""""*"L'""!
Log # TXX-91464 File # 10110 Ref. # 10CFR50.55(e) ltlELECTRIC December 20, 1991 Wihm J. Cahlit. Jr.
Group \\ks President U. S. Nuclear Regulatory Commission Attn:
Document Control Desk Washingtcn, DC 20555 SUBJECTt COMANCHE PEAK STEAM ELECTRIC STATION (CPSES) - UNIT 4 DOCKET NO. 50-446 INCOMPLETE FUSION ON TUBE STEEL SEAM WELD SDAR CP 91-009 (INTERIM RLPORT)
Gentlemen:
On October 22. 1991 TU '.",r.tric identified a defect involving incomplete fusion ia the manufactutn seam weld on a tube steel member.
This is an interim report of a potentially reportable item under the provisions of 10CFR50.55(e).
l l
Specifically, on pipe support FW-2 020-700-C52R, incomplete fusion.was noted for approximately 17 inches on the inside seam of a 10"x10"x5/8" tube steel I
member.
This tube steel was from heat number C97278, was manufactured by Copperweld Tubing Group in January 1980, and was subsequently supplied by Hills Alloy Steel in March 1980.
The reportabiiity evaluation for this issue is continuing and is scheduled for completion or. June 24, 1992.
The next report on this issue will be submitted upon completion of the evaluation,
. Sincerely.
1 William J. Cahill, Jr.
t l
By:
'l) l D. R. Woodlan l
Docket Licensing Manager l
rtJ/vid c-Mr. R. D. Martin. Region IV Mr M. B. Fi el ds. !;:,R Resident Inspectors, CPSES (2) o 9112300265 911220 FDR ADOCK 05000446 l
Q s