- 05000213/LER-1976-016-03, /03l-2:on 760705,auxiliary Feed Pump Failed to Develop Proper Discharge Pressure for Startup.Caused by Back Leakage from Steam Generator 3 Through Check Valve in Feed Line.Faulty Check Valve Removed,Cleaned & Repaired + (17:16:21, 24 December 2024)
- 05000213/LER-1976-004-04, /04L-1:on 760202,Jan 1976 Monthly Impingement Loss for Spottail Shiners Exceeded ETS Limits.No Corrective Action Taken + (17:16:23, 24 December 2024)
- 05000213/LER-1977-001-03, /03L-0:on 761214,small Leak Found at Juncture of Waste Liquid/Steam Generator Blowdown Line & Svc Water Effluent Line.Caused by Pipe Matl Deterioration from Steam Generator Blowdown Stream & Cold Svc Water Interaction + (17:16:26, 24 December 2024)
- 05000213/LER-1977-002-03, /03L-0:on 770224,leak Found at Recycle Test Tank a Manway.Caused by Corroded Aluminum Bolts & Nuts. Temporary Clamps Applied to Stop Leakage.Aluminum Nuts & Bolts Replaced W/Stainless Steel + (17:16:28, 24 December 2024)
- ML19343C260 + (17:16:29, 24 December 2024)
- 05000213/LER-1977-005-03, /03L-0:on 770404,decrease in Charging Pump Discharge Pressure & Increase in Motor Amperage Noted.Caused by Pump Shaft Circumferential Cracks Under Pressure Reducing Sleeve.Shaft & Pump Wear Rings Replaced + (17:16:31, 24 December 2024)
- 05000213/LER-1977-006-03, /03L-0:on 770426,while Filling & Venting Charging Pump 1A,small Weep Noted on Suction End Mechanical Seal Housing 1A.Caused by Small Leak Path Opened Through Slight Porosity During Decontamination of Housing.Housing Replaced + (17:16:33, 24 December 2024)
- 05000213/LER-1977-007-03, /03L-0:on 770428,inboard Motor Bearing Temp Increase Caused Charging Pump 1A to Be Shut Down.Caused by Excessive Thrust on Motor Bearing Thrust Plate Due to Axial Misalignment Between Pump & Motor.Bearings Replaced + (17:16:34, 24 December 2024)
- ML19343C256 + (17:16:35, 24 December 2024)
- 05000213/LER-1977-008-03, /03L-0:on 770523,containment Air Recirculation Fan 2 Vibration Exceeded Alarm Setpoints.Caused by Normal Wear. Bearing Replaced + (17:16:37, 24 December 2024)
- 05000213/LER-1977-009-03, /03L-0:on 770531,overhead Crane Control Malfunctioned,Lifting Spent Fuel Racks Approx 12 & 6 Inches. Caused by Button Stuck in Depressed Position Due to Mechanical Wear of Button Internal Mechanism.Button Replaced + (17:16:39, 24 December 2024)
- GO2-19-162, Amendment 65 to Final Safety Analysis Report, Chapter 12, Radiation Protection + (17:16:41, 24 December 2024)
- ML19343C252 + (17:16:43, 24 December 2024)
- ML19343C251 + (17:16:44, 24 December 2024)
- ML19343C250 + (17:16:45, 24 December 2024)
- ML19343C249 + (17:16:46, 24 December 2024)
- ML19343C248 + (17:16:47, 24 December 2024)
- ML19343C247 + (17:16:47, 24 December 2024)
- ML19343C246 + (17:16:48, 24 December 2024)
- ML19343C245 + (17:16:49, 24 December 2024)
- 05000213/LER-1978-001-01, /01T-0:on 780126,Marathon Terminal Blocks Failed in twenty-second Hour of Scheduled 24-h Screening Type Test to Show Ability to Function in Postulated Containment Environ After Loca.Caused by Current Path + (17:16:51, 24 December 2024)
- ML19343C242 + (17:16:52, 24 December 2024)
- ML19343C241 + (17:16:53, 24 December 2024)
- ML19343C240 + (17:16:54, 24 December 2024)
- 05000213/LER-1978-003-03, /03L-0:on 780317,leak Found at Junction of Waste Liquid/Steam Generator Blowdown Line & Svc Water Effluent Blowdown Line.Caused by Interaction of Hot Generator Blowdown & Cold Svc Water.Line Repaired & Pipe Extended + (17:16:56, 24 December 2024)
- ML19343C238 + (17:16:58, 24 December 2024)
- ML19343C237 + (17:16:59, 24 December 2024)
- ML19343C236 + (17:17:00, 24 December 2024)
- 05000213/LER-1978-005-03, /03L-0:on 780403,HPIS Pump a Dragged During Manual Operation to Check Coupling Alignment.Caused by Cracked Wear Rings & Impeller Bushing.All Rings & Bushings Replaced.Pump re-assembled,test Run & Found Acceptable + (17:17:01, 24 December 2024)
- ML19343C234 + (17:17:03, 24 December 2024)
- 05000213/LER-1978-004-01, /01T-0 Suppl:On 780427-28,significant Gas Generation & Pressure Buildup Found in Annular Poison Cavity in Spent Fuel Racks.Caused by Decomposition in B4C Plates &/Or Decomposition of Binder Matl Used w/B4C Plates + (17:17:05, 24 December 2024)
- ML19343C232 + (17:17:06, 24 December 2024)
- 05000213/LER-1978-007-03, /03L-0:on 780504,pinhole Leak Found in Pumps Discharge Recirculation Orifice Bypass Valve.Caused by Severe Erosion Due to Valve Design.Valve Replaced & Better Design Under Investigation + (17:17:08, 24 December 2024)
- ML19343C229 + (17:17:09, 24 December 2024)
- ML19343C230 + (17:17:09, 24 December 2024)
- ML19343C228 + (17:17:10, 24 December 2024)
- ML19343C227 + (17:17:10, 24 December 2024)
- ML19343C226 + (17:17:11, 24 December 2024)
- ML19343C224 + (17:17:12, 24 December 2024)
- ML19343C225 + (17:17:12, 24 December 2024)
- ML19343C223 + (17:17:13, 24 December 2024)
- ML19343C222 + (17:17:13, 24 December 2024)
- ML19343C220 + (17:17:14, 24 December 2024)
- ML19343C221 + (17:17:14, 24 December 2024)
- ML19343C218 + (17:17:15, 24 December 2024)
- ML19343C219 + (17:17:15, 24 December 2024)
- ML19343C217 + (17:17:16, 24 December 2024)
- 05000219/LER-1976-010-03, /03L-0:on 760401,during Pump Operability Test for Containment Spray Sys 2,torus Spray Valve V-21-15 Failed to Open.Caused by Misaligned Starter Contacts.Contacts Repositioned & Inspected + (17:17:17, 24 December 2024)
- ML19343C215 + (17:17:18, 24 December 2024)
- 05000219/LER-1976-012-03, /03L-0:on 760414,maint Personnel Discovered That Sensing Line to Flow Switch in Standby Gas Treatment Sys I Were Reversed & Switched out-of-calibr.Cause Unknown.Sensing Lines Oriented Properly & Switch Recalibr + (17:17:20, 24 December 2024)
- 05000219/LER-1976-017-01, /01P-0:on 760701,oxygen Concentration in Torus Reached Indicted Level of 5.4% Which Exceeded Tech Specs Limit.Caused by Erratic Behavior of Torus Oxygen Analyzer Following Calibr + (17:17:25, 24 December 2024)