + (07:05:20, 26 May 2025)
- ML20086K216 + (07:08:42, 26 May 2025)
- TAC:M72166 + (07:08:57, 26 May 2025)
- 05000461/LER-1990-003, :on 900212,13 Rosemount Transmitters Determined to Be Inoperable Due to Loose Covers & Broken Neck Seal. Completed Two Performances of PM Task to Verify Housing Cover Torque & Neck Seal Integrity + (07:10:23, 26 May 2025)
- 05000461/LER-1990-003-01, Forwards LER 90-003-01 Re 13 Rosemount Transmitters Being Inoperable Due to Loose Housing Covers & Broken Neck Seal. LER Revised to Update Info Provided,Including Licensee Contact,C/A & Maint Work Document Numbers + (07:10:27, 26 May 2025)
- TXX-9140, Supplemental Deficiency Rept CP-89-011 Re Pipe Support Defects Noted in Insp Rept 50-445/89-12.Initially Reported on 890824.General Policy Memo Issued Cautioning Against Damaging Installed Hardware + (07:12:11, 26 May 2025)
- ML20086G847 + (07:14:42, 26 May 2025)
- NG-75-1158, AO 50-261/75-14:on 750715,valve V2-14B Steam Driven Auxiliary Feedwater Pump Discharge to Steam Generator B Failed to Open.Caused by Belleville Spring Being Filled W/Grease.Belleville Spring Packs & Shafts to Be Inspected + (07:18:03, 26 May 2025)
- NG-75-1139, Summarizes Actions Taken Following AO 50-261/75-9 on 750501. Summaries of Repairs & Insps Performed During Forced Outage Given + (07:18:07, 26 May 2025)
- ML20086E311 + (07:20:24, 26 May 2025)
- ML20086E291 + (07:20:29, 26 May 2025)
- ML20086D804 + (07:21:40, 26 May 2025)