- ML20065S605 + (00:03:36, 17 December 2024)
- ML20065S597 + (00:03:36, 17 December 2024)
- ML20065S595 + (00:03:38, 17 December 2024)
- 0CAN129001, Application for Amends to Licenses DPR-51 & NPF-6,revising TSs 6.9,6.13,6.10 & 6.12 to Delete Sections Re Environ Qualification in Order to Simplify Specs + (00:03:39, 17 December 2024)
- 05000445/LER-1990-041, :on 901119,protection Set Inverter IV1PC3 Not Operable within 24 H of Trip.Cause of Trip Attributed to Ac Voltage Transients,Inadequate Termination on Loose Wire & Failure to Identify Damaged Components + (00:03:41, 17 December 2024)
- ML20065S582 + (00:03:42, 17 December 2024)
- ML20065S579 + (00:03:43, 17 December 2024)
- 05000369/LER-1990-031, :on 901116,train B of Control Room Ventilation Sys Declared Inoperable While Train a Inoperable for Sys Alignments.Caused by Differential Pressure Switch Not Sensing Flow.Switch Replaced + (00:03:45, 17 December 2024)
- 05000369/LER-1990-032, :on 901117,unit Experienced Turbine Trip, Followed by Reactor Trip.Cause Unknown.Control Room Personnel Initiated Turbine Exhaust Hood Spray + (00:03:47, 17 December 2024)
- 05000328/LER-1990-016-01, :on 901117,determined That Unit 2 Operated in Noncompliance W/Tech Spec 2.2.1 & LCO 3.3.1 Because of Nonconservative Calibr of Nis Intermediate Range Channels. Caused by Procedural Inadequacies + (00:03:50, 17 December 2024)
- ML20065S552 + (00:03:51, 17 December 2024)
- 0CAN129005, Requests Extension Until 910415 to Submit Revised Response to NRC 901010 SER on Station Blackout Rule + (00:03:52, 17 December 2024)
- 05000277/LER-1990-036, :on 901115,excessive Reactor Coolant Cooldown Occurred While Placing Shutdown Cooling Mode of RHR in Svc. Caused by Incorrect Procedural Guidance.Appropriate Operating Procedures Will Be Revised + (00:03:58, 17 December 2024)
- ML20065S521 + (00:04:03, 17 December 2024)
- 05000277/LER-1990-037, :on 901119,discovered That TS Violation Occurred as Result of Not Taking Appropriate LCO Actions When IRM Channels for RPS a Trip Circuit Fell Below Required Amount.Caused by Procedural Weakness + (00:04:05, 17 December 2024)
- 05000387/LER-1982-029-03, /03L-0:on 820923,HV161108A2 Isolation Valve Failed to Close When Remotely Actuated.Caused by Induced Voltage in Control Circuitry of Solenoid Valve.Appropriate Conductor Grounded & Design Change Initiated to Prevent Recurren + (00:04:07, 17 December 2024)
- ML20065S514 + (00:04:08, 17 December 2024)
- ST-HL-AE-3620, Describes Error Found in Const of E-field Sys Used as Part of Protected Area Boundary,Instrusion Detection Sys. Reconfigured E-field Zone Modified Per Correct free-standing E-field Specs.Tabulations of E-field Zones Encl + (00:04:09, 17 December 2024)
- 05000247/LER-1982-040-32, /03L-0:on 820915,reactor Containment Fan Cooler Unit 22 Removed from Svc Due to Increased Svc Water Leakage Causing Addl Burden on Liquid Waste Disposal Sys.Cause Unknown.Investigation Continuing + (00:04:10, 17 December 2024)
- 05000354/LER-1990-028-02, :on 901117,turbine Trip on Moisture Separator High Level Resulted in Reactor Scram Due to Moisture Separator Level Control Sys Malfunction.Troubleshooting of Level Control Sys Conducted + (00:04:13, 17 December 2024)
- 05000247/LER-1982-040, Forwards LER 82-040/03L-0 + (00:04:14, 17 December 2024)
- ML20065S493 + (00:04:14, 17 December 2024)
- 05000369/LER-1990-029-01, :on 901109,potential for Loss of RHR Train Discovered.Caused by Design Deficiency Re One Pump W/ Stronger Developed Head to Cause Weaker Parallel Pump to Deadhead & Fail.Caution Added to Procedure + (00:04:16, 17 December 2024)
- 05000354/LER-1990-027-02, :on 901116,discovered That Analysis of Offgas Sys Sample for Hydrogen Content Not Performed within 4 H as Required by Tech Specs.Caused by Personnel Error.Technician Counseled & Disciplinary Action Taken + (00:04:18, 17 December 2024)
- 05000387/LER-1982-029, Forwards LER 82-029/03L-0 + (00:04:19, 17 December 2024)
- 05000387/LER-1982-030-03, /03L-0:on 820922,when 250-volt Battery Charger for Dc Power Source Was Placed in Svc,Associated Capacitor Self Destructed.Old Style Capacitor Replaced.Design Mod Initiated + (00:04:21, 17 December 2024)
- 05000277/LER-1990-035, :on 901115,discovered That Multiple Safety Sys Could Be Inoperable as Result of 4 Kv Emergency Bus Undervoltage Relays Outside Acceptable Calibr Limits.Caused by Inadequate Design.Relays Modified + (00:04:23, 17 December 2024)
- ML20065S470 + (00:04:24, 17 December 2024)
- 05000387/LER-1982-030, Forwards LER 82-030/03L-0 + (00:04:25, 17 December 2024)
- 05000244/LER-1982-021-03, /03L-0:on 820923,containment Spray Pumps & Sodium Hydroxide Additive Sys,Check Valve 862 B Failed to Promptly Close.Valve Repairs Consisted of Machining Seat & Disc Assembly + (00:04:26, 17 December 2024)
- 05000244/LER-1982-021, Forwards LER 82-021/03L-0 + (00:04:28, 17 December 2024)
- ML20065S437 + (00:04:28, 17 December 2024)
- ML20065S432 + (00:04:30, 17 December 2024)
- ML20065S431 + (00:04:31, 17 December 2024)
- 05000247/LER-1982-041-03, /03L-0:on 820919,operator Observed Excessive Containment Weld Channel/Penetration Pressurization Air Flow.Valve SOV 1279 Found Leaking to Atmosphere.Valve Will Be Replaced During Current Refueling Outage + (00:04:33, 17 December 2024)
- 05000247/LER-1982-041, Forwards LER 82-041/03L-0 + (00:04:35, 17 December 2024)
- ML20065S404 + (00:04:35, 17 December 2024)
- LIC-94-0098, Responds to NRC Re Violations Noted in Insp Rept 50-285/94-07.Corrective Action:Additional Emphasis on RP Requirements Are Now Included in Initial GET as Well as Requalification GET + (00:04:36, 17 December 2024)
- ST-HL-AE-4787, Forwards Response to Violations Noted in Insp Rept 50-498/94-11.Corrective Actions:Internal Investigation Performed by Licensee & Concluded That No Suggestion Individual Deliberately Sought to Deceive NRC + (00:04:36, 17 December 2024)
- ML20065S379 + (00:04:37, 17 December 2024)
- ML20065S373 + (00:04:38, 17 December 2024)
- ML20065S378 + (00:04:38, 17 December 2024)
- ML20065S371 + (00:04:39, 17 December 2024)
- ML20065S361 + (00:04:39, 17 December 2024)
- NRC-94-0038, Responds to NRC Re Violations Noted in Insp Rept 50-341/94-05.Corrective Actions:Lessons Learned Meeting Was Held W/All Involved Organizations Present to Discuss Event + (00:04:40, 17 December 2024)
- ML20065S359 + (00:04:41, 17 December 2024)
- ML20065S357 + (00:04:42, 17 December 2024)
- 05000387/LER-1982-028-03, /03L-0:on 820922,fire Started in Motor Control Ctr.Caused by Personnel Inadvertently Grounding Live Bus Bar.Fire Extinquished,Bus Bar Cleaned,Rebuilt & Tested & Personnel Counseled + (00:04:44, 17 December 2024)
- 2CAN059405, Monthly Operating Rept for Apr 1994 for ANO Unit 2 + (00:04:45, 17 December 2024)
- ML20065S353 + (00:04:45, 17 December 2024)
- ML20065S351 + (00:04:46, 17 December 2024)