Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19338F129 + (18:49:33, 25 December 2024)
- 05000313/LER-1980-032-04, /04L-0:on 800905,during Cooldown Following Steam Generator Tube Leak,Excessive Release of Radioactive Matls in Gaseous Wastes Occurred.Caused by Premature Lifting of Letdown Relief Valve PSV-1236.Valve Was Readjusted + (18:49:39, 25 December 2024)
- ML19338F124 + (18:49:45, 25 December 2024)
- 05000324/LER-1980-052, Forwards LER 80-052/03L-0 + (18:49:52, 25 December 2024)
- ML19338F121 + (18:49:54, 25 December 2024)
- ML19338F119 + (18:50:01, 25 December 2024)
- ML19338F118 + (18:50:02, 25 December 2024)
- 05000313/LER-1980-032, Forwards LER 80-032/04L-0 + (18:50:05, 25 December 2024)
- ML19338F115 + (18:50:07, 25 December 2024)
- 05000339/LER-1980-060-03, /03L-0:on 800913,in Mode 1,procedure 2-PT-62.4 Revealed That Leakage Past Outer Seals on Personnel Air Lock Door Exceeded Tech Specs.Caused by Misaligned Personnel Hatch on Outer Door + (18:50:10, 25 December 2024)
- 05000368/LER-1979-056, Forwards Updated LER 79-056/03X-1 + (18:51:19, 25 December 2024)
- ML19338F110 + (18:51:23, 25 December 2024)
- ML19338F109 + (18:51:25, 25 December 2024)
- 05000334/LER-1980-070-01, /01T-0:on 800922,unplanned Dilution of RCS Occurred.Caused by Boric Acid Blender Procedure Not Accounting for Manual Emergency Boration Flow Path Being in Svc.Procedure Has Been Changed + (18:51:28, 25 December 2024)
- 05000293/LER-1980-062-03, /03L-0:on 800903,following Surveillance Testing, a Diesel Generator Declared Inoperable Due to Snapped Fuel Line in Area of Diesel Generator Cylinder 9R.Caused by Severed Fuel Crossover T Type Connector + (18:51:40, 25 December 2024)
- 05000339/LER-1980-063-03, /03L-0:on 800920,during Performance of incore- Excore Detector Calibr Startup Test,Found Zero Point Shift of Delta T/T Avg Channel III Summing Amp.Cause Undetermined. Channel Placed in Trip & New Summing Amp Installed + (18:52:18, 25 December 2024)
- ML19338F104 + (18:52:21, 25 December 2024)
- 05000339/LER-1980-060, Forwards LER 80-060/03L-0 + (18:53:00, 25 December 2024)
- 05000334/LER-1980-070, Forwards LER 80-070/01T-0 + (18:53:40, 25 December 2024)
- 05000293/LER-1980-062, Forwards LER 80-062/03L-0 + (18:54:57, 25 December 2024)
- ML19338F094 + (18:55:00, 25 December 2024)
- 05000339/LER-1980-063, Forwards LER 80-063/03L-0 + (18:55:21, 25 December 2024)
- 05000339/LER-1980-061-03, /03L-0:on 800919,LHSI Pump B Relieve Valve Actuated at 190 Psia Rather than 220 Psia.Probably Caused by Weakened Spring Action Allowing Lower Pressure to Open Valve.Spring Tension Reset & Valve Returned to Svc + (18:55:51, 25 December 2024)
- 05000339/LER-1980-050-03, /03L-0:on 800902,during Mode 5,pressurizer power- Operated Relief Valve Was Inoperable When Nitrogen Supply Dropped.Caused by Low Nitrogen Pressure.Pressure Was Restored in 12-h by Renewing Supply & Pressurizing Tanks + (18:56:20, 25 December 2024)
- 05000285/LER-1980-022-03, /03L-0:on 800911,during Safety Injection Actuation Signal Surveillance test,86B/VIAS Lockout Failed to Trip. Caused by Burned Coil.Coil Replaced W/Spare & Tested Satisfactorily for Proper Operation + (18:56:44, 25 December 2024)
- ML19338F087 + (18:56:46, 25 December 2024)
- 05000254/LER-1980-022-03, /03L-0:on 800903,during Calibr Surveillance,Temp Switch TS 1-2371A Tripped at 212 F Rather than 200 F.Caused by Setpoint Drift.Switch Replaced + (18:57:04, 25 December 2024)
- ML19338F085 + (18:57:08, 25 December 2024)
- 05000346/LER-1980-069-03, /03L-0:on 800902,during Diesel Generator 1-1 Oil Change,Bolt Fragment Discovered in Crankcase Sump.Caused by Loose Bolts in Idler Gear to Support Spider of Turbocharger Spring Drive Assembly.Modified Assembly Installed + (18:58:26, 25 December 2024)
- 05000285/LER-1980-022, Forwards LER 80-022/03L-0 + (18:58:47, 25 December 2024)
- 05000339/LER-1980-061, Forwards LER 80-061/03L-0 + (18:58:57, 25 December 2024)
- 05000254/LER-1980-022, Forwards LER 80-022/03L-0 + (18:59:09, 25 December 2024)
- 05000339/LER-1980-050, Forwards LER 80-050/03L-0 + (18:59:27, 25 December 2024)
- ML19338F074 + (18:59:30, 25 December 2024)
- ML19338F072 + (18:59:33, 25 December 2024)
- 05000278/LER-1980-023-03, /03L-0:on 800908,reactor Water Cleanup Demineralizer Water Inlet Temp Switch Did Not Actuate at 200 F.Caused by Setpoint Drift.Switch Recalibr & Satisfactorily Tested + (18:59:52, 25 December 2024)
- ML19338F069 + (18:59:58, 25 December 2024)
- ML19338F067 + (18:59:59, 25 December 2024)
- 05000346/LER-1980-069, Forwards LER 80-069/03L-0 + (19:00:28, 25 December 2024)
- ML19338F064 + (19:00:32, 25 December 2024)
- 05000219/LER-1980-041-03, /03L-0:on 800905,core Spray Sys 2 Was Removed from Svc to Repair Leaking Vent Line on Core Spray Booster Pump D.Caused by Personnel Using Pipe as Foot Hold.Pipe Nipple Replaced & Sys Returned to Svc + (19:00:48, 25 December 2024)
- ML19338F062 + (19:00:52, 25 December 2024)
- ML19338F061 + (19:00:54, 25 December 2024)
- 05000219/LER-1980-041, Forwards LER 80-041/03L-0 + (19:00:57, 25 December 2024)
- 05000366/LER-1980-128, Advises That LER 80-128/03L-0 Issued on 800923 Should Be Disregarded & Replaced W/Ler Issued on 800925 + (19:01:01, 25 December 2024)
- ML19338F056 + (19:01:05, 25 December 2024)
- ML19338F055 + (19:01:09, 25 December 2024)
- 05000334/LER-1980-017, Updated LER 80-017/01T-1:on 800326,reanalysis of Piping & Supports for Main Steam Sys Outside Containment Revealed Design Deficiencies If All Five Safety Relief Valves Opened on Any Manifold.Caused by Load Resulting from Open V + (19:01:12, 25 December 2024)
- ML19338F053 + (19:01:14, 25 December 2024)
- 05000346/LER-1980-070-03, /03L-0:on 800828,during Weekly Diesel Fuel Pump Test ST 5016.01,diesel Fuel Pump Failed to Start at Required 95 Psig.Caused by Broken Pressure Switch.Switch Repaired & Recalibrated + (19:01:18, 25 December 2024)
- ML19338F051 + (19:01:22, 25 December 2024)